Data Sheet

Coil specifications - Electromechnical Relay
Coil data DC, type 39.31/61
Coil data AC/DC, type 39.11/21/31/41/01/51/61/71
Coil data AC, type 39.11/21/31/41/01/51/61/71
Coil data leakage current suppression versions, type 39.31.3/61.3
Coil data AC/DC timer, type 39.81/91
16
The 39 Series interface modules (supply version 3) have built-
in leakage current suppression to address industry concerns
of the contacts not dropping-out when there is residual current
in the circuit; at (110...125)VAC/DC and (230...240)VAC.
This problem can occur, for example, when connecting the
interface modules to PLC‚s with triac outputs or when
connecting via relatively long cables.
(1)
60 VAC/DC for type 39.31/61 only
Nominal
Voltage
Coil code Operating range
Must drop-out
voltage
Rated input
current at U
N
Rated power
U
N
U
min
U
max
U
r
I
N
at U
N
V V V V
mA
W
125
(110...125)
7.125 88 138 12.5 4.6 0.6
220 7.220 176 242
22 3.0 0.6
Nominal
Voltage
Coil code Operating range
Must drop-out
voltage
Rated input
current at U
N
Rated power
U
N
U
min
U
max
U
r
I
N
at U
N
V V V V
mA
VA/W
6 0.006 4.8 6.6
0.6 35 0.2/0.2
12 0.012 9.6 13.2
1.5 15 0.2/0.2
24 0.024 19.2 26.4 2.4 11 0.25/0.25
60
(1)
0.060 48 66 6.0 5.7 0.35/0.35
125
(110…125)
0.125 88 138 12.5 5.6 0.7/0.7
Nominal
Voltage
Coil code Operating range
Must drop-out
voltage
Rated input
current at U
N
Rated power
U
N
U
min
U
max
U
r
I
N
at U
N
V V V V
mA
VA/W
230
(230...240)
8.230 184 264 23 4.3 1/0.4
Nominal
Voltage
Coil code Operating range
Must drop-out
voltage
Rated input
current at U
N
Rated power
U
N
U
min
U
max
U
r
I
N
at U
N
V V V V
mA
VA/W
125
(110...125)
3.125 88 138 44 8.4 1.1/1
230
(230...240)
3.230 184 264 72 5.9 1.4/0.5
Nominal
Voltage
Coil code
Operating range
(AC/DC)
Must drop-out
voltage
Rated input current at U
N
Rated power
at U
N
U
N
U
min
U
max
U
r
DC AC DC AC
V V V V
mA mA
W VA/W
12 0.012 9.6 13.2
1.2 15 23 0.2 0.3/0.2
24 0.024 19.2 26.4 2.4 11 19 0.25 0.4/0.3
II-2014, www.findernet.com
39
SERIE S
39 Series - Relay interface modules - Technical data
B