Data Sheet

X-2017, www.findernet.com
B
1 Pole - 6A electromechanical relay
interface modules, 6.2mm wide.
Ideal interface for PLC and electronic systems
Sensitive DC coil or AC/DC coil versions
Integral coil indication and protection circuit
Instant ejection of relay using plastic retaining
clip
UL Listing (certain relay/socket combinations)
35mm rail (EN60715) mounting
38.51/38.51.3
Screw terminal
38.61/38.61.3
Screwless terminal
*
Special version for max ambient temperature +70°C.
** Maximum ambient temperature limitations apply
in the case of adjacent mounting of modules, where
the coil is energised with a duty cycle of
≥50 % or where the ON time exceeds 1 hour:
+55°C: applies to groups limited to 2 adjacent
modules and where each group is separated by an
air gap ≥6.2mm.
+30°C: applies to a group of more than 2 adjacent
modules.
For outline drawing see page 13
38.51/61 38.51.3/38.61.3
1 pole electromechanical relay
Screw terminal and screwless terminal
35mm rail (EN60715) mounting
Leakage current suppression
1 pole electromechanical relay
Screw terminal and screwless terminal
35mm rail (EN60715) mounting
Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT)
Rated current/
Maximum peak current A 6/10 6/10
Rated voltage/
Maximum switching voltage VAC 250/400 250/400
Rated load AC1 VA 1500 1500
Rated load AC15 (230VAC) VA 300 300
Single phase motor rating (230VAC) kW 0.185 0.185
Breaking capacity DC1: 30/110/220V A 6/0.2/0.12 6/0.2/0.12
Minimum switching load mW (V/mA) 500 (12/10) 500 (12/10)
Standard contact material AgNi AgNi
Coil specification
Nominal voltage (U
N
) VAC/DC 12 - 24 - 48 - 60 - (110…125) - (220…240)** (110…125)
VAC (230…240)* (230…240)
VDC 6 - 12 - 24 - 48 - 60 (non polarized)
Rated power AC/DC VA (50Hz)/W See page 9 1/1 0.5/—
Operating range AC/DC (0.8…1.1)U
N
(94…138)V
AC (184…264)V (184…264)V
DC (0.8…1.2)U
N
Holding voltage AC/DC 0.6U
N
/0.6U
N
0.6U
N
/0.6U
N
Must drop-out voltage AC/DC 0.1U
N
/0.05U
N
44 V 72 V
Technical data
Mechanical life AC/DC cycles 10·10
6
10·10
6
Electrical life at rated load AC1 cycles 60·10
3
60·10
3
Operate/release time ms 5/6 5/6
Insulation between coil
and contacts (1.2/50µs) kV 6 (8mm) 6 (8mm)
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature range (U
N
≤60V/>60V) °C –40…+70/–40…+55 —/–40…+55
Protection category
IP 20 IP 20
Approvals relay (according to type)
1
38
SERIES
38 SERIES
Relay interface modules - 1 Pole 6A EMR