Instruction Manual

Providing Power to Annunciators Appendix B: Sensiscan 2000
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
49
Providing Power to Annunciators
Sensiscan 2000 panels use the MPS-24AF or the MPS-24BF Main Power
Supply. This 24 VDC output is filtered, regulated, power-limited, and non-
resettable.
MPS-24AF - 3 A maximum current draw
MPS-24BF - 200 mA maximum current draw
The power run to the annunciator does not require a Power Supervision Relay
because loss of power is inherently supervised through a communications
loss.
Note: When not using the trouble input on annunciator or expander, jumper Trouble
Input terminals of TB1 on annunciator together.
MPS-24AF Main Power Supply - Connect the power run for the
annunciator module to the MPS-24AF TB3 Terminals 3(+) & 4(–), as shown
below.
Figure 21 MPS-24AF Power Connections - Sensiscan 2000
MPS-24BF Main Power Supply - Connect the power run for the
annunciator module to the MPS-24BF TB2 Terminals 3(+) & 4(–)as shown
below.
Figure 22 MPS-24BF Power Connections - Sensiscan 2000
TB2
+24 R C OM M O N + 24
COMMON
POWER LIMITED
BAT + B AT -
ACSf-mps24a.cdr
(–) Common
(+) 24 VDC Non-
Resettable Power
TB1
MPS-24AF Terminal Blocks
TB3
TB2
BATT –BATT +
COMMON COMMON
1 2 3 4
1 2
ACSf-mps24b.cdr
(–) Common
(+) 24 VDC Non-Resettable Power