Manual

Document 52776 Rev A November 04, 2005
FACP
with Keltron RCVR/XMTR
Wiring Diagram
52776 Revision A
November 04, 2005
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
Sprinkler Supervisory Signal
Alarm/Trouble Signal
* Note: For more information,
refer to Keltron manual.
ECN 05-680
4XTMF
Note: Cut TBL jumper on 4XTMF/4XTM
module to send alarm/trouble signal from
the same pair of terminals.
CAUTION!
For reasons of wiring diagram clarity, terminal designa-
tions of Keltron modules are not shown in actual order.
Follow Keltron manual and module markings for exact ter-
minal locations to prevent severe module damage!
Fire Alarm Control Panel
(terminal blocks not shown in actual
positions)
(24 VDC,
Non-Resettable)
4XTMF Module