Data Sheet

8
X-2017, www.findernet.com
39 SERIES
Relay interface modules 0.1- 2- 6A
39
SERIES
B
MasterPLUS - EMR
1 Pole interface modules, 6.2mm wide, ideal
for PLC and electronic systems
Accepts output fuse module 093.63,
093.63.0.024, 093.63.8.230 (for5x20 mm
fuses) for quick and easy load protection, see
page 30
Common connection possible with optional
jumper links (terminals A1, A2 and 11)
UL Listing (certain relay/socket combinations)
39.31/39.61 39.31.3/39.61.3
6A electromechanical relay
6 to 125VAC/DC, 125 and 220VDC, 230VAC,
24…240VAC/DC supply
Screw terminal and push-in terminal
35mm rail (EN60715) mounting
6A electromechanical relay
Leakage current suppression version,
125VAC/DC and 230VAC supply
Screw terminal and push-in terminal
39.31/39.31.3
Screw terminal
39.61/39.61.3
Push-in terminal
Fuse module
093.63
093.63.0.024
093.63.8.230
Fuse module
093.63
093.63.0.024
093.63.8.230
For outline drawing see page 25, 26
Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT)
Rated current/
Maximum peak current A 6/10 6/10
Rated voltage/
Maximum switching voltage VAC 250/400 250/400
Rated load AC1 VA 1500 1500
Rated load AC15 (230VAC) VA 300 300
Single phase motor rating (230VAC) kW 0.185 0.185
Breaking capacity DC1: 30/110/220V A 6/0.2/0.12 6/0.2/0.12
Minimum switching load mW (V/mA) 500 (12/10) 500 (12/10)
Standard contact material AgNi AgNi
Supply specification
Nominal voltage (U
N
) VAC/DC 6 - 12 - 24 - 60 - 110…125 - 24…240 110…125
VAC (50/60Hz) 220…240 220…240
VDC 110…125 - 220
Rated power VA (50Hz)/W See page 20 See page 20
Operating range (0.8…1.1)U
N
(0.8…1.1)U
N
Holding voltage 0.6U
N
0.6U
N
Must drop-out voltage 0.1U
N
0.3U
N
Technical data
Mechanical life AC/DC cycles 10·10
6
10·10
6
Electrical life at rated load AC1 cycles 60·10
3
60·10
3
Operate/release time ms 5/6 5/6
Insulation between coil
and contacts (1.2/50μs) kV 6 (8mm) 6 (8mm)
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature range °C –40…+70 (+55 for 220VDC) –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)