2
Features
Priority change relay
Special relay for alternating loads,
for applications with pumps, compressors,
air conditioning or refrigeration units
• 2 independent NO output, 12 A
• 4 functions
• 2 independent control signals, insulated from
supply
• 110...240 V and 24 V AC/DC supply versions
• Modular housing, 35 mm wide
• 35 mm rail (EN 60715) mount
• Cd-free contact material
2 NO (2 DPST-NO)
12 / 20
250 / 400
3,000
1,000
0.55
12 / 0.3 / 0.12
300 (5 / 5)
AgNi
24 110 … 240
0.12 0.18
1.1 / 1.7 1.5 / 3.9
16.8…28.8 90…264
16.8…32 90…264
100 x 10
3
0.2...20
≤ 0.7
50
6
1,000
–20…+50
IP20
• Multi-function (MI, ME, M2, M1)
Contact specification
Contact configuration
Rated current / Max. peak current A
Rated voltage / Max. switching voltage V AC (50/60 Hz)
Rated load AC1 VA
Rated load AC15 VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Standard contact material
Supply specification
Nominal voltage (U
N
) V AC (50/60 Hz) / DC
Rated power in stand-by W
with 2 active relays W/VA(50 Hz)
Operating range V AC (50/60 Hz)
V DC
Technical data
Electrical life at rated load AC1 cycles
Output delay time (T on function diagrams) s
Power-on activation time s
Minimum impulse duration ms
Insulation between supply and contacts (1.2/50 μs) kV
Dielectric strength between open contacts V AC
Ambient temperature °C
Protection category
Approvals (according to type)
72 Series -
Monitoring relays
72.42
Screw terminal
For outline drawing see page 8