Datasheet

1
B
58
SERIES
58 SERIES
Relay interface modules 7 - 10A
3 & 4 Pole relay interface modules,
31mm wide.
Ideal interface for PLC and electronic systems
58.33 - 3 Pole 10A (Push-in terminals)
58.34 - 4 Pole 7A (Push-in terminals)
AC coils and DC coils
Supply status indication and coil suppression
module as standard
Identification label
Cadmium Free contacts
UL Listing (certain relay/socket combinations)
35mm rail (EN60715) mounting
58.P3 / 58.P4
Push-in terminals
58.P3 58.P4
3 pole, 10A
Push-in terminals
35mm rail (EN60715)
mounting
4 pole, 7A
Push-in terminals
35mm rail (EN60715)
mounting
For outline drawing see page 7 Example: AC Example: DC
Contact specification
Contact configuration 3 CO (3PDT) 4 CO (4PDT)
Rated current/Maximum peak current A 10/20 7/15
Rated voltage/
Maximum switching voltage VAC
250/400 250/250
Rated load AC1 VA 2500 1750
Rated load AC15 (230VAC) VA 500 350
Single phase motor rating (230VAC) kW 0.37 0.125
Breaking capacity DC1: 30/110/220V A 10/0.25/0.12 7/0.25/0.12
Minimum switching load mW (V/mA) 300 (5/5) 300 (5/5)
Standard contact material AgNi AgNi
Coil specification
Nominal voltage (U
N
) VAC (50/60Hz) 12 - 24 - 48 - 110 - 120 - 230 12 - 24 - 48 - 110 - 120 - 230
VDC 12 - 24 - 48 - 125 12 - 24 - 48 - 125
Rated power AC/DC VA (50Hz)/W 1.5/1 1.5/1
Operating range AC (0.8…1.1)U
N
(0.8…1.1)U
N
DC (0.8…1.1)U
N
(0.8…1.1)U
N
Holding voltage AC/DC 0.8U
N
/0.5U
N
0.8U
N
/0.5U
N
Must drop-out voltage AC/DC 0.2U
N
/0.1U
N
0.2U
N
/0.1U
N
Technical data
Mechanical life AC/DC cycles 20·10
6
/50·10
6
20·10
6
/50·10
6
Electrical life at rated load AC1 cycles 200·10
3
150·10
3
Operate/release time ms 10/5 (AC) - 10/15 (DC) 11/3 (AC) - 11/15 (DC)
Insulation between coil
and contacts (1.2/50μs) kV 3.6 3.6
Dielectric strength
between open contacts VAC
1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)

Summary of content (4 pages)