Instruction Manual

Appendix B: Sensiscan 2000 Installing Modules in the System
50
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
Installing Modules in the System
The annunciator modules begin annunciation with the CPU and continue
with the annunciation of circuits on the module installed directly after the
CPU. To ensure full employment of annunciator points, mount system
modules that require annunciation in the CPU row first, then in the second
row, etc. Modules with circuits that need not be annunciated by the system
should be installed further down in the cabinet.
Note: Without invoking the Eight-Point Shift, the first eight points would be dedicated
to CPU functions, not circuits of the first module. Refer to "Setting Rotary and DIP
Switches" on page 28.
Figure 23 CPU Module Ribbon Cable Connections
ACSf-instmods.cdr
Top Row: Annunciator Address “1”
Points 1-32, annunciated by either the first
ACM-16ATF and its first expander, or by
the first ACM-32AF.
2nd Row: Annunciator Address “1”
Points 33-64, annunciated by either the
second and third expanders of an ACM-
16ATF, or by an AEM-32AF expander.
3rd Row: Annunciator Address “2”
Points 65-96, annunciated by either the
second ACM-16ATF and its first expander,
or by the second ACM-32AF.
4th Row: Annunciator Address “2”
Points 97-128, annunciated by either the
second and third expanders of the second
ACM-16ATF, or by an AEM-32AF.
CPU Side View