User guide

32 Distributed Audio Panel Manual — P/N 52265:B1 6/8/2010
Field Programming Switch SW1 Settings on Optional FC-MGM Module
Switch 6, 7 and 8 - used to determine the number of times the voice message will repeat.
SW2 - Record Bypass Switch (on optional FC-MGM Module)
This switch, when placed in the down position, prevents accidental erasure of stored voice mes-
sages. See 'Operating Instructions' on page 52 for additional information.
•UP Position = The stored digital voice message may be overwritten with
a new one.
•Down Position = The stored digital voice message can not be
overwritten (factory default setting).
SWITCH
6
SWITCH
7
SWITCH
8
NUMBER OF TIMES TO REPEAT DIGITAL
VOICE MESSAGE
ON OFF OFF 3
OFF ON OFF 3
ON ON OFF 6 (factory default)
OFF OFF ON 8
ON ON ON INFINITE (until FACP trigger is reset)
Table 2.4 Switch Settings for Message Repeat
RECORD
BYPASS
RECORD
BYPASS