Instruction Manual

ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
43
Appendix A: Sensiscan 200
Capabilities
When installed with a Sensiscan 200, the modules can annunciate the status
of initiating and notification circuits, relays, and several system control
functions. Up to 32 devices can be connected to the EIA-485
communications output, all addresses combined. Two way communications
can occur with only one annunciator set to address “1”; other devices must
be configured as “Receive Only”. Check battery calculation tables for power
limitations. Each annunciator LED is automatically assigned to one and only
one system point:
Circuits:
IZ-4F, IZ-4AF, IZ-8F Initiating Device Circuits (alarm and trouble)
IC-4F, ICE-4F, ICR-4LF Notification Appliance Circuits (activation
and trouble)
CR-4F, CRE-4F, CR-4LF Control relays (activation and trouble)
TC-2F, TC-4F circuits (activation and trouble)
System Controls:
Acknowledge
Signal Silence
•System Reset
Activate Notification Circuits 1 and 2, the Remote Signaling Municipal
Tie circuit, and the Alarm Relay.
Connecting EIA-485 Circuit
Communication between the CPU and the annunciator module is
accomplished over a two-wire EIA-485 serial interface.
Power-limited and supervised.
6000 feet maximum distance (with 16 AWG wire) between the control
panel and the furthest annunciator.
Use twisted pair cable with a characteristic impedance of
approximately 120 ohms.
EIA-485 circuit rated 5.5 VDC max., 60 mA max.