Datasheet

7
39.30 39.30.3
Features
1 Pole interface modules, 6.2mm wide, ideal for
PLC and electronic systems
Accepts output fuse module 093.63 (for 5 x
20 mm fuses) for quick and easy load
protection, see page 22
Common connection possible with optional
jumper links (terminals A1, A2 and 13+)
0.1 or 2 A solid state relay
24 - 125 VAC/DC, 6 to 220 VDC and 230
VAC supply
35 mm rail (EN 60715) mounting
0.1 or 2 A solid state relay
Leakage current suppression version, 125
and 230 VAC supply
For outline drawing see page 20
39 Series - Relay interface modules 0.1 - 2 - 6 A
39.30.x.xxx.9024 39.30.x.xxx.7048 39.30.x.xxx.8240 39.30.3.xxx.9024 39.30.3.xxx.7048 39.30.3.xxx.8240
1 NO (SPST-NO) 1 NO (SPST-NO)
2/20 DC 0.1/0.5 DC 2/40 AC 2/20 DC 0.1/0.5 DC 2/40 AC
24/33 DC 48/60 DC 240/275 AC 24/33 DC 48/60 DC 240/275 AC
(1.5…24) DC (1.5…48)DC (12…240) AC (1.5…24) DC (1.5…48)DC (12…240) AC
1 0.05 22 1 0.05 22
0.001 0.001 1.5 0.001 0.001 1.5
0.12 1 1.6 0.12 1 1.6
24 - 110…125
220...240 110…125 - 220…240
6 - 12 - 24 - 60 - 110…125 - 220
See page 17 See page 17
(0.8…1.1) U
N
(0.8…1.1) U
N
0.1 U
N
0.3 U
N
0.2/0.6 0.04/0.11 12/12 0.2/0.6 0.04/0.11 12/12
2,500 2,500
–20…+55 –20…+55
IP20 IP20
39.30 / 39.30.3
Screw terminal
MasterPLUS - SSR
Fuse module
093.63
Output specification (SSR)
Contact configuration
Rated current/Maximum peak current (10 ms)
Rated voltage/Maximum blocking voltage
Switching voltage range
Minimum switching current
Max. “OFF-state” leakage current
Max. “ON-state” voltage drop
Supply specification
Nominal voltage (U
N
)
Rated power
Operating range
Must drop-out voltage
Technical data
Operate/release time
Dielectric strength between input/output
Ambient temperature range
Protection category
Approvals relay (according to type)
A
V
V
mA
mA
V
VAC/DC
VAC (50/60 Hz)
VDC
VA (50 Hz)/W
ms
VAC
°C
XII-2012, www.findernet.com