56 SЕRIES Miniature power relays 12 A Industrial furnaces and ovens Control and management of electric power Industrial motors Circuit breakers and switches Panels for electrical distribution Control panels Carousel warehouses Vending machines
56 SERIES Miniature power relays 12 A 56 SERIES 56.32/56.34 Plug-in - 12 A Power relay, 2 & 4 pole • Flange mount option (Faston 187, 4.8 x 0.5 mm termination) • AC coils & DC coils • Lockable test button and mechanical flag indicator • Cadmium Free contacts (standard version) • Contact material options • 96 series sockets • Coil EMC suppression • Accessories • European Patent 56.32-0300 A • 2 or 4 pole changeover contact • Plug-in/Faston 187 56.32 • 2 pole normally open contact (≥ 1.
56 SERIES 56 SERIES Miniature power relays 12 A 56.42/56.44 Printed circuit mount 12 A Power relay • 2 & 4 pole • AC coils & DC coils • Cadmium Free contacts (standard version) • Contact material option • RT III (wash tight) option available • 2 or 4 pole changeover contact • PCB mount 56.42 • 2 pole normally open contact (≥ 1.5 mm gap) • PCB mount 56.42-0300 56.44 * For 4 CO (4PDT) only. For UL ratings see: “General technical information” page V 56.42 Copper side view 56.
6 SERIES Miniature power relays 12 A 56 SERIES Ordering information Example: 56 series plug-in relay, 2 CO (DPDT), 12 V DC coil, lockable test button and mechanical indicator. 5 6 . 3 A B C D 2 . 9 . 0 1 2 . 0 0 4 0 Series A: Contact material 0 = Standard AgNi 2 = AgCdO 4 = AgSnO2 Type 3 = Plug-in 4 = PCB B: Contact circuit 0 = CO (nPDT) 3 = NO (nPST), ≥ 1.5 mm contact gap No.
56 SERIES Miniature power relays 12 A 56 SERIES Technical data Insulation according to EN 61810-1 Nominal voltage of supply system V AC Rated insulation voltage V AC Pollution degree Insulation between coil and contact set Type of Insulation Overvoltage category Rated impulse voltage kV (1.2/50 μs) Dielectric strength V AC Insulation between adjacent contacts Type of insulation Overvoltage category Rated impulse voltage kV (1.
56 SERIES Miniature power relays 12 A 56 SERIES Coil specifications DC coil data, 2 pole relay Nominal voltage UN V 6 12 24 48 60 110 125 220 Coil code 9.006 9.012 9.024 9.048 9.060 9.110 9.125 9.220 AC coil data, 2 pole relay Operating range Umin V 4.8 9.6 19.2 38.4 48 88 100 176 Umax V 6.6 13.2 26.4 52.8 66 121 138 242 Resistance R Ω 40 140 600 2400 4000 12500 17300 54000 Rated coil consumption I at UN mA 150 86 40 20 15 8.8 7.2 4 Nominal voltage UN V 6 12 24 48 60 110 120 230 240 Coil code 8.
56 SERIES 56 SERIES Miniature power relays 12 A Accessories Top flange mount adaptor for 56.32 056.25 A 056.25 with relay 056.25 056.25 with relay Rear flange mount adaptor for 56.32 056.26 056.26 056.26 with relay 056.26 056.26 with relay Top 35 mm rail (EN 60715) adaptor for 56.32 056.27 056.27 056.27 with relay 056.27 056.27 with relay Top flange mount adaptor for 56.34 056.45 056.45 056.45 with relay 056.45 056.45 with relay Top 35 mm rail (EN 60715) adaptor for 56.34 056.
6 SERIES Sockets and accessories for 56 series relays 56 SERIES Screw terminal (Box clamp) socket panel or 35 mm rail mount (EN 60715) For relay type 96.02 Blue 56.32 96.02.0 Black 96.04 Blue 56.34 96.04.
56 SERIES 96 SERIES Sockets and accessories for 56 series relays Screw terminal (Plate clamp) socket panel or 35 mm rail (EN 60715) mount For relay type A 96.72 Blue 56.32 96.72.0 Black 96.74 Blue 56.34 96.74.0 Black Accessories 96.72 Approvals (according to type): Metal retaining clip (supplied with socket - packaging code SMA) Modules (see table below) Technical data Rated values Dielectric strength Protection category Ambient temperature Screw torque Wire strip length Max. wire size for 96.
96 SERIES Sockets and accessories for 56 series relays 56 SERIES PCB socket 96.12 Approvals (according to type): 96.12 (blue) 56.32 For relay type Accessories 96.12.0 (blue) 96.14 (blue) 56.34 96.14.0 (blue) A 094.51 Technical data Rated values Dielectric strength Protection category Ambient temperature 15 A - 250 V 2 kV AC IP 20 °C –40…+70 Copper side view 96.12 Copper side view 96.14 Packaging codes How to code and identify retaining clip and packaging options for sockets.