Coil specifications - 1 Pole 6A Electromechnical Relay
Coil data sensitive DC, 1 Pole Coil data AC/DC, 1 Pole
Nominal
voltage
Coil
code
Operating range
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
I at U
N
P at U
N
V V V mA W
6 7.006 4.8 7.2 35 0.2
12
7.012
9.6 14.4 15.2
0.2
24
7.024
19.2 28.8 10.4
0.3
48
7.048
38.4 57.6 6.3
0.3
60
7.060
48 72 7
0.4
Nominal
voltage
Coil
code
Operating range
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
I at U
N
P at U
N
V V V mA VA/W
12 0.012 9.6 13.2 16 0.2/0.2
24 0.024 19.2 26.4 12 0.3/0.2
48 0.048 38.4 52.8 6.9 0.3/0.3
60
0.060
48 66 7 0.5/0.5
110…125
0.125
88 138 5(*) 0.6/0.6(*)
220…240
0.240
176 264 4(*) 1/0.9(*)
(*) Rated coil consumption and power consumption values relate to
U
N
=125 and 240V.
Coil data AC, 1 Pole (indicated for max ambient temperature +70°C)
Nominal
voltage
Coil
code
Operating range
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
I
at U
N
P at U
N
V V V mA VA/W
(230…240) AC 8.240 184 264 3 0.7/0.3
Coil data, leakage current suppression types, 1 Pole
Nominal
voltage
Coil
code
Operating range
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
I
at U
N
P at U
N
V V V mA VA/W
(110…125) AC/DC 3.125 94 138 8(*) 1/1(*)
(230…240) AC 3.240
184
264 7(*) 1.7/0.5(*)
(*) Rated coil consumption and power consumption values relate to U
N
=125 and 240V.
The 38 Series interface modules (supply version 3) have built-in
leakage current suppression to address industry concerns of
the contacts not dropping-out when there is residual current in
the
circuit; at (110…125)VAC and (230…240)VAC.
This problem can occur, for example, when connecting
the interface modules to PLC‚s with triac outputs or when
connecting via relatively long cables.
Coil specifications - 1 Pole 16A and 2 Pole 8A Electromechanical Relay
Coil data sensitive DC, 1 Pole 16A and 2 Pole 8A
Nominal
voltage
Coil
code
Operating range
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
I
at U
N
P at U
N
V V V mA W
12 7.012 9.6 14.4 41 0.5
24 7.024 19.2 28.8 19.5 0.5
60 7.060 48 72 8 0.5
Coil data AC/DC, 1 Pole 16A and 2 Pole 8A
Nominal
voltage
Coil
code
Operating range
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
I
at U
N
P at U
N
V V V mA W
24 0.024 19.2 26.4 20 0.5/0.5
60 0.060 48 66 7.1 0.5/0.5
110…125 0.125 88 138 4.6 0.6/0.6
220…240 0.240 184 264 3.8 0.9/0.9
Coil data AC, 1 Pole 16A and 2 Pole 8A
Nominal
voltage
Coil
code
Operating range
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
I
at U
N
P at U
N
V V V mA VA/W
230…240 8.230 184 264 5.3 1.2/0.6
Coil specification - 1 & 2 Pole Electromagnetic Relays
R 38 - DC coil operating range v ambient temperature
1 Pole and 2 Pole
1
2
3
4
1 - Max. permitted coil voltage at nominal load (DC coil).
2 - Max. permitted coil voltage at nominal load (AC/DC coils U≤60V).
3 - Max. permitted coil voltage at nominal load (AC/DC coils U>60V).
4 - Min pick-up voltage with coil at ambient temperature.
9
38
SERIES
38 SERIES
Relay interface modules - Technical data