Fire Alarm Control Panel MS-2 & MS-4 MS-2E & MS-4E Instruction Manual Document 51512 10/18/2011 Rev: P/N 51512:G2 G2 ECN 11-740
Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
Software Downloads In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system.
Table of Contents Section 1: Product Description ............................................................................................. 10 1.1: Product Features ..........................................................................................................................................10 1.2: Specifications...............................................................................................................................................11 1.3: Controls and Indicators..........
Table of Contents Section 4: Operating Instructions ......................................................................................... 40 4.1: Switch Functions in Normal Mode ..............................................................................................................40 4.1.1: ACK - Acknowledge .........................................................................................................................40 4.1.2: Silence.....................................................
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies: • Underwriters Laboratories Standards • NFPA 72 National Fire Alarm Code Before proceeding, the installer should be familiar with the following documents.
MS-2 Two Zone Main Circuit Board IDC (4.7 K, ½ watt ELR) (supervised, power-limited) Zone 2 BZone 2 B+ Zone 1 BZone 1 B+ NAC (4.7KW, ½ watt ELR) 2.5A max. (supervised, power-limited) BB+ Trouble Relay (fail-safe) 2 amps @ 30 VDC (nonsupervised) Common Trouble (Normally Open) Normal (Normally Closed) Alarm Relay 2 amps @ 30 VDC (nonsupervised) Common Normally Closed Normally Open 24 VDC Special Application Resettable Power 500 mA max.
MS-4 Four Zone Main Circuit Board IDC (4.7 K, ½ watt ELR) TB3 (supervised, power-limited) NAC (4.7K, ½ watt ELR) TB2 2.5A max.
Section 1: Product Description The MS-2 is a two zone FACP (Fire Alarm Control Panel) and the MS-4 is a four zone FACP. The information in this manual refers to both the MS-2 and MS-4 unless otherwise specified. These control panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings.
Specifications Product Description Zone Enable/Disable (one per zone) • LED Indicators Fire Alarm (one per zone) Supervisory (one per zone) Trouble (one per zone) Maintenance (one per zone) AC Power NAC Disable Zone Disable NAC Fault System Trouble Power Trouble Walktest Alarm Silence Earth Fault LED (on circuit board) lights if zero impedance between FACP and ground exist Battery Fault (on circuit board) Charger Fault (on circuit board) • Piezo sounder for alarm, troubl
Product Description Controls and Indicators Initiating Device Circuits - TB3 Alarm Zones 1 & 2 (MS-2 and MS-4) Alarm Zones 3 & 4 (MS-4 only) Power-limited circuitry Operation: All zones Style B (Class B) Normal Operating Voltage: Nominal 20 VDC, Maximum 27 VDC Alarm Current: 15 mA minimum Short Circuit Current: 40 mA maximum Maximum Loop Resistance: 100 ohms End-of-Line Resistor: 4.
Controls and Indicators Product Description • Walktest • Zone Enable/Disable - Zone 1 • Zone Enable/Disable - Zone 2 • Zone Enable/Disable - Zone 3 (MS-4 only) • Zone Enable/Disable - Zone 4 (MS-4 only) LED Indicators • Fire Alarm Zone 1 - red LED • Fire Alarm Zone 2 - red LED • Fire Alarm Zone 3 - red LED (MS-4 only) • Fire Alarm Zone 4 - red LED (MS-4 only) • Supervisory Zone 1 - yellow LED • Supervisory Zone 2 - yellow LED • Supervisory Zone 3 - yellow LED (MS-4 only) • Supervi
Product Description Circuits 1.4 Circuits Input Circuits Two input IDCs (Initiating Device Circuits) on the MS-2 and four IDCs on the MS-4 provide Style B (Class B) configurations. All IDCs accept i3 detectors as well as conventional two-wire smoke detectors, four-wire smoke detectors and normally-open contact devices.
Optional Modules and Accessories Product Description condition exists. The 4XTMF mounts to the MS-2 main circuit board option module connectors J3 & J5 or the MS-4 main circuit board, occupying one of the two sets of option module connectors J3 & J5 or J4 & J6. 4XLMF LED Interface Module (MS-4 only) The LED Interface Module supports the RZA-4XF Remote Annunciator module. Annunciator wiring is supervised for open conditions by this module.
Notes 16 MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
Section 2: Installation The cabinet can be surface mounted or semi-flush mounted using the optional Trim Ring P/N: TR-1-R. The door is removable during the installation period by opening and lifting if off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional 0.250” diameter holes located at the bottom. Carefully unpack the system and check for shipping damage.
Installation Backbox Mounting Top Depth = 2.875” (7.3 cm) Door = 14.677” (37.28 cm) Depth = 3.05” (7.75cm) Door = 15.342” (38.97 cm) Bottom Depth = 4.75” (12.065 cm) ms-4cabb.wmf Battery Box = 8.5” (21.59 cm) Battery Box = 14.5” (37.384 cm) Figure 2.2 Backbox and Battery Box When using batteries larger than 7 Amp Hour (up to 18 Amp Hour), the BB-17F battery box (or UL-listed equivalent) must be installed. To install the BB-17F: 1. 18 Mount the FACP cabinet to the wall. 2.
Operating Power Installation 2.2 Operating Power ! WARNING: DISCONNECT POWER SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED. Primary Power Source (AC) and Earth Ground Connections AC power connections are made inside the control panel cabinet.
Installation Input Circuits 2.3 Input Circuits The MS-2 has two IDCs (Initiating Device Circuits) and the MS-4 has four IDCs. Each circuit is compatible with System Sensor’s i3 smoke detectors which generate a maintenance signal when the detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls below the detector rating. The maximum loop resistance limit for each IDC is 100 ohms.
Input Circuits Installation Combination Waterflow/Supervisory Zone A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. The following figure illustrates the wiring of Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit. Note that only Zone 1 on the MS-2 and Zone 2 on the MS-4 can be configured in this manner.
Installation Output Circuits 2.4 Output Circuits 2.4.1 Notification Appliance Circuits The MS-2 provides one Style Y (Class B) NAC (Notification Appliance Circuit) while the MS-4 provides two Style Y (Class B) NACs. Each circuit is capable of providing a maximum of 2.5 amps of current. Total current drawn from these as well as other DC power outputs cannot exceed 3.0 amps for the MS-2 or 6.0 amps for the MS-4 with the optional second transformer installed (refer to battery calculations section).
Output Circuits Installation 2.4.2 Special Application DC Power Output Connections Resettable 24 VDC special application power is available on both the MS-2 and MS-4 control panels. Nonresettable 24 VDC special application power is available only on the MS-4. Nonresettable Power (500 mA) -MS-4Only 24 VDC filtered, nonresettable special application power can be obtained from these terminals (power-limited) TB1 ms-4tb1.
Installation Power-limited Wiring Requirements 2.5 Power-limited Wiring Requirements Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpowerlimited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the MS-4 is illustrated below.
Installation of Optional Modules Installation 2.6 Installation of Optional Modules ! CAUTION: DISCONNECT POWER REMOVE ALL POWER (AC AND DC) BEFORE INSTALLING OR REMOVING MODULES OR WIRING. 2.6.1 CAC-4 Class A Converter Module (MS-4 only) Installation The CAC-4 Module can be used to convert the four Style B (Class B) Initiating Device Circuits to Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z (Class A).
Installation Installation of Optional Modules circuit. Do not wire to the corresponding A+ and A- terminals on the CAC-4 module. Note that Zone 1 IDC on the MS-2 and Zone 2 IDC on the MS-4 can be configured as a combination waterflow/supervisory circuit as illustrated in the following figure. IMPORTANT! All devices must be within 20 feet of the Class A portion of the circuit and wiring must be in conduit. Class B (Style B) IDC - 4.
Installation of Optional Modules Installation The following steps must be followed when installing each of these modules: Cut jumper JP1 (for connectors J3 and J5) and/or JP2 (for connectors J4 and J6) on the main circuit board to allow the control panel to supervise the placement of any installed option module. 3. Install the two supplied metal standoffs in the locations indicated. These standoffs provide the required earth ground protection. 4.
Installation Installation of Optional Modules Maximum Coil Resistance: 14.
Installation of Optional Modules Installation 4XZMF Zone Relay Module (MS-4 only) The 4XZMF provides four zone alarm, one system alarm and one system trouble Form-C relays. Nonpower-limited and power-limited wiring must have a minimum distance of 0.25”, wire to wire. If this module is used to drive nonpower-limited and power-limited circuits, follow the instructions below: Relay #1 through #4 will activate with Output #1 through #4 and remain latched. 4xzma.
Installation Installation of Optional Modules 4XLMF LED Interface Module (MS-4 only) The 4XLMF supports the RZA-4XF Remote Annunciator module. The wiring of this module must follow the requirements as specified in “Power-limited Wiring Requirements” on page 24. Important: The 4XLMF module can only be installed on connectors J3 and J5 of the MS-4 main circuit board. 4XLB +24 VDC Out #1 Out #2 Out #3 Out #4 System Trouble Sound Resound 1 2 3 4 5 6 7 8 4xlma.
Notes MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011 31
Section 3: Program Options via DIP Switch This section describes the programming options available via DIP switch settings. The FACP can be field programmed using option DIP switches SW1, SW2, and SW3 which are located in the bottom right side of the main circuit board. A factory-installed dip switch cover, which prevents accidental programming, must first be removed. Once programming is complete, the cover must be reinstalled.
DIP Switch Settings Program Options via DIP Switch 3.1 DIP Switch Settings The following tables list the programmable features for the MS-2 and MS-4. Placing a DIP switch in the ON position will select the feature while placing the DIP switch in the OFF position will deselect the feature. The exceptions to this rule are SW3 DIP switches 5 & 6. These two switches are used to select the Notification Appliance Circuit synchronization feature.
Program Options via DIP Switch Switch Number SW1 SW2 SW3 DIP Switch Settings DIP Switch Number DIP Switch ON 1 Silence Inhibit 2 Auto-silence 3 Temporal Coding 4 Selective Silence (if sync.
DIP Switch Settings Program Options via DIP Switch 3.1.1 SW1 DIP Switch Settings Silence Inhibit Switch 1, placed in the ON position, selects the Silence Inhibit feature. This feature prevents the silencing or resetting of the NACs (Notification Appliance Circuits) for a period of one minute after initiation of an alarm. Placing switch 1 to the OFF position deselects the Silence Inhibit feature. The factory default setting is switch 1 OFF for no Silence Inhibit.
Program Options via DIP Switch DIP Switch Settings IDC Combination Circuit Switch 8, placed in the ON position, sets IDC #1 on the MS-2 or IDC #2 on the MS-4 as a combination circuit. A combination zone can be used for monitoring supervisory devices such as valve tamper switches and alarm devices such as waterflow switches. Supervisory conditions, which latch via software, can be silenced by pressing the Acknowledge and then Silence buttons.
DIP Switch Settings Program Options via DIP Switch IDC1 Supervisory for MS-2 or IDC2 Supervisory for MS-4 Switch 4, placed in the ON position, programs IDC #1 on the MS-2 or IDC #2 on the MS-4 as a Supervisory circuit. A supervisory zone can be used for monitoring supervisory devices such as sprinkler tamper switches. A supervisory activation will pulse the piezo sounder at a ½ second rate and flash the zone supervisory LED at the same rate. The factory default setting is switch 2 OFF for no Supervisory.
Program Options via DIP Switch DIP Switch Settings NAC2 Disable (MS-4 only) Switch 4 only on the MS-4, placed in the ON position, will disable NAC #2, preventing the notification appliances from activating. This feature may be used during maintenance or while testing the system to prevent building evacuation. The FACP will indicate an NAC disabled fault and system trouble while this feature is selected. The factory default setting is switch 4 OFF for NAC2 enabled.
Notes MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011 39
Section 4: Operating Instructions The MS-2 and MS-4 have two modes of operation which are Normal and Walktest modes. Upon initial power-up, the system will be in Normal Mode. This section discusses operation of the control panel in the Normal Mode. 4.1 Switch Functions in Normal Mode 4.1.1 ACK - Acknowledge The Acknowledge button, which is located on the FACP membrane switch panel, silences the system piezo sounder and changes all flashing system LEDs to on steady.
Walktest Operating Instructions 4.1.5 Walktest The Walktest button, which is located on the FACP membrane switch panel, allows a panel walktest to be performed. Pressing and holding the Walktest button for a minimum of two seconds causes the FACP to enter audible walktest. Pressing the Walktest button and then the Silence button and holding both for a minimum of two seconds will cause the panel to enter silent walktest.
Operating Instructions Status LEDs During an audible walktest, if a device remains latched in alarm (such as a Pull Station that is not reset after activation), subsequent testing of devices on the same zone will not trigger the NACs. Be certain to reset or clear each device after testing. Silent Walktest To perform a silent Walktest, press the Walktest button, then press the Alarm Silence button and hold both for a minimum of two seconds.
Operation Operating Instructions Zone Fire Alarm LED A red LED for each zone that blinks to indicate that an alarm exists on the corresponding zone. It turns on steady when the Acknowledge or Alarm Silence button is pressed. Zone Supervisory LED A yellow LED for each zone that blinks if the zone has been programmed for supervisory and a supervisory condition exists on the corresponding zone. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Operating Instructions Operation 4.4.
Operation Operating Instructions • Pulse the FACP piezo sounder one second On and one second Off • Transfer fail-safe Trouble relay • Additional LEDs will turn on or blink according to the specific trouble NAC Disable LED if NAC has been disabled Zone Disable LED if a zone has been disabled NAC Fault LED if a fault is detected on an NAC Power Trouble LED if an AC, battery or charger fault is detected AC Power LED will turn off if AC fail or brownout occurs Alarm Silence LED if Silence but
Section 5: Power Supply Calculations 5.1 Overview This section contains instructions and tables for calculating power supply currents in alarm and standby conditions. This is a four-step process, consisting of the following: 1. Calculating the total amount of AC branch circuit current required to operate the system 2. Calculating the power supply load current for non-fire and fire alarm conditions and calculating the secondary (battery) load 3.
Calculating the System Current Draw Power Supply Calculations 5.3 Calculating the System Current Draw 5.3.1 Overview The control panel must be able to power all internal and external devices continuously during the non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when primary power is applied, use Calculation Column 1 in Table 5.3 on page 48. The control panel must support a larger load current during a fire alarm condition.
Power Supply Calculations Calculating the Battery Size Table 5.3 contains three columns for calculating current draws. For each column, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 5.4 on page 49.
Calculating the Battery Size Power Supply Calculations 1. Enter the totals from Table 5.3 on page 48, Calculation Columns 2 and 3 where shown. 2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below). 3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere hours. 4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH). 5.
Appendix A: NFPA Standard-Specific Requirements The MS-2 and MS-4 have been designed for use in commercial, industrial, and institutional applications and meet the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this Appendix.
Index Numerics B 2 Zone Main Circuit Board 8 4 Zone Main Circuit Board 9 411 15 411UD 15 4XLMF installation 26, 30 see also LED Interface Module 15 see also LED interface module 30 specifications 30 wiring to RZA-4XF 30 4XTMF installation 26, 27 operation 27 see also Transmitter Module 14 see also transmitter module 27 specifications 27 4XZMF installation 26, 29 see also Zone Relay Module 15 see also zone relay module 29 specifications 29 backbox dimensions 14, 17 mounting 17 battery 14, 19 precautions 1
D–L Index D description 10 device compatibility 10 Digital Alarm Communicator/Transmitter see also 411 & 411UD 15 dimensions backbox 14, 17 dip switch cover 32 DIP switch options see also programming 32 DIP switch settings 33 see also programming 32 disable see also zone enable/disable 11 disable NAC 37 dress panel 10, 15 E Earth Fault LED 43 earth ground 19 enable see also zone enable/disable 11 End-of-Line resistor IDC 12, 20, 21 NAC 12, 22 F fail-safe trouble relay 23 fail-safe relay see also trouble
Index M–S M main circuit board see also 2 Zone 8 see also 4 Zone 9 maintenance 20 piezo pulse rate 13 maintenance signal see also smoke detector monitoring 10 modes of operation see also normal and walktest 40 mounting cabinet 17 municipal box 27 municipal box transmitter see also 4XTMF 14 N NAC 9, 10, 12, 14, 22 coding 35 current 22 disable 37 End-of-Line resistor 12, 22 maximum current 12 nonsilenceable 37 see also Notification Appliance Circuit 8 wiring 22 NAC Disable LED 42 NAC Fault LED 42 nonpower-
T–Z Index option module placement 27 supervisory piezo pulse rate 13 see also programming supervisory 36, 37 supervisory relay 9, 10, 14, 23 contact rating 12 supervisory response 44 supervisory restoral 44 switch functions 40 synchronization Gentex 38 see also strobe synchronization 38 System Sensor 38 Wheelock 38 system current 10 system current calculations 47 System Sensor synchronization 38 System Trouble LED 42 T temporal coding 35 transformer assembly 14 rating 14 Transmitter Module 14 transmitter
Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009).
World Headquarters 1 Firelite Place Northford, CT 06472-1653 USA 203-484-7161 fax 203-484-7118 www.firelite.