Data Sheet

VII-2018, www.findernet.com
B
2 CO relay interface modules,
15.8mm wide
Ideal interface for PLC and electronic systems
Type 48.P5
- 2 CO 8A
- Push-in terminals
Type 48.52
- 2 CO 8A
- Screw terminals
AC coils or DC sensitive coils
Supply status indication and EMC coil
suppression module as standard
Identification label
UL Listing (certain relay/socket combinations)
35mm rail (EN60715) mounting
Cadmium-free contact material
48.P5
Push-in terminal
48.52
Screw terminal
48.P5 48.52
2 CO 8A
Push-in terminals
2 CO 8A
Screw terminals
48.52 / 72
48.52 / 72
For outline drawing see page 11
Contact specification
Contact configuration 2 CO (DPDT) 2 CO (DPDT)
Rated current/Maximum peak current A 8/15 8/15
Rated voltage/
Maximum switching voltage VAC 250/250 250/250
Rated load AC1 VA 2000 2000
Rated load AC15 (230VAC) VA 400 400
Single phase motor rating (230VAC) kW 0.3 0.3
Breaking capacity DC1: 30/110/220V A 8/0.3/0.12 8/0.3/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi
Coil specification
Nominal voltage (U
N
) VAC (50/60Hz) 12 - 24 - 110 - 120 - 230 12 - 24 - 110 - 120 - 230
VDC 12 - 24 - 125 12 - 24 - 125
Rated power AC/sens. DC VA (50Hz)/W 1.2/0.5 1.2/0.5
Operating range AC (0.8…1.1)U
N
(0.8…1.1)U
N
sens. DC (0.73…1.5)U
N
(0.73…1.5)U
N
Holding voltage AC/DC 0.8U
N
/0.4U
N
0.8U
N
/0.4U
N
Must drop-out voltage AC/DC 0.2U
N
/0.1U
N
0.2U
N
/0.1U
N
Technical data
Mechanical life cycles 10·10
6
10·10
6
Electrical life at rated load AC1 cycles 100·10
3
100·10
3
Operate/release time ms 7/4 (AC) - 12/12 (DC) 7/4 (AC) - 12/12 (DC)
Insulation between coil
and contacts (1.2/50µs) kV 6 (8mm) 6 (8mm)
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
5
48
SERIES
48 SERIES
Relay interface modules 8A