Data Sheet

30
X-2017, www.findernet.com
39 SERIES
Relay interface modules 0.1- 2- 6A
39
SERIES
B
Accessories
093.63
Approvals
(according to type):
093.63.0.024
093.63.8.230
Output fuse module for 39.31/30/81/80/61/60/91/90 types 093.63 093.63.0.024 093.63.8.230
- For 5x20mm fuses up to 6A, 250V
- Type 093.63 - Easy visibility of the fuse condition through the window
- Type 093.63.0.024 - (6…24)VAC/DC with LED fuse status indicator
- Type 093.63.8.230 - (110…240)VAC with LED fuse status indicator
- Quick connection to socket
Notes
Safety: Because the output circuit can be reinstated (point 3 below), even with the fuse removed, it is important not to
consider the removal of the fuse as a “safety disconnect. Always isolate elsewhere before working on the circuit.
UL: According to UL508A, the fuse module cannot be installed in power circuits (in which it is mandatory that a fuse certified
according to UL category JDDZ be fitted). However, where the MasterInterface is connected as an output interface to a PLC
no such restrictions apply, and the fuse module can be usefully employed.
Type 093.63
Type 093.63.0.24 / 093.63.8.230
Multi-state fuse module
0. As delivered, the socket comes without a fuse module. However, the absent fuse is internally replaced with an electrical link
- which allows the interface relay to be used without a fuse module.
In this state, the peg/indicator is visually hidden and the connection is protected by a special cap.
1. With fuse module inserted after removing the cap, the fuse is positioned electrically in series with the common output
terminal of the interface module (11 for EMR versions, 13+ for SSR versions, 15 for EMR timer, 15+ for SSR timer).
This state is indicated by the peg/indicator.
2. If the fuse module is extracted (for example; because the fuse element has blown) the output circuit will be locked open, as
this will generally be the “safe option.
This state is indicated by the peg/indicator.
3. In order to reinstate the output circuit it is necessary to either re-insert the fuse module (complete with functional fuse), or
alternatively, return the peg/indicator to position 0 by gently applying pressure in the direction of the arrow.