Datasheet
X-2017, www.findernet.com
B
2 CO forcibly guided contacts relay interface
modules,15.8mm wide
Type 48.12
- 2 CO 8A
- Screw terminals
• Relay with forcibly guided contacts according
to EN 61810-3 Type B (previously EN 50205)
• 35mm rail (EN60715) mounting
• Cadmium-free contact material
48.12
Screw terminal
48.12
• 2 CO 8A
• Forcibly guided contacts relay
• Screw terminals
48.12
According to EN 61810-3 only 1 NO and 1 NC
(11-14 and 21-22 or 11-12 and 21-24) shall be
used as forcibly guided contacts.
For outline drawing see page 9
Contact specification
Contact configuration 2 CO (DPDT)
Rated current/Maximum peak current A 8/15
Rated voltage/
Maximum switching voltage VAC 250/400
Rated load AC1 VA 2000
Rated load AC15 (230VAC) VA 500
Single phase motor rating (230VAC) kW 0.37
Breaking capacity DC1: 30/110/220V A 8/0.65/0.2
Minimum switching load mW (V/mA) 500 (10/10)
Standard contact material AgNi+Au
Coil specification
Nominal voltage (U
N
) VAC (50/60Hz) —
VDC 12 - 24
Rated power AC/DC VA (50Hz)/W —/0.7
Operating range AC —
DC (0.75…1.2)U
N
Holding voltage AC/DC —/0.4U
N
Must drop-out voltage AC/DC —/0.1U
N
Technical data
Mechanical life AC/DC cycles —/10·10
6
Electrical life at rated load AC1 cycles 100·10
3
Operate/release time ms 10/4
Insulation between coil
and contacts (1.2/50µs) kV 6 (8mm)
Dielectric strength
between open contacts VAC 1500
Ambient temperature range °C –40…+70
Protection category IP 20
Approvals relay (according to type)
1
48
SERIES
48 SERIES
Relay interface modules 8A