Adding the Charger for Additional Current Due to internal fuses, the maximum alarm
current that can be drawn from the batteries and passed through the charger’s two output
circuits is limited to 10 amps maximum (each circuit). The PS-12600 batteries, however,
are capable of supplying up to 45 amps of current in alarm. The remaining 25 amps of
alarm current can be drawn directly from the battery terminals to supply Notification
Appliance Circuits, control modules and other alarm devices as illustrated in Figure 12
Figure 12 Typical Connections for Drawing Additional Current
To connect a charger as shown in Figure 12, follow these steps:
Step Action
1 Connect the Battery+ and Battery– terminals of the power supply to the charger
Battery output (TB2: Batt 1+ and Batt 1–) as shown in Figure 12.
2 Connect the Battery+ and Battery– terminals of the first auxiliary device to the
charger output circuit (TB2: Out 2+ and Out 2–) as shown Figure 12.
3 Connect the Battery+ and Battery– terminals of the second auxiliary device to the
charger output circuit (TB2: Out 1+ and Out 1–) as shown in Figure 12.
4 Connect the Battery+ and Battery– terminals of the third auxiliary device to the
batteries as shown in Figure 12.
5 Connect the batteries to the charger.