Owner's manual

IPDACT-2(UD) - Configuration
III-33
Doc.DM385-I
Rev. 4.0
includes the passwords through which information is exchanged between the
IPDACT-2(UD) and the VisorALARM, monitoring time, etc.
The minimum configuration for an IPDACT-2(UD) which permits an installer to
use this installation mechanism is as follows:
a) If you do not have a DHCP server
Type of register Register
IPDACT-2(UD) IP address and mask 01
IPDACT-2(UD) access gateway 02
IPDACT-2(UD) account number 11
Main VisorAlarm IP address 12
Backup VisorAlarm IP Address 21
UDP Port 13
b) If you have a DHCP server
Type of register Register
IPDACT-2(UD) account number 11
Main VisorAlarm IP address 12
Backup VisorAlarm IP Address 21
UDP Port 13
After configuring these parameters and restarting the device, the installer
must re-access the telephonic console as previously described and access
register 04. Here the installer password configured in the VisorALARM must
be configured. If the IPDACT-2(UD) has IP connectivity with the
VisorALARM and the password is correct, the IPDACT-2(UD) will receive the
configuration defined in the profile configured in the VisorALARM.
Through this mechanism, the installed IPDACT-2(UD) is registered in the
Teldat VisorALARM which from this point begins to monitor the former and
the IPDACT-2(UD) receives the necessary configuration in order to exchange
information with the Teldat VisorALARM.
If the whole process has gone smoothly, the IPDACT-2(UD) will begin to
exchange monitoring messages with the VisorALARM and from this point
onwards the IPDACT-2(UD) telephone relays activate (the line status LED
lights up).
III - 3.1.4.
Configuration Example
In cases of configuring the IPDACT-2(UD) with the following data:
IP address: 192.168.1.100, mask 255.255.255.0
Access GW: 192.168.1.20
IPDACT-2(UD) account number: 1234