Data Sheet

15
Technical data
Contact specification (EMR)
F 39 - Electrical life (AC) v contact current H 39 - Maximum DC1 breaking capacity
When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of 60·10
3
can be expected.
In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Cycles
Resistive load - cosϕ = 1
Inductive load - cosϕ = 0.4
DC voltage (V)
DC breaking current (A)
Insulation according to EN 61810-1
Nominal voltage of supply system VAC 230/400
Rated insulation voltage VAC 250 400
Pollution degree 3 2
Insulation between coil and contact set
Type of Insulation Reinforced
Overvoltage category III
Rated impulse voltage kV (1.2/50) µs 6
Dielectric strength VAC 4,000
Insulation between open contacts (EMR)
Type of disconnection Micro-disconnection
Dielectric strength VAC/kV (1.2/50) µs 1,000/1.5
Conducted disturbance immunity
U
N
≤ 60 V U
N
= 125 V U
N
= 230 V
Fast transients (burst 5/50 ns, 5 kHz) according to EN 61000-4-4
at supply terminals
kV 4 4 4
Voltage pulses (surge 1.2/50 s) according to EN 61000-4-5 at
supply terminals (differential mode)
kV 0.8 2 4
Other data
Bounce time (EMR) : NO/NC ms 1/6
Vibration resistance (EMR,10..55 Hz): NO/NC
g
10/15
Power lost to the environment
without contact current
W 0.2 (24 V) – 0.4 (230 V)
with rated current W 0.6 (24 V) – 0.9 (230 V)
II-2014, www.findernet.com
Terminals
Screw terminal Push-in terminal
Wire strip length mm 10 8
Screw torque Nm 0.5
Solid and stranded cable Solid and stranded cable
Max. wire size mm
2
1 x 2.5/2 x 1.5 1 x 2.5
AWG 1 x 14/2 x 16 1 x 14
Min. wire size mm
2
1 x 0.2 1 x 0.2
AWG 1 x 24 1 x 24
B
39 Series - Relay interface modules - Technical data
39
SERIES