Datasheet

70.11 70.31 70.41
Electronic voltage monitoring relays for
single and three-phase applications
Multifunctional types, providing the flexibility
of monitoring Undervoltage, Overvoltage,
Window Mode, Phase rotation, Phase loss,
Asymmetry and Neutral loss
Positive safety logic - Make output contact
opens if the relay detects an error
All functions and values can be easily adjusted
by the selector and trimmer on front face
“Blade + cross” – both flat blade and cross
head screw drivers can be used to adjust the
regulators and the function selector
Colored LEDs for clear & immediate visual
indication
1 CO relay output, 6 or 10 A
Modular housing, 17.5 or 35 mm wide
35 mm rail (EN 60715) mount
Cd-free contact material
1 CO (SPDT) 1 CO (SPDT) 1 CO (SPDT)
10 / 30 6 / 10 6 / 10
250 / 400 250 / 400 250 / 400
2,500 1,500 1,500
750 500 500
0.5 0.185 0.185
10 / 0.3 / 0.12 6 / 0.2 / 0.12 6 / 0.2 / 0.12
300 (5 / 5) 500 (12 / 10) 500 (12 / 10)
AgNi AgNi AgNi
220…240 380…415 380…415
2.6 / 0.8 11 / 0.9 11/ 0.9
130…280 220…510 220…510
80 · 10
3
60 · 10
3
60 · 10
3
170…270 300…480 300…480
4...25
0.5...60 0.5...60 0.5...60
0.5 1 1
5 (L-N) 10 (L-L) 10 (L-L)
≈ 1 ≈ 1 ≈ 1
444
1,000 1,000 1,000
–20…+50 –20…+50 –20…+50
IP20 IP20 IP20
1
Single-phase (220...240 V)
voltage monitoring:
Undervoltage
Overvoltage
Window mode (overvoltage
+ undervoltage)
Voltage fault memory
selectable
Three-phase (380...415 V)
voltage monitoring:
Undervoltage
Overvoltage
Window mode (overvoltage
+ undervoltage)
Voltage fault memory
selectable
Phase loss
Phase rotation
Three-phase (380...415 V,
with or without neutral)
voltage monitoring:
Window mode (overvoltage
+ undervoltage)
Phase loss
Phase rotation
Asymmetry
Neutral loss selectable
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage/Max. switching voltage V AC
Rated load AC1 VA
Rated load AC15 VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Standard contact material
Supply specification
Nominal system voltage (U
N
) V AC (50/60 Hz)
Rated power VA (50 Hz) / W
Operating range V AC (50/60 Hz)
Technical data
Electrical life at rated load AC1 cycles
Voltage detection level range V
Asymmetry detection level range %
Switch-off delay time (T on function diagrams) s
Switch-on lock-out time s
Switch-on hysteresis (H on function diagrams) V
Power-on activation time s
Insulation between supply and contacts (1.2/50 μs) kV
Dielectric strength between open contacts V AC
Ambient temperature °C
Protection category
Approvals (according to type)
Features
70 Series - Line monitoring relay
IX-2012, www.findernet.com
Screw terminal
For outline drawing see page 8