Data Sheet

Contact specification
Ratings and utilization categories according to EN61095:2009
Type Utilization category
AC-7a AC-7b AC-7c
Rated current
(A)
Rated electrical
life (Cycles)
Rated current
(A)
Rated electrical
life (Cycles)
Rated current
(A)
Rated electrical
life (Cycles)
22.32….1xx0 (AgNi contacts) 25
70·10
3
(NO)
10 30·10
3
30·10
3
(NC)
22.32….4xx0 (AgSnO
2
contacts) 25 30·10
3
10 30·10
3
10 30·10
3
22.34….1xx0 (AgNi contacts) 25
150·10
3
(NO)
10 30·10
3
100·10
3
(NC)
22.34….4xx0 (AgSnO
2
contacts) 25 30·10
3
10 30·10
3
10 30·10
3
22.44….4xx0 40 100·10
3
22 150·10
3
22.64….4xx0 63 100·10
3
30 150·10
3
Utilization category: AC-7a = Slightly inductive loads (cosϕ=0.8)
AC-7b = Motor loads; (cosϕ=0.45, I
making=6xIbreaking)
AC-7c = Compensated electric discharge lamps (cosϕ=0.9, C=10mF/A)
H 22 - Maximum DC1 breaking capacity - Type 22.32/22.34 H 22 - Maximum DC1 breaking capacity - Type 22.44/22.64
DC breaking current (A)
DC voltage (V)
DC breaking current (A)
DC voltage (V)
type 22.64
type 22.44
When switching a resistive load (DC1) having voltage and current values under the curve, an electrical life of ≥100·10
3
can be expected.
In the case of DC13 loads, the connection of a diode in parallel with the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Coil specifications
AC/DC version data (type 22.32)
Nominal
voltage
Coil
code
Operating range Rated coil
consumption
U
N
U
min
U
max
I
N
at U
N
(AC)
V V V mA
12 0.012 9.6 13.2 165
24 0.024 19.2 26.4 83
48 0.048 38.4 52.8 42
60 0.060 48 66 33
120
(110…125) 0.120 88 138 16.5
230
(230…240 AC)
(220 DC)
0.230
184 (AC)
176 (DC)
264 (AC)
242 (DC)
8.7
AC/DC version data (type 22.44 / 22.64)
Nominal
voltage
Coil
code
Operating range Rated coil
consumption
U
N
U
min
U
max
I
N
at U
N
(AC)
V V V mA
12 0.012 10.2 13.2 417
24 0.024 20.4 26.4 208
120
(110…125)
0.120 102 138 41
230
(230…240 AC)
(220 DC)
0.230 196
264 (AC)
242 (DC)
21
AC/DC version data (type 22.34)
Nominal
voltage
Coil
code
Operating range Rated coil
consumption
U
N
U
min
U
max
I
N
at U
N
(AC)
V V V mA
12 0.012 9.6 13.2 165
24 0.024 19.2 26.4 83
48 0.048 38.4 52.8 42
60 0.060 48 66 33
120
(110…125) 0.120 88 138 16.5
230
(230…240 AC)
(220 DC)
0.230
184 (AC)
176 (DC)
264 (AC)
242 (DC)
8.7
R 22 - Coil operating range v ambient temperature
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
8
VII-2018, www.findernet.com
L
22 SERIES
Modular contactors 25- 40- 63A
22
SERIES