Datasheet

Indication elements
7E Series - Energy meter
6
LC-Display Type 7E.23, 7E.46, 7E.56
Type 7E.23
Ttotal kWh Indicates total consumption
Tpart. kWh Indicates partial consumption, this value is resettable
P kW Indicates the instantaneous power
U V Indicates the voltage
I A Indicates the current
2,000 Imp/kWh Pulsed according to drawn power
Error indication (line 1L/2L inverted) with pulsating 600/600 ms
Type 7E.46
T1total kWh Indicates total consumption Tariff 1
T1part. kWh Indicates partial consumption for Tariff 1, this value is resettable
T2total kWh Indicates total consumption Tariff 2
T2part. kWh Indicates partial consumption for Tariff 2, this value is resettable
P kW Indicates the instantaneous power per phase or all phases
U V Indicates the voltage per phase
I A Indicates the current per phase
100 Imp/kWh Pulsed according to drawn power
kWh Indicates the unit kWh when the consumption is displayed
L1/L2/L3 For P-, U-, I- or Error display, the corresponding phase is displayed
Error Indicates a missing phase or incorrect current direction - the
appropriate phase is also displayed
Type 7E.56
T1total kWh Indicates total consumption
T1part. kWh Indicates partial consumption, this value is resettable
CT Indicates the set current transformer ratio, factory setting is 5:5
Select The transformer ratio can be selected in the menu item Select *
P kW Indicates the instantaneous power per phase or all phases
U V Indicates the voltage per phase
I A Indicates the current per phase
10 Imp/kWh Pulsed according to drawn power
kWh Indicates the unit kWh when the consumption is displayed
L1/L2/L3 For P-, U-, I- or Error display, the corresponding phase is displayed
Error Indicates a missing phase or incorrect current direction - the
appropriate phase is also displayed
* To adjust the current transformer ratio remove the bridge Z1 - Z2 and reset the energy
meter according to the operation instructions. Then lock it again with the bridge. For a
tamper proof lead seal use 4 terminal covers (07E.16).
For 7E.23.8.230.0001 only with total consumption.
X-2012, www.findernet.com