Data Sheet

9
VI-2014, www.findernet.com
Auxiliary modules
Mechanically linked contacts
according to Annex L of EN 60947-5-1
Contact specification
Contact configuration 2 NO 1 NO + 1 NC 2 NO 1 NO + 1 NC
Conventional free air thermal current I
th
A6 6
Rated power AC15 (230 V) VA 700 700
Electrical life at rated load cycles 30 x 10
3
30 x 10
3
Contact material AgNi AgNi
Short circuit protection
Rated conditional short circuit current kA 1 1
Back-up fuse A 6 (gL/gG type) 6 (gL/gG type)
Terminals Solid and stranded cable Solid and stranded cable
Max. wire size mm
2
1 x 4 / 2 x 2.5 1 x 2.5
AWG 1 x 12 / 2 x 14 1 x 14
Min. wire size mm
2
1 x 0.2 1 x 1
AWG 1 x 24 1 x 18
Screw torque Nm 0.8 0.6
Wire strip length mm 9 9
Power lost to the environment
without contact current W
with rated current W 0.5 0.5
Approvals (according to type)
Type of contactor Type 22.32 Type 22.44
Type 22.34 Type 22.64
22.32 + 022.33/022.35
22.34 + 022.33/022.35
22.44 + 022.63/022.65
22.64 + 022.63/022.65
022.33 022.35 022.63 022.65
NOTE: it is not possible to assembly the auxiliary module on 22.32.0.xxx.x4x0 (2 NC versions).
22 Series - Modular contactors 25 - 40 - 63 A
22
SERIES
L