Datasheet

18
39 Series - Timed interface modules
Functions
NO contact/output
Supply voltage
LED
OFF
ON
ON
ON
Times scales
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
(0.1...3)s
(3...60)s
(1...20)min
(0.3...6)h
Timer specifications
Open
Open
Open (timing to close in progress)
Closed
EMC specifications
Type of test Reference standard
Electrostatic discharge
contact discharge EN 61000-4-2
4 kV
air discharge EN 61000-4-2 8 kV
Radio-frequency electromagnetic field
(80 ÷ 1,000 MHz) EN 61000-4-3 10 V/m
(1,400 ÷ 2,700 MHz) EN 61000-4-3 10 V/m
Fast transients (burst) (5-50 ns, 5 and 100 kHz)
on Supply terminals EN 61000-4-4 4 kV
on control signal terminals EN 61000-4-4 4 kV
Surges (1.2/50 s) on supply and control
signal terminals
common mode EN 61000-4-5 2 kV
differential mode EN 61000-4-5 0.8 kV
Radio-frequency common mode
(0.15 ÷ 80 MHz)
on Supply terminals EN 61000-4-6 10 V
on control signal terminals EN 61000-4-6 3 V
Radiated and conducted emission EN 55022 class B
Other data
Bounce time (EMR) : NO/NC ms 1/6
Vibration resistance (EMR,10..55 Hz): NO/NC
g
10/15
Power lost to the environment
without contact current
W 0.3
with rated current W 0.8
Terminals
Wire strip length mm 10
Screw torque Nm 0.5
Solid and stranded cable
Max. wire size
mm
2
1 x 2.5/2 x 1.5
AWG 1 x 14/2 x 16
Min. wire size
mm
2
1 x 0.2
AWG 1 x 24
XII-2012, www.findernet.com