Data Sheet

VII-2019, www.findernet.com
7
G
7F
SERIES
7F SERIES
Filter Fan (24…630)m
3
/h
Filter Fan for electrical cabinets and
enclosures 24VDC versions
Very low acoustic noise
Minimal depth within enclosure
Air volume 230 m
3
/h (free flow)
Air volume 180 m
3
/h
(with Exhaust Filter installed in cabinet)
Nominal voltage: 24VDC
Time-saving installation and maintenance
Filter Fan supplied in Reverse flow mode ( 7F.80)
* Product codes, see pages 8 & 11
7F.50.9.024.4230
Nominal voltage 24VDC
Air volume 230m
3
/h
Rated power 26W
Size 4
Note:
By reversing the fan motor, the air direction
can be changed from “Inlet” Filter Fan mode
to “Exhaust” Filter Fan mode** (except for the
types 7F.50.8.xxx.4370, 7F.50.8.xxx.5500 and
7F.50.8.xxx.5630).
** Supplied in “Inlet Filter Fan mode (Standard).
For outline drawing see page 15
Fan data
Air volume (free flow) m
3
/h 230
Air volume (with exhaust filter installed) m
3
/h 180
Noise level dB (A) 61
Life time at 40°C h 50000
Electrical data
Nominal voltage (U
N
) VDC 24
Operating range DC (0.8…1.1)U
N
Current consumption A 1.08
Rated power W 26
Other data
Housing, cover Plastics according to UL94V-0, light grey (RAL7035)
Filter mat (included) G3 according to EN 779, filtering degree (80…90)%
Filter material Synthetic fibre with progressive construction, temperature
resistant to 100°C, self extinguishing, Class F1 (DIN53438)
Electrical connections/wire size screw terminals / max. 2.5mm
2
Screw torque Nm 0.8
Ambient temperature range °C –10…+70
Protection class I
Protection category according to EN60529 IP 54
Approvals (according to type)