Data Sheet

VII-2018, www.findernet.com
B
1 CO relay interface modules,
15.8mm wide
Ideal interface for PLC and electronic systems
Type 48.P3
- 1 CO 10A
- Push-in terminals
Type 48.31
- 1 CO 10A
- Screw terminals
AC coils or DC sensitive coils
Supply status indication and EMC coil
suppression module as standard
Identification label
UL Listing (certain relay/socket combinations)
35mm rail (EN60715) mounting
Cadmium-free contact material
48.P3
Push-in terminal
48.31
Screw terminal
48.P3 48.31
1 CO 10A
Push-in terminals
1 CO 10A
Screw terminals
For outline drawing see page 11
Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT)
Rated current/Maximum peak current A 10/20 10/20
Rated voltage/
Maximum switching voltage VAC 250/400 250/400
Rated load AC1 VA 2500 2500
Rated load AC15 (230VAC) VA 500 500
Single phase motor rating (230VAC) kW 0.37 0.37
Breaking capacity DC1: 30/110/220V A 10/0.3/0.12 10/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi
Coil specification
Nominal voltage (U
N
) VAC (50/60Hz) 12 - 24 - 110 - 120 - 230 12 - 24 - 110 - 120 - 230
VDC 12 - 24 - 125 12 - 24 - 125
Rated power AC/sens. DC VA (50Hz)/W 1.2/0.5 1.2/0.5
Operating range AC (0.8…1.1)U
N
(0.8…1.1)U
N
sens. DC (0.73…1.5)U
N
(0.73…1.5)U
N
Holding voltage AC/DC 0.8U
N
/0.4U
N
0.8U
N
/0.4U
N
Must drop-out voltage AC/DC 0.2U
N
/0.1U
N
0.2U
N
/0.1U
N
Technical data
Mechanical life cycles 10·10
6
10·10
6
Electrical life at rated load AC1 cycles 200·10
3
200·10
3
Operate/release time ms 7/4 (AC) - 12/12 (DC) 7/4 (AC) - 12/12 (DC)
Insulation between coil
and contacts (1.2/50µs) kV 6 (8mm) 6 (8mm)
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
4
48 SERIES
Relay interface modules 10A
48
SERIES