Connecting Batteries to the Charger
Installation and Configuration
CHG-75 PN 51315:A 08/01/01 17
2.8 Connecting Batteries to the Charger
Batteries ranging from 25 AH to 75 AH can be connected to the charger. This section
provides illustrations and instructions for connecting two or four batteries.
2.8.1 Connecting Two Batteries
The following steps must be followed when connecting two batteries to the charger:
1. Remove all power sources to the charger
2. Connect the battery negative (-) cable to TB2, Terminal 2 on the charger (labeled
BATT -) as illustrated in Figure 2.10
3. Connect the battery positive cable to TB2, Terminal 1 on the charger (labeled
BATT +) as illustrated in Figure 2.10
4.
Do not connect the Battery Interconnect Cable at this time.
Proceed to the
section titled "Powering the Charger" on page 25
TB2
P4
P3
JP5
TB1
F1CB1
JP2
JP1
P5
P7
R27
P2
EARTH GND AC NEU TRAL AC HOT
+ 24R COMM ON + 24 COMMON
POWER L IMITED
MPS- 24AE PC C REV ___
MPS- 24AP CC REV ___
MPS24A.
-
+
-
+
JP1
JP3
SW 1
JP4
TB3
TB4
TB2
ENABLE
AC DELAY
16 HR
DELAY
TENS
ONES
CU T F OR
240VAC
GND FLT
DI SAB LE
AM-1 ENABLE
ADDRESS
ON OFF
AM-1
JP5
JP2
F1
F2
J4
J1 J2
J3
F3
TB1
HOT
OUT
+
BAT
+
OUT
-
BAT
-
EARTH
NEUT
15 15
A- B- A+ B+
NC NO C
0
4
3
9
2
6
1
5
7
8
12
13
15
14
10
11
0
4
3
9
2
6
1
5
7
8
12
13
15
14
10
11
BAT + BAT -
Figure 2.10 Connecting Two 25 AH Batteries
Power Supply
CHG-75
25 AH
12V
25 AH
12V
Battery
Interconnect
Cable *
Battery +
Battery -
Out +
Out -
-
+
*Do not connect the Battery Interconnect Cable at this time.
Refer to "Powering the Charger" on page 25.
!
AC Power
Hot
Neutral
Earth
Battery
Terminal
chg7mp2f.cdr