User Manual

Wiring the EIA-485 Terminal Blocks 2. Installation
ACM-8RF PN 50362:C 03/21/01
13
Wiring the EIA-485 Terminal Blocks
Communications between the Fire Alarm Control Panel and the ACM-8RF is
accomplished over a two-wire EIA-485 serial communications bus which must
be power-limited. Communications between the host FACP and ACM-8RFs
is supervised by the fire alarm control panel.
Wiring Specifications
The EIA-485 circuit cannot be T-tapped; it must be wired in a
continuous fashion from the control panel to the ACM-8RFs.
The maximum wiring distance between the panel and ACM-8RFs is
6,000 feet.
The wiring must be a 18 AWG to 14 AWG twisted shielded pair cable
having a characteristic impedance of 120 ohms, +/- 20%.
Limit the total wire resistance to 100 ohms.
Do not run cable adjacent to, or in the same conduit as, 120 volts AC
service, noisy electrical circuits that are powering mechanical bells or
horns, audio circuits above 25 V
RMS
, motor control circuits, or SCR
power circuits.
Note: Never use the EIA-485 shield for grounding purposes. Terminate the EIA-485
shield at the Fire Alarm Control Panel only.
Table 2 Wire Specifications
EIA-485 Shield in Conduit
When the EIA-485 wiring is in conduit, connect the shield to system common.
The shield can enter the cabinet, but must be insulated from the cabinet (no
electrical contact). Between ACM-8RFs, wire-nut multiple shields together
(which can be inside of the respective ACM-8RF enclosure but ensure that the
shield does not contact earth ground).
Figure 5 Terminating the Shield in Conduit
Standard Annealed Copper Wire
Wire Size
A.W.G
Diameter
in Mils
Cross Section Ohms per 1000 feet
Pounds per
1000 feet
Circ. Mils Sq. Inch @ 77°F. @ 149°F.
14 64 4110 0.00323 2.85 2.97 12.4
16 51 2580 0.00203 4.09 4.73 7.82
18 40 1620 0.00128 6.51 7.51 4.92
1
IN (+)
4
IN (–)
TB2
3
OUT (–)
2
OUT (+)
ACM8RF-term1.cdr