User Manual

1. Introduction Features
8
ACM-8RF PN 50362:C 03/21/01
Features
Figure 1 ACM-8RF Features
Relays
The Relay Control Module provides eight Form-C relays with 5 amp contacts
@ 125 VAC (resistive) or 30 VDC (resistive) and 2 amps at 125 VAC
inductive). The relay contacts are gold plated silver alloy for medium duty
switching and are not intended for motor control or pilot duty. Wiring to the
relays is via sturdy removable terminal blocks.
24 VDC Power and Earth Ground
Wiring to removable terminal block TB1 is for 24 VDC power-limited,
regulated, nonresettable power from the host FACP or a compatible UL listed
battery backed power supply such as the Fire•Lite FCPS-24F. This terminal
block may be used to daisy chain the 24 VDC to other ACM-8RFs or EIA-485
Fire•Lite compatible devices.
12
OFF
12345
6
78
O
F
F
Relays
Relays
SW4 - Mode
Select
Switch
SW3 - Relay Assignment
DIP Switches
SW1-SW2
Address
Select Rotary
Switches
TB2 - EIA-485
Terminal Block
TB1 - 24 VDC
Terminal Block
ACM-8RF.cdr
K5
K6
K7
K8
K4
K3
K2
K1