Datasheet

H
7
IX-2021, www.findernet.com
80
SERIES
80 SERIES
Modular timers 8 A
Multi-function and multi-voltage
17.5mm wide
Six time scales from 0.1s to 24h
High input/output isolation
35mm rail (EN60715) mount
“Blade + cross” - both flat blade and cross head
screw drivers can be used to adjust the range
and function selectors, the timing trimmer, and
to disengage the rail mounting clip
New multi-voltage versions with “PWM clever”
technology
80.51.0.240.0000
Screw terminal
80.51.0.240.P000
Push-in terminal
80.51
Multi-voltage (24…240)VAC/DC
Multi-function
AI: On-delay
DI: Interval
SW: Symmetrical flasher (starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
Wiring diagram
(without control signal)
Wiring diagram
(with control signal)
For UL ratings see:
General technical informationpage V
For outline drawing see page 9
Contact specification
Contact configuration 1 CO (SPDT)
Rated current/Maximum peak current A 8/16
Rated voltage/
Maximum switching voltage VAC 250/400
Rated load AC1 VA 2000
Rated load AC15 (230VAC) VA 400
Single phase motor rating (230VAC) kW 0.3
Breaking capacity DC1: 30/110/220 V A 8/0.3/0.12
Minimum switching load mW (V/mA) 500 (10/5)
Standard contact material AgNi
Supply specification
Nominal voltage (U
N
) VAC (50/60Hz) 24…240
VDC 24…240
Rated power AC/DC VA (50Hz)/W <1.8/<1
Operating range VAC 17…265
VDC 17…265
Technical data
Specified time range (0.1…2)s, (1…20)s, (0.1…2)min, (1…20)min, (0.1…2)h, (1…24)h
Repeatability % ±1
Recovery time ms ≤50
Minimum control impulse ms 50
Setting accuracy-full range % ±5
Electrical life at rated load in AC1 cycles 100·10
3
Ambient temperature range °C –20…+60
Protection category IP 20
Approvals (according to type)