Data Sheet
7
Coil specifications
Nominal Coil Operating range Rated coil
voltage code consumption
U
N
U
min
U
max
I at U
N
(50Hz)
V V V mA
12 8.012 9.6 13.2 90.5
24 8.024 19.2 26.4 46
110 8.110 88 121 10.1
120 8.120 96 132 11.8
230 8.230 184 253 7.0
AC coil data
Nominal Coil Operating range Rated coil
voltage code consumption
U
N
U
min*
U
max
I at U
N
V V V mA
12 7.012 8.8 18 41
24 7.024 17.5 36 22.2
125 7.125 91.2 188 4
DC coil data (0.5 W sensitive)
Nominal Coil Operating range Rated coil
voltage code consumption
U
N
U
min
U
max
I at U
N
V V V mA
12 9.012 8.8 18 56
24 9.024 17.5 36 29
125 9.125 91.2 188 6
DC coil data (0.65 W)
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
R 49 - AC coil operating range v ambient temperatureR 49 - DC coil operating range v ambient temperature
Standard (650 mW)
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
R 49 - DC coil operating range v ambient temperature
Sensitive coil (500 mW)
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
*U
min
= 0.8 U
N
for 49.61 and 49.81
49.31/52/72
49.31/52/72
49.61/81
49.61/81
1
2
1
2
1
2
II-2014, www.findernet.com
B
49 Series - Relay interface modules 8 - 10 - 16 A
49
SERIES