Datasheet
7
with control signal
Multi-function
without control signal
Type
83.01
83.02
*** Type 83.02: regulated
using an external
potentiometer
(10 kΩ - 0.25 W).
***
***
(AI) On-delay.
Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs when power is removed.
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
(GI) Pulse delayed.
Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs after a fixed time of 0.5s.
(SW) Symmetrical flasher (starting pulse on).
Apply power to timer. Output contacts transfer immediately
and cycle between ON and OFF for as long as power is
applied. The ratio is 1:1 (time on = time off).
(BE) Off-delay with control signal.
Power is permenently applied to the timer. The output contacts
transfer immediately on closure of the control signal (S).
Opening the control signal initiates the preset delay, after which
time the output contacts reset.
(CE) On- and off-delay with control signal.
Power is permenently applied to the timer.
Closing the control signal (S) initiates the preset delay, after
which time the output contacts transfer. Opening the control sig-
nal initiates the same preset delay, after which time the
output contacts reset.
(DE) Interval with control signal on.
Power is permenently applied to the timer.
On momentary or maintained closure of control signal (S),
the output contacts transfer, and remain so for the duration
of the preset delay, after which they reset.
(WD) Watchdog (Retriggerable interval with control signal on).
Power is permanently applied to the timer.
On momentary or maintained closure of control signal (S),
the output contacts transfer, and remain so for the duration
of the preset delay, after which they reset; subsequent closures of
control signal during the delay will extend the time. If the closure
of the control signal (S) is longer than the preset time (T) then the
output contacts reset.
Both output contacts (15-18 and 25-28)
follow the timing function
2 timed contacts
1 timed +
1 instantaneous contact
Both output contacts (15-18 and 25-28)
follow the timing function
Both output contacts [15-18 and 25(21)-28(24)]
stay permanently open
Both output contacts [15-18 and 25(21)-28(24)]
stay permanently open
The output contact 15-18 follows the timing function
The output contact 21-24 follows the power supply (U)
The output contact 15-18 follows the timing function
The output contact 21-24 follows the control signal (S)
Wiring diagram
83.01
83.01
83.02
83.02
83.02 type
NOTE: The timing function must be set when the timer is de-energised. Or for the 83.02/52, when the contact mode selector is in the OFF position.
Contact mode selector
Functions without control signal (example: AI)
Functions with control signal (example: BE)
Functions
U = Supply voltage S = Signal switch = Output contact
I-2015, www.findernet.com
83 Series - Modular timers 16 A
83
SERIES
H