A
65 SERIES
Power relays 20 - 30A
65
SERIES
Contact specification
F 65 - Electrical life (AC) v contact current H 65 - Maximum DC1 breaking capacity
Resistive load - cosφ = 1
Inductive load - cosφ = 0.4
Cycles
limit for 1NO+1NC types
1 normally open + 1 normally closed type
1 normally open type
DC breaking current (A)
DC voltage (V)
When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥80·10
3
can be expected.
In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Coil specifications
DC coil data
Nominal
voltage
Coil code Operating range Resistance Rated coil
consumption
U
N
U
min
U
max
R I at U
N
V V V
Ω
mA
6 9.006 5.1 6.6 28 214
12 9.012 10.2 13.2 110 109
24 9.024 20.4 26.4 445 54
48 9.048 40.8 52.8 1770 27.1
60 9.060 51 66 2760 21.7
110 9.110 93.5 121 9420 11.7
125 9.125 106 138 12000 10.4
220 9.220 187 242 37300 5.8
AC coil data
Nominal
voltage
Coil code Operating range Resistance Rated coil
consumption
U
N
U
min
U
max
R I at U
N
(50Hz)
V V V
Ω
mA
6 8.006 4.8 6.6 4.6 367
12 8.012 9.6 13.2 19 183
24 8.024 19.2 26.4 74 90
48 8.048 38.4 52.8 290 47
60 8.060 48 66 450 37
110 8.110 88 121 1600 20
120 8.120 96 132 1940 18.6
230 8.230 184 253 7250 10.5
240 8.240 192 264 8500 9.2
400 8.400 320 440 19800 6
R 65 - DC coil operating range v ambient temperature R 65 - AC coil operating range v ambient temperature
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
1 - Max. permitted coil voltage.