Data Sheet
IV-2018, www.findernet.com
3
A
46
SERIES
46 SERIES
Miniature industrial relays 8 to16A
1 & 2 CO industrial style power relays
For socket mount or direct connection via
Faston connectors
Type 46.52
- 2 CO 8A
Type 46.61
- 1 CO 16A
• AC coils & DC coils
• Available with: lockable test button,
mechanical indicator & LED indicator
• 8mm, 6kV (1.2/50μs) isolation, coil-contacts
• Cadmium free contacts
• 97 series 35 mm rail (EN 60715) Screw,
Screwless or Push-in terminals, and PCB mount
sockets
• Coil Indication and EMC suppression modules
99 series and Timer module 86.30 options
• Optional alternative mounting adaptors
• European Patent
46.52
32.8
29
12.4
20
4.75 0.5 4.75
6.5
46.61
46.52 46.61
• 2 CO 8A
• Plug-in/Solder terminals
• 1 CO 16A
• Plug-in/Faston 187
For UL ratings see:
“General technical information” page V
Contact specification
Contact configuration 2 CO (DPDT) 1 CO (SPDT)
Rated current/Maximum peak current A 8/15 16/25*
* With the AgSnO
2
material
the maximum peak current is
80A- 5ms on normally open
contact.
Rated voltage/
Maximum switching voltage VAC 250/440 250/440
Rated load AC1 VA 2000 4000
Rated load AC15 (230VAC) VA 350 750
Single phase motor rating (230VAC) kW 0.37 0.55
Breaking capacity DC1: 30/110/220V A 6/0.5/0.15 12/0.5/0.15
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi
Coil specification
Nominal voltage (U
N
) VAC (50/60Hz) 12 - 24 - 48 - 110 - 120 - 230 - 240
VDC 12 - 24 - 48 - 110 - 125
Rated power VA/W 1.2/0.5 1.2/0.5
Operating range AC (0.8…1.1)U
N
(0.8…1.1)U
N
DC (0.73…1.1)U
N
(0.73…1.1)U
N
Holding voltage AC/DC 0.8U
N
/0.4U
N
0.8U
N
/0.4U
N
Must drop-out voltage AC/DC 0.2U
N
/0.1U
N
0.2U
N
/0.1U
N
Technical data
Mechanical life AC/DC cycles 10·10
6
10·10
6
Electrical life at rated load AC1 cycles 100·10
3
100·10
3
Operate/release time ms 10/3 15/5
Insulation between coil
and contacts (1.2/50μs) kV 6 (8mm) 6 (8mm)
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT II RT II
Approvals (according to type)