Instruction Manual

4. Installation Setting Rotary and DIP Switches
28
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
Setting Rotary and DIP Switches
The Annunciator Address Rotory Switches and the DIP Switches must be
set before the annunciator will operate properly. The rotory switches are set
to the addresss of the annunciator. The DIP switches are set to determine how
the annunciator operates. For further information see the appendix for the
specific FACP.
Figure 8 Setting Rotory and DIP Switches
DIP Switch Settings
1 - Not Used: This switch must be set “OFF”
2 - Expanders Installed: None = OFF; One = ON; Two = OFF; Three = ON
3 - Expanders Installed: None = OFF; One = OFF; Two = ON; Three = ON
4 - Eight-Point Shift: Set switch “ON” to switch the CPU functions out of the first
eight annunciator points. This switch is intended for systems between 9 and 16
circuits and employing one ACM-16ATF module (with no expander) where
annunciation of all circuits is desired.
5 - Receive Only: Set this switch “ON” for each annunciator that will provide the
same information as another annunciator in a different location.
Note: When two or more annunciators hold the same address, all but one must be
configured as “Receive Only” annunciators.
6 - Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any
event. (The piezo will also be disabled if Flash Inhibit is “ON”.)
7 - Switch Inhibit: To disable the point control switches on the annunciator from
executing system control functions, set this switch “ON”. When inhibited, the
switches will serve as local Lamp Test switches only. In addition, the
Acknowledge/Lamp Test switch will function only in a local capacity, unrecognized
by the control panel.
8 - Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated
with unacknowledged events. Flash Inhibit also disables the piezo from sounding.
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
J4 - Key Switch Connector
DIP Switches
Annunciator Address
Rotory Switches
Switch
Positions
OFF ON
Tens Ones
Using a small screw
driver, rotate dials to
desired address.
This address is set to
‘02’ or ‘2’.
ACSf-switch.cdr