Data Sheet

Technical data
Insulation 22.32/22.34 22.44/22.64
Rated insulation voltage VAC 250 440 440
Pollution degree 3* 2 3
Insulation between coil and contact set
Type of insulation Reinforced Reinforced
Overvoltage category III III
Rated impulse voltage kV (1.2/50µs) 6 4
Dielectric strength VAC 4000 2000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50µs) 4 4
Dielectric strength VAC 2500 2000
Insulation between open contacts NO contact NC contact NO/NC contacts
Contact gap mm 3 1.5 3
Overvoltage category III II III
Rated impulse voltage kV (1.2/50µs) 4 2.5 4
Dielectric strength VAC/kV (1.2/50µs) 2500/4 2000/3 2000/3
* Only for versions without Auto-On-Off selector. For versions with Auto-On-Off selector pollution degree 2 applies.
Conducted disturbance immunity
Fast transients (burst 5/50ns, 5kHz) at coil terminals according to
EN61000-4-4 Level 4 (4kV) Level 2 (2kV)
Voltage pulses (surge 1.2/50µs) at supply terminals (differential mode)
according to EN61000-4-5 Level 4 (4kV) Level 2 (2kV)
Short circuit protection 22.32 / 22.34 22.44 22.64
Rated conditional short circuit current kA 3 3 3
Back-up fuse A 32 (gL/gG type) 63 80
Terminals Solid and stranded cable
22.32 / 22.34 22.44 / 22.64
Max. wire size – contact terminals mm
2
1x6 / 2x4 1x25 (solid) - 1x16 (stranded)
AWG 1x10 / 2x12 1x4 (solid) - 1x6 (stranded)
Max. wire size – coil terminals mm
2
1x4 / 2x2.5 1x2.5
AWG 1x12 / 2x14 1x14
Min. wire size – contact and coil terminals mm
2
1x0.2 1x1 (coil) - 1x1.5 (contacts)
AWG 1x24 1x18 (coil) - 1x16 (contacts)
Screw torque Nm 0.8
1.2 (coil terminals) -
3.5 (contact terminals)
Wire strip length mm 9 10
Other data 22.32 22.34 22.44 22.64
Vibration resistance (10…150)Hz g 4 4 3 3
Shock resistance g 10 10 15 15
Power lost to the environment without contact current W 2 2 5 5
with rated current W 4.8 6.3 17 37
NOTE
22.32/22.34: It is suggested an air gap of 9mm between adjacent relays for installations and working conditions close to the limit (that is, ambient
temperature >40°C, coil operated for a prolonged period of time, all contacts loaded with current >20A).
22.44/22.64: The maximum ambient temperature with 3 adjacent contactors is +40°C; when more than 3 contactors are installed, it is necessary an air
gap of 9mm.
With 2 adjacent contactors the maximum ambient temperature is +55°C; when more than 2 contactors are installed, it is necessary an air
gap of 9mm.
7
VII-2018, www.findernet.com
L
22
SERIES
22 SERIES
Modular contactors 25- 40- 63A