Data Sheet

X-2017, www.findernet.com
B
Technical data - Solid State Relays
Other data 38.81/38.91 38.31/38.41
Power lost to the environment without output current W 0.25 (24VDC) 0.5
with rated current W 0.4 2.2 (DC output)/3 (AC output)
Terminals 38.81 38.91
Wire strip length mm 10 10
Screw torque Nm 0.5
Max. wire size solid cable stranded cable solid cable stranded cable
mm
2
1x2.5 / 2x1.5 1x2.5 / 2x1.5 1x2.5 1x2.5
AWG 1x14 / 2x16 1x14 / 2x16 1x14 1x14
38.31 38.41
Wire strip length mm 10 10
Screw torque Nm 0.5
Max. wire size solid cable stranded cable solid cable stranded cable
mm
2
1x2.5 / 2x1.5 1x2.5 / 2x1.5 1x2.5 1x2.5
AWG 1x14 / 2x16 1x14 / 2x16 1x14 1x14
Input specifications - Solid State Relays type 38.81 and 38.91 - 6.2mm wide
Input data DC Input data AC/DC
Nominal
voltage
Supply
code
Operating range Release
voltage
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
U
I
at U
N
P
V V V V mA W
6 7.006 5 7.2 2.4 7 0.2
24 7.024 16.8 30 10 10.5 0.3
60 7.060 35.6 72 20 6.5 0.4
Nominal
voltage
Supply
code
Operating range Release
voltage
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
U
I
at U
N
P
V V V V mA VA/W
110…125
0.125 88 138 22 5.5* 0.7/0.7
220…240
0.240 184 264 44 3.5* 1/0.9
(*) Rated coil consumption and power consumption values relate to
U
N
=125 and 240V.
Input data - Leakage current suppression types
Nominal
voltage
Supply
code
Operating range Release
voltage
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
U
I
at U
N
P at U
N
V
V V V mA W
110…125 AC/DC
3.125 94 138 44 8(*) 1/1(*)
230…240 AC
3.240 184 264 72 6.5(*)
1.6/0.6(*)
(*) Rated coil consumption and power consumption values relate to
U
N
=125 and 240V.
The 38 Series interface modules (supply version 3) have built-in
leakage current suppression to address industry concerns of the
contacts not dropping-out when there is residual current in the circuit;
at (110…125)VAC and (230…240)VAC.
This problem can occur, for example, when connecting the interface
modules to PLC‚s with triac outputs or when connecting via relatively
long cables.
Input specification - Solid State Relay types 38.31 and 38.41 - 14mm wide
Input data DC Input data AC/DC
Nominal
voltage
Supply
code
Operating range
Release
voltage
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
U
I
at U
N
P
V V V V mA W
12
7.012 9.6 18 5 9 0.2
24
7.024 16.8 30 5 12 0.3
Nominal
voltage
Supply
code
Operating range
Release
voltage
Rated coil
consumption
Power
consumption
U
N
U
min
U
max
U
I
at U
N
P
V V V V mA W
24
0.024 16.8 30 9 16.5 0.3
10
38 SERIES
Relay interface modules - Technical data
38