Owner's manual

Optional Voltmeter/Ammeter Installation
Installation and Configuration
CHG-75 PN 51315:A 08/01/01 15
2.6 Optional Voltmeter/Ammeter Installation
An ammeter (AM-1) or voltmeter (VM-1) can be installed for use with the CHG-75
charger. If installing an AM-1 or VM-1, mount the meter to a BB-26 or BB-55F battery
box as illustrated below.
VM-1 Voltmeter Connections
- the VM-1 can be installed on the CHG-75 to provide a
visual indication of the battery/charger voltage. When the battery is disconnected, the
voltmeter measures charger voltage only. The VM-1 can mount to a BB-26 or BB-55F
battery box. To connect the VM-1 to the CHG-75:
Connect the VM-1 positive lead to TB2 Out (+)
Connect the VM-1 negative lead to TB2 Out (-)
Mount the VM-1 into a mounting slot on the front of the battery box
AM-1 Ammeter Connections
- the AM-1 can be installed on the CHG-75 to provide a
visual indication of the charger current. The AM-1 can mount to a BB-26 or BB-55F
battery box. To connect the AM-1 to the CHG-75:
Cut jumper JP5 on the CHG-75
Connect the AM-1 harness to connector J4 on the CHG-75. Be sure to
observe polarity
Mount the AM-1 into a mounting slot on the front of the battery box
Figure 2.7 Mounting AM-1 or VM-1 on BB-55F Battery Box
metertobb-55f.cdr
JP4
TB4
TB2
ENABLE
AC DELAY
16 HR
DELAY
GND FLT
DISABLE
AM-1 ENABLE
AM-1
JP5
JP2
F2
J4
J1 J2
J3
F3
-
+
BATT
+
OUT TO FACP
-
15
15
NC NO C
AM-1
VM-1
Figure 2.8 Wiring AM-1 or VM-1 to CHG-75
+
-
+ AM-1
- AM-1
+ VM-1
- VM-1
To Load/FACP
- Out
+ Out
chg75amvm.cd