Data Sheet
A
Plug-in mount/Faston 187
Magnetic blow power relay
• Plug-in (92 series sockets) or Faston 187
(4.8x0.5mm) with optional mounting adaptors
• 1 & 2 Pole NO contacts
• High DC load (resistive and inductive)
switching capability
• DC coils
• Reinforced insulation between coil and
contacts according to EN60335-1, with 6mm
clearance & 8mm creepage distance
• Cadmium free contact material
• Sockets and accessories
62.31-4800 62.32-4800
• 1 pole normally open contact (double break,
≥4.2mm contact gap)
• Plug-in/Faston 187
• 2 pole normally open contact
(≥2.1mm contact gap)
• Plug-in/Faston 187
* Maximum peak current 120A- 5ms.
For outline drawing see page 12
62.31-4800 62.32-4800
Contact specification
Contact configuration 1 NO (SPST-NO) double break, ≥4.2mm 2 NO (DPST-NO), ≥2.1mm
Rated current/Maximum peak current A 16/30* 16/30*
Rated voltage/
Maximum switching voltage VAC 250/400 250/400
Rated load AC1 VA 4000 4000
Breaking capacity DC1: 30/125/220V A 16/16/12 16/12/6
Breaking capacity DC inductive (L/R=40ms):
30/125/220V A 16/5/3 10/2/1.2
Minimum switching load mW (V/mA) 1000 (10/10) 1000 (10/10)
Standard contact material AgSnO
2
AgSnO
2
Coil specification
Nominal voltage (U
N
) VDC 6 - 12 - 24 - 48 - 60 - 110 - 125 - 220
Rated power DC W 1.3 1.3
Operating range DC (0.85…1.1)U
N
(0.85…1.1)U
N
Holding voltage DC 0.6U
N
0.6U
N
Must drop-out voltage DC 0.1U
N
0.1U
N
Technical data
Mechanical life DC cycles 10·10
6
10·10
6
Electrical life at rated load DC1 cycles 100·10
3
100·10
3
Operate/release time ms 16/5 16/5
Insulation between coil
and contacts (1.2/50µs)
kV
6 6
Dielectric strength
between open contacts VAC
3000 2000
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT I RT I
Approvals (according to type)
6
II-2018, www.findernet.com
62 SERIES
Power relays 16A
62
SERIES