Section 1: Product Description
The MS-2 is a two zone FACP (Fire Alarm Control Panel) and the MS-4 is a four zone FACP. The
information in this manual refers to both the MS-2 and MS-4 unless otherwise specified. These
control panels provide reliable fire signaling protection for small to medium sized commercial,
industrial and institutional buildings. The FACP is compatible with System Sensors i
3
detectors
which are microprocessor-based conventional smoke detectors that can transmit a maintenance
trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when
the ambient temperature falls below the detector rating (refer to System Sensors i
3
Installation and
Maintenance Instructions document I56-1800-00 for device specifications). In addition, the control
panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire
smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact
devices. Refer to the Fire•Lite Device Compatibility Document for a complete listing of
compatible devices.
Outputs include one NAC (Notification Appliance Circuit) on the MS-2 and two NACs on the MS-
4. Each FACP has a Form-C Alarm and Trouble relay and 24 VDC special application resettable
power. In addition, the MS-4 has a Form-C Supervisory relay and a nonresettable special
application power output. The FACP supervises wiring, AC voltage and battery level.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will
activate audible and visual signaling devices, illuminate an indicating LED, sound the piezo
sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify
a remote station or initiate a auxiliary control function. The MS-2E and MS-4E offer the same
features as the MS-2 and MS-4 but allows connection to 220/240 VAC.
1.1 Product Features
Style B (Class B) IDC (Initiating Device Circuit)
one zone programmable for combination supervisory and
waterflow
MS-2 - two IDCs
MS-4 - four IDCs
Style Y (Class B) NAC (Notification Appliance Circuit)
MS-2- one NAC
MS-4 - two NACs
Form-C Alarm Relay
Form-C Trouble Relay
Form-C Supervisory Relay (MS-4 only)
3.0 amps total system current standard for MS-2 and MS-4
6.0 amps total system current available for MS-4 with optional second transformer
Dress Panel DP-MS2/4
Optional Trim Ring P/N: TR-1-R for semi-flush mounting the cabinet
Control Buttons
ACK (Acknowledge)
Alarm Silence
Reset
Walktest
NOTE: Unless otherwise specified, the terms MS-2 and MS-4 are used in this manual to refer to
the MS-2 and MS-2E as well as the MS-4 and MS-4E FACPs respectively.