Data Sheet

II-2016, www.findernet.com
1
B
4C
SERIES
4C SERIES
Relay interface modules 8 to 16A
1 & 2 CO relay interface modules,
15.8mm wide with Push-in terminal
Ideal interface for PLC and electronic systems
Type 4C.P1
- 1 CO 16A
Type 4C.P2
- 2 CO 8A
AC coils or DC coils
Supply status indication and coil suppression
module as standard
Identification label
UL Listing (certain relay/socket combinations)
35mm rail (EN60715) mounting
4C.P1 / 4C.P2
Push-in terminals
4C.P1 4C.P2
1 CO 16A
Push-in terminals
2 CO 8A
Push-in terminals
For outline drawing see page 5
Contact specification
Contact configuration 1 CO (SPDT) 2 CO (DPDT)
Rated current/Maximum peak current A 16/25 8/15
Rated voltage/
Maximum switching voltage VAC 250/440 250/440
Rated load AC1 VA 4000 2000
Rated load AC15 (230VAC) VA 750 350
Single phase motor rating (230VAC) kW 0.55 0.37
Breaking capacity DC1: 30/110/220V A 16/0.5/0.15 6/0.5/0.15
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi
Coil specification
Nominal voltage (U
N
) VAC (50/60Hz) 12 - 24 - 110 - 120 - 230 12 - 24 - 110 - 120 - 230
VDC 12 - 24 - 125 12 - 24 - 125
Rated power AC/DC VA (50Hz)/W 1.2/0.5 1.2/0.5
Operating range AC (0.8…1.1)U
N
(0.8…1.1)U
N
DC (0.73…1.1)U
N
(0.73…1.1)U
N
Holding voltage AC/DC 0.8 U
N
/ 0.4 U
N
0.8 U
N
/ 0.4 U
N
Must drop-out voltage AC/DC 0.2 U
N
/ 0.1 U
N
0.2 U
N
/ 0.1 U
N
Technical data
Mechanical life AC/DC cycles 10 · 10
6
10 · 10
6
Electrical life at rated load AC1 cycles 100 · 10
3
100 · 10
3
Operate/release time ms 15/5 (AC) - 15/12 (DC) 10/3 (AC) - 10/10 (DC)
Insulation between coil
and contacts (1.2/50μs) kV 6 (8mm) 6 (8mm)
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature range °C ≤ 12A: –40…+70/>12A: –40…+50 –40…+70
Protection category IP 20 IP 20
Approvals - relay (according to type)