User guide

Distributed Audio Panel Manual — P/N 52265:B1 6/8/2010 41
Output Circuits Installation
3.6 Output Circuits
3.6.1 Trouble Relay - TB1
The main circuit board provides a Form-C Trouble relay, for independent monitoring, rated for 2.0
amps @ 30 VDC (resistive) and 0.6 amp @ 30 VAC (resistive). This relay is ‘fail safe’, meaning
that it is normally energized. Should system power shut off, this relay will deenergize, transferring
its contacts.
3.6.2 AC Power Loss Relay - TB11
The main circuit board provides a Form-C AC Power Loss relay rated for 2.0 amps @ 30 VDC
(resistive) and 0.6 amps @ 30 VAC (resistive).
ac25datb12.wmf
Remote Power Supply
or Battery Charger
Normally Open
Contacts
1 2
Figure 3.9 Trouble Contact Input Terminal
Figure 3.10 Trouble Relay
TB1
2550daacrl.wmf
Shown in energized,
nontrouble condition
Figure 3.11 AC Power Loss Relay
TB11
Shown in energized,
normal AC Power condition
2550daacrl.wmf