Addressable Fire Alarm Control Panel MS-9200UDLS MS-9200UDLSE MS-9200UDLSC Manual Document 52750 4/14/2014 Rev: H P/N 52750:H ECN 14-226
Fire Alarm & Emergency Communication System Limitations While a life safety system may lower insurance rates, it is not a substitute for life and property insurance! An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notification capability—can provide early warning of a developing fire.
Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
Software Downloads In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system.
Table of Contents Section 1: Product Description ............................................................................................. 13 1.1: Features and Options ...................................................................................................................................13 1.2: Specifications...............................................................................................................................................15 1.3: Controls and Indicators.............
Table of Contents 2.4: Relays...........................................................................................................................................................33 2.5: Notification Appliance Circuits ...................................................................................................................34 2.5.1: Style Y (Class B) NAC Wiring .........................................................................................................34 2.5.
Table of Contents Walktest................................................................................................................................................83 Zone Assignment..................................................................................................................................84 Noun/Adjective.....................................................................................................................................84 Description ............................
Table of Contents 3.7.4: Walktest ...........................................................................................................................................130 3.7.5: System..............................................................................................................................................131 3.7.6: Zone Setup .......................................................................................................................................
Table of Contents Section 5: Central Station Communications ...................................................................... 153 5.1: Transmittal Priorities .................................................................................................................................154 Section 6: Remote Site Upload/Download.......................................................................... 156 6.1: Remote Download ............................................................................
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies: • • Underwriters Laboratories/Underwriters Laboratories Canada National Fire Protection Association Before proceeding, the installer should be familiar with the following documents.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014 CAUTION! HIGH VOLTAGE (Supervised, Nonpower-Limited) 120 VAC, 60 Hx, 2.0 amps 220/240 VAC, 50 Hz, 1.2 amps TRANSFORMER 1 AC Power Transformer 1 Connector Transformer 2 Connector Important! Removing Ground Fault Disable Jumper JP7 voids UL/NFPA Style/Class identifications for circuits. Remove jumper JP7 only with the approval of the AHJ (Authority Having Jurisdiction). To disable ground fault detection, remove jumper/shunt from JP7.
Peripheral Devices and Their Documents: ANN Audio Control for ECC-50/100 Doc. #LS10001-000FL-E or ACC-25/50(ZS/T) Doc. #51889 ANN-RLY ANN-S/PG 10 Form-C ANN-LC Printer Driver Relay Card Lite-Connect module Doc. #151417 Doc. #53033 Doc. #LS10158-000FL-E ANN-I/O LED Driver Doc. #151416 ANN-80(C) LCD Text Annunciator/Indicator Doc. #52749 ANN-(R)LED LED Display Doc. #53032 IPDACT Internet Communicator Doc.
Section 1: Product Description The Fire-Lite MS-9200UDLS is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent addressable control panel has an extensive list of powerful features.The combination of Fire-Lite’s newer series devices and legacy 300 Series devices, along with the MS-9200UDLS FACP, offer the latest in fire protection technology.
Product Description Features and Options • Telephone Line Active LEDs • Communication Confirmation (Kissoff) LED • Touchtone/Rotary dialing • Programmable Make/Break Ratio • EIA-232 Printer/PC interface (variable baud rate) • 80-character LCD display (backlit) • Real-time clock/calendar with daylight savings time control • History file with 1,000 event capacity • Advanced fire technology features: Automatic drift compensation Maintenance alert Detector sensitivity test capability (N
Specifications Product Description ANN-RLED Annunciator Module annunciates alarms only ANN-LC Lite-Connect Module • Automated activation of the ACC-25/50(ZS/T) Audio-Command-Center • Legacy ACS/TERM Annunciators (cannot be used if ANN annunciators are used): ACS Series-LED Zone Annunciators LDM Graphic Annunciator Series LCD-80F Liquid Crystal Display point annunciator LCD-80FC Remote Fire Indicator (Canadian applications) ACM-8RF Relay Module 1.
Product Description Specifications Nonresettable or Resettable Special Application Power (24 VDC Nominal) - TB1, Terminals 1 (+) & 2 (-) Factory-set as nonresettable, suitable for powering annunciators Jumper selectable (JP4) for conversion to resettable power output Maximum ripple voltage: 20mVRMS Total DC current available is up to 1.0 amp (see Figure 1.
Controls and Indicators Product Description The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP. Special Application Nonresettable or Resettable Power Special Application Resettable or Nonresettable Power 1.0 amp max per circuit 1.0 amp max per circuit NAC #1 2.5 amps max NAC #3 2.5 amps max Standby 2.0 amps max per panel per circuit Alarm 6.
Product Description Digital Alarm Communicator/Transmitter Key Panel Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Components Product Description Cabinet The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel (DP-9692), which mounts to the inside of the cabinet (required by ULC for Canadian installations). Transformer Assembly Optional XRM-24B(E) xrm-24s.wmf One 100VA transformer is provided standard with the panel (3.0 amps maximum for output circuits).
Product Description Optional Modules 1.5.3 300 Series Intelligent Addressable Devices Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS9200UDLS FACP. The address of 300 Series devices cannot be set above 99. Refer to the SLC Wiring Manual for a list of compatible addressable devices. 1.5.4 Addressable Device Accessories End-of-Line Resistor Assembly The End-of-Line resistors are included with each module.
Accessories Product Description Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to “Remote Site Upload/Download” on page 156). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option. 1.7.2 DP-9692 Dress Panel dp9200udls.cdr An optional dress panel DP-9692 is available for the MS-9200UDLS (required by ULC for Canadian installations).
Product Description Accessories 1.7.6 Battery Charger CHG-75 Battery Charger The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS-9200UDLS FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel.
Accessories Product Description • A variety of optional annunciation devices can be connected to an ANN-BUS communication circuit. ANN Series devices can be connected to the primary communication circuit (EIA485) terminals on TB9. A secondary communication circuit for these devices is available at TB8. Each ANN-BUS communication circuit supports up to eight (8) annunciators.
Product Description Accessories ANN-LED Annunciator Module The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general system faults and input zones/points when used with a compatible FACP. The ANN-LED module provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or addressable points. The ANN-RLED provides alarm (red) indication for up to 30 input zones or addressable points.
Getting Started Product Description LDM Series Lamp Driver Modules (Graphic Annunciator) The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic LED annunciator. Legacy ACM-8RF Relay Control Module The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps.
Product Description Telephone Requirements and Warnings 1.9.2 Digital Communicator Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact: Manufacturer: Fire•Lite Alarms, Inc. One Fire-Lite Place Northford, CT 06472 (203) 484-7161 Product Model Number: MS-9200UDLS FCC Registration Number: US:1W6AL11B9200UDLS Ringer Equivalence: 1.
Telephone Requirements and Warnings 1.9.4 Product Description For Canadian Applications The following is excerpted from CP-01 Issue 5: NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s).
Section 2: Installation The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom. Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered.
Mounting Optional Transformer/Remounting Chassis Installation 2.2 Mounting Optional Transformer/Remounting Chassis One XRM-24B(E) transformer is supplied standard with the control panel. An optional second XRM-24B(E) transformer can be ordered and installed to provide maximum system power. Note that the XRM-24B and XRM-24BE are only suitable for use with MS-9200UDLS(E) with a main circuit board assembly number 9200UDLS-PCX Rev Y, where “X” and “Y” can be any letter or number.
Installation Mounting Optional Transformer/Remounting Chassis Semi-Flush Mounting Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box. Hinge Slot for optional Dress Panel Mounting slots for optional Trim Ring Semi-flush mounting hole 9050udencl.cdr Hinge Slot for optional Dress Panel Figure 2.
Mounting Optional Transformer/Remounting Chassis Installation Depth Top Door Backbox Depth Door Backbox Left Side Right Side Bottom Figure 2.4 MS-9200UDLS Cabinet Dimensions An optional Trim Ring (P/N TR-CE-) is also available for semi-flush mount installations.
Installation Power 2.3 Power ! WARNING: RISK OF EQUIPMENT DAMAGE AND PERSONAL INJURY SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED. 2.3.1 AC Power and Earth Ground Connection 2 J11 TRANSFORMER 1 J10 LC J1 HOT NEUT EARTH Primary power required for the FACP is 120 VAC, 60 Hz, 2.
Relays Installation 2.3.2 Battery Power The batteries must be sealed lead acid type. Before connecting the batteries to the FACP, make certain that the interconnect cable between the batteries is not connected. Do not connect the interconnect cable until the system is completely installed. Observe polarity when connecting the batteries. Connect the battery cable to J9 on the main circuit board. Refer to “Power Supply Calculations” on page 159, for calculation of the correct battery rating.
Installation Notification Appliance Circuits 2.5 Notification Appliance Circuits The control panel provides four Style Y (Class B) or four Style Z (Class A) NACs (Notification Appliance Circuits) when using the optional ZNAC-92 Class A converter module. Each circuit is capable of 2.5 amps of current. Total current in alarm for all external devices cannot exceed 6.0 amps (refer to “Calculating the System Current Load” on page 159). Use UL listed 24 VDC notification appliances only.
Remote Synchronization Output Installation 2.5.2 Style Z (Class A) NAC Wiring with ZNAC-92 Converter 4 Style Z (Class A) Notification Appliance Circuits, supervised and power-limited NAC 1 NAC 4 NAC 3 Polarized Bell NAC 2 Polarized Bell Polarized Bells Polarized Strobe Polarized Strobe Polarized Horns Polarized Horn 9200cnacz.
Installation UL Power-limited Wiring Requirements 2.7 UL Power-limited Wiring Requirements Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits.
UL Power-limited Wiring Requirements Installation Power-limited Circuits (Class 2) Power-limited Circuits (Class 2) Nonpower-limited Circuits Nonpower-limited Circuits Power-limited Circuits (Class 2) 92udculpw3.wmf maintain minimum 0.25” between power-limited and nonpower-limited circuits wiring Ferrite Clamps (See Section 2.8.1 for for more information.) AC Power Grounding Stud (see Figure 2.
Installation Digital Communicator 2.8 Digital Communicator Two independent telephone lines can be connected to the control panel. Telephone line control/command is made possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is critical that the panel's digital communicator be located as the first device on the incoming telephone circuit to properly function. Important! The DACT must not be used to dial a phone number that is call-forwarded.
Optional Module Installation Installation 2.8.1 Ferrite Clamp Installation Per FCC requirements, ferrite clamps (supplied) are required on both phone lines. Apply one clamp per phone line inside the FACP cabinet as shown in Figures 2.11 and 2.14. To install, simply close the clamp around the phone line until it snaps shut. It is not necessary to loop the phone line around the clamp. Simply clasp the clamp around the phone line. There is no need to loop the phone line around the clamp.
Installation Optional Module Installation Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the MS-9200UDLS. In addition, the System Trouble LED will turn on to indicate the Disconnect condition. Note: The 4XTMF Module is not directly suitable for transmitting a reverse polarity supervisory signal.
Optional Module Installation Installation TB5 TB6 TB8 TB9 Standoff NO NC C TB10 Standoff NC NO C Xmt Rcv Dtr Gnd A B In+ In- Out+ Out- + A B B+ A+ B- A- A B Slc Slc Slc Slc Shield 4XTM J5 & J6 Connectors J6 J5 4XTMF J7 JP3 Cut J um pe r J P 3 J12 PH15 PH16 PRI. PHONE LINE SEC. PHONE LINE FACP main circuit board 92udlsc4xtm.wmf SW1 Figure 2.
Installation Optional Module Installation 2.9.2 ANN-BUS Annunciators/Modules ANN-BUS Wiring This section contains information on calculating ANN-BUS wire distances and the types of wiring configurations (Class B). Calculating Wiring Distance for ANN-BUS Modules The following instructions will guide the installer in determining the type of wire and the maximum wiring distance that can be used with FACP ANN-BUS accessory modules.
Optional Module Installation Installation The following formulas were used to generate the wire distance chart: 6.0 Volts Maximum Resistance (Ohms) = Total Worst Case Current Draw (amps) Maximum Resistance (Ohms) Maximum Wire Length (feet) = *500 (6,000 feet maximum) Rpu where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below) Wire Gauge Ohms per 1,000 feet (Rpu) 22 16.2 18 6.4 16 4.02 14 2.
Installation Optional Module Installation Wiring Configuration Figure 2.18 illustrates the wiring between the FACP’s Primary ANN-BUS and ANN-BUS devices. 92udlsctoann80.wmf ANN-BUS and power wiring are supervised and power-limited B A (+) (-) 24 VDC nonresettable TB1 4 3 2 1 ANN-BUS Device Primary ANN-BUS + TB9 TB1 TB2 SLC SLC SLC SHIELD TB10SLC B+ A+ B- A- A B ANN ACS JP7 1 2 3 + - REMOTE PWR SUPPLY SYNC + 24V - + 24V NON-RST RST POWER POWER A B + MS-9200UDLS Figure 2.
Optional Module Installation Installation Powering ANN-BUS Devices from an Auxiliary Power Supply Figure 2.20 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as the FCPS-24FS6/8, when the total ANN-BUS power requirements exceed the panel’s DC Power Output capability. OUT3 - NAC3 + OUT2 - NAC2 + OUT1 - NAC1 + Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults). TB2 92udblsCtofcpstoann.
Installation Optional Module Installation Address Switch 5 Switch 4 Switch 3 Switch 2 Switch 1 not valid OFF OFF OFF OFF OFF 01 OFF OFF OFF OFF ON 02 OFF OFF OFF ON OFF 03 OFF OFF OFF ON ON 04 OFF OFF ON OFF OFF 05 OFF OFF ON OFF ON 06 OFF OFF ON ON OFF 07 OFF OFF ON ON ON 08 OFF ON OFF OFF OFF Switch 5 must be set to OFF for ANN-BUS devices to be recognized.
Optional Module Installation 4. Installation Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key. Annunciator backplate ann-80_iso2.wmf Annunciator cover with LCD display Press in latch and Pull annunciator cover open Key switch shown in OFF/Locked position Mounting The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical box.
Installation Optional Module Installation Wiring ANN-80 to FACP The following steps can be used as a guide to wire the annunciator. Make certain all power has been removed from the FACP prior to annunciator installation. 1. Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal block TB1 ann-80boxinside.wmf wiring channel wires TB1 2. Remove appropriate amount of wire insulation 3.
Optional Module Installation Installation The following table shows the ANN-80 connections to the MS-9200UDLS. MS-9200UDLS ANN-80 (TB1) Terminal GND (-) on TB1 Terminal 1 (-) Terminal PWR (+)TB1 Terminal 2 (+) Terminal Data (A) on TB9 Terminal 3 (A) Terminal Data (B) on TB9 Terminal 4 (B) Programming Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator must be added to the system via FACP programming.
Installation Optional Module Installation 5. Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure 2.22). Only one printer can be connected. Specifications • Operating Voltage: 24 VDC • Current (Alarm and Standby): 45 mA • Ambient Temperature: 32°F to 120°F (0°C to 49°C) • Max. Wiring Distance from FACP: 6,000 ft. (1,800 m) • Mounting: Surface • Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.
Optional Module Installation Installation Setting Printer Options Refer to the documentation supplied with the PRN-6F printer for instructions on using the printer menu controls. Set the printer options (under the menu area) as shown in the following table: Option Setting Option Setting Font HS Draft CPI 10CPI LPI 6 LPI Skip 0.
Installation Optional Module Installation ANN-I/O LED Driver Module ANN-I/O Board Layout Figure 2.23 illustrates the ANN-I/O board showing locations of screw terminals for connection to the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-BUS ID number. Terminals not used (future) ann-IObrd.cdr ANN-BUS (ID#) Address DIP switch ANN-BUS Connector Figure 2.23 ANN-I/O Board Layout Specifications • Max. ANN-BUS Voltage: 28 VDC • Max.
Optional Module Installation Installation ANN-I/O Connection to FACP The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.24. After the ANN-I/O is connected to the panel, it must be added to the system via FACP programming. Refer to the section titled “ANN-I/O Options” on page 108.
Optional Module Installation P1 LED1 annI-ioleds2.wmf Installation Pin # 1 2 LED2 3 LED3 4 LED4 5 LED5 6 LED6 LED7 7 LED8 8 LED9 9 LED10 10 LEDs LED Power 11 Anode no connection 12 P2 LED11 LED12 LED13 LED14 LED15 LED16 Cathode Pin # 1 2 3 4 5 6 LED17 7 LED18 8 LED19 9 LED20 10 LEDs LED Power 11 Anode no connection 12 Cathode Figure 2.25 ANN-I/O LED Wiring ann-ledstacked.wmf ANN-LED Annunciator Module Figure 2.
Optional Module Installation Installation Specifications • Max. ANN-BUS Voltage: 24 VDC • Max. Current: Alarm: 68 mA Standby: 28 mA • Operating Temperature: 32°F to 120°F (0°C to 49°C) • For indoor use in a dry location only Mounting/Installation ann-led.wmf The ANN-LED Module is supplied with a metal backbox, mounting bracket, and cover. Refer to the ANN-LED Installation Document #53032 for more information. Figure 2.
Installation Optional Module Installation ANN-LED Board Layout and Connection to FACP Figure 2.28 illustrates the ANN-LED board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number. 1 2 3 4 5 6 7 8 SW1 JP2 ANN-BUS (ID#) Address DIP switch 92udlsctoled.
Optional Module Installation Installation Mounting/Installation FACP Chassis Installation ann-rlyinchassis.wmf The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis or inside the ROME Series enclosure. Refer to the ANN-RLY Installation Document #53033 for instructions on chassis mounting or to the ROME Series Installation Document #53530 for mounting in the separate backbox.
Installation Optional Module Installation ANN-RLY Board Layout and Connection to FACP Figure 2.30 illustrates the ANN-RLY board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number. JP2 ANN-BUS (ID#) Address DIP switch 1 2 3 4 5 6 7 8 SW1 J1 TB2 92udlsctorly.
Optional Module Installation Installation Mounting The ANN-LC mounts inside the FACP cabinet. Slide the two tabs of the bracket into the backbox protrusions on the lower right side. Secure with the included self-tapping screw. Refer to the ANN-LC Product Installation Document for more information. backbox ANN-LC FLLCmnttabs.wmf protrusions Figure 2.31 Mounting the ANN-LC into the Backbox Wiring the ANN-LC to the Panel The ANN-LC connects to the MS-9200UDLS via the FACP’s secondary ANN-BUS.
Installation Optional Module Installation A parallel printer may also be connected to the FACP using the optional ANN-S/PG Serial/Parallel Interface Module. Refer to “ANN-S/PG Serial/Parallel Interface Module” on page 23 for installation details. Refer to “ANN-BUS Options” on page 107 for programming information. ! CAUTION: POSSIBLE EQUIPMENT DAMAGE DO NOT CONNECT A PRINTER OR PC TO THE MS-9200UDLS FACP IF A GROUND FAULT (ZERO IMPEDANCE TO GROUND) EXISTS ON THE CONTROL PANEL. CIRCUIT DAMAGE MAY RESULT.
Automatic Audio Panel Control Installation 2.9.4 ECC-FFT Firefighter Telephone B The ECC-FFT connects from TB1 (non-resettable aux power) on the FACP to the DC Power input on the ECC-FFT board. - + A ECC-FFT TB1 TB2 MS-9200UDLS TB3 TB4 JP7 + - REMOTE PWR SUPPLY SYNC + 24V - + 24V NON-RST RST POWER POWER 1B+ 3B+ 3B- 1B- 2B+ 4B+ 4B- 2B- 9200udlsctofft.wmf + Figure 2.34 ECC-FFT Connections 2.
Installation Automatic Audio Panel Control Connect the ECC-50/100 panel’s FACP Data Bus at TB13 to TB9 on the MS-9200UDLS FACP. to other ACS/ANN devices ECC-50/100 B + TB8 OUT+ IN+ OUT- IN- TB9 ACS TB10 SLC B+ SLC SLC SLC A+ B- A- SHIELD A B MS-9200UDLS 9200udecc.wmf A ANN ACS Figure 2.
Section 3: Programming NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES This product incorporates field-programmable software.
Programming User Programming 3.2 User Programming The MS-9200UDLS is completely field programmable and requires no special software skills. While programming the MS-9200UDLS, the fire protection capabilities of the control panel are enabled. Site-specific programming may be accomplished in any of the following ways: • Autoprogramming Feature - This is a convenient method for quickly bringing the FACP addressable SLC devices on-line without the necessity of programming each device individually.
Initial Power-up Programming User Programming Levels There are two user programming levels: • User Master Program Level 1 is used for programming panel specific data relating to device types, zoning, messages, control panel functions, etc. • User Maintenance Program Level 2 is used by a qualified operator to access features such as Disable/Enable, View and Clear History, Walktest and System Time Change. 3.
Programming Master Programming Level To enter the user Programming mode, press 2.
Master Programming Level Programming When Autoprogram is selected, the control panel will begin autoprogramming the system by communicating with each addressable device installed on the SLC loop.
Programming Master Programming Level When the last digit is keyed-in, the following screen will be displayed: DETECTOR TYPE 1=SMOKE(PHOTO) 2=USER-DEFINED-1 3=SMOKE(ION) Press the down arrow key to view additional choices. Press the number corresponding to the desired selection to program that type to the newly added detector.
Master Programming Level Programming If no detectors have been installed on the loop, the following will be displayed: NO DETECTOR INSTALLED Edit Detector Screen #1 If the selected address has been added to programming, device summary screens will be displayed. These screens allow the programmer to view all device settings at a single glance. Pressing the left or right arrow keys will allow the programmer to rapidly view the devices at the previous or next address (if installed).
Programming EDIT DETECTOR 1=ENABLED 2=TYPE 3=VERIFICATION Edit Detector Screen #2 EDIT DETECTOR 1=ENABLED 2=TYPE 3=VERIFICATION Edit Detector Screen #2 Master Programming Level Enable/Disable Detector To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No.
Master Programming Level EDIT DETECTOR 1=WALKTEST 2=PAS 3=PRE-SIGNAL Edit Detector Screen #3 Programming Walktest The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation. To enable a device for the Walktest feature, press 1 while viewing the Edit Detector Screen #3 until the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No.
Programming Master Programming Level With the preceding program settings, when the detector with address 005 is activated, zone Z98 will cause its associated control module to activate immediately, sounding the connected signaling device to indicate the Pre-signal condition. Following the Pre-signal delay time, zone Z001 will cause its associated control module to activate and the control panel will initiate an alarm condition.
Master Programming Level Programming Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the detector currently being programmed. When an adjective has been selected, it will appear at the top of the display as indicated by the asterisks.
Programming Master Programming Level Description EDIT DETECTOR 1=NOUN/ADJECTIVE 2=DESCRIPTION Edit Detector Screen #5 The Description selection allows the programmer to enter additional information about the detector currently being programmed. This information will be displayed as part of the device label on the display.
Master Programming Level Programming Module Programming POINT PROGRAM SELECT TYPE 1=DETECTOR 2=MODULE Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or change the programming of an addressable module.
Programming Master Programming Level Edit Module Screen for Monitor Module The programmer can change a modules existing or factory default programming by pressing 3 in the Modules Screen. The following screen will be displayed: EDIT MODULE ENTER MODULE ADDRESS Edit Module Screen A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 012.
Master Programming Level Programming If the selected address corresponds to a monitor module, a screen displaying information about the module with the selected address will be displayed as illustrated in the following: NORMAL MONITOR ZNNN 1M012 EDIT MONITOR 1M012 1=ENABLED YES 2=TYPE MONITOR Edit Monitor Screen #2 EDIT MONITOR 1M012 1=WALKTEST YES 2=ZONE ASSIGNMENT 00 Edit Monitor Screen #4 EDIT MONITOR 1=PRE-SIGNAL 1M012 NO Edit Monitor Screen #3 EDIT MONITOR 1M012 1=ADJECTIV
Programming Master Programming Level Monitor module type selection will affect the function of the point as follows: Monitor Type Pull-Station User-Defined-1 Waterflow User-Defined-2 Monitor User-Defined-3 Future Future Smoke-Conventional User-Defined-5 Heat-Conventional User-Defined-6 Medic-Alert 1 User-Defined-7 Hazard-Alert 1 User-Defined-8 Tornado-Alert 1 User-Defined-9 Phone User-Defined-10 Tamper User-Defined-11 Supervisory User-Defined-12 Supervisory-AR 2 User-Defined-13 HVAC OVRRIDE 3 Power-Monito
Master Programming Level EDIT MONITOR 1=PRE-SIGNAL Edit Monitor Screen #3 Programming Pre-signal To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display reads Pre-signal Yes. Each press of the 1 key will cause the display to toggle between Pre-signal Yes and Pre-signal No. Refer to“Presignal” on page 141 for additional information.
Programming Master Programming Level 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the monitor module currently being programmed.
Master Programming Level EDIT MONITOR 1=NOUN/ADJECTIVE 2=DESCRIPTION Edit Monitor Screen #5 Programming Description The Description selection allows the programmer to enter additional information about the monitor module currently being programmed. This information will be displayed as part of the device label on the LCD display.
Programming Master Programming Level Edit Module Screen for Control Modules MODULES 1=ADD 2=DELETE 3=EDIT The programmer can change a module’s existing or factory default programming by pressing 3 in the Modules Screen. The following screen will be displayed: EDIT MODULE ENTER MODULE ADDRESS Modules Screen Edit Module Screen A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 002.
Master Programming Level EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE Edit Control Screen #2 Programming Type To select the type of control module being programmed, press the 2 key while viewing the Edit Control Screen #2. This will cause the control panel to display the following Control Type Screens. Press the down arrow key to view additional screens and selections.
Programming Master Programming Level Zone Assignment A maximum of five zones can be programmed to each addressable control module. Pressing 2 while viewing Edit Control Screen #3 displays the following screen: ZONE ASSIGNMENT Z00 Z Z Z Z Zone Assignment Screen Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left.
Master Programming Level 1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN Noun/Adjective Screen Programming Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the control module currently being programmed.
Programming EDIT CONTROL 1=ADJECTIVE/NOUN 2=DESCRIPTION Edit Control Screen #4 Master Programming Level Description The Description selection allows the programmer to enter additional information about the control module currently being programmed. This information will be displayed as part of the device label on the display.
Master Programming Level Programming 3.6.
Programming Master Programming Level panel. Do not assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condition. Attempting to do so will generate an error message and will be prevented by software checks. Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause the display to toggle between Pre-signal 98 On and Pre-signal 98 Off.
Master Programming Level ZONE SETUP 1=ZONE TYPES 2=ZONES AVAILABLE 3=ZONE MESSAGE Zone Setup Screen #3 Programming Zone Type Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on the control panel.
Programming Master Programming Level Zone Message Pressing 3 while viewing Zone Setup Screen #3 will display the following screen: ZONE 1=Z00 2=Z01 3=Z02 MESSAGE NO MESSAGE MESSAGE 1 NO MESSAGE Pressing the down arrow key will display additional screens for Zones up to Z99. Press the number key corresponding to the Zone to be programmed. Screens will be displayed allowing the programmer to select Audio Messages 1 through 14.
Master Programming Level Programming Device Addressing It is important to note that the MS-9200UDLS addressable device capacity is 99 detectors and 99 control/monitor modules. Newer devices can be set to addresses higher than 99 but these addresses will not function with the MS-9200UDLS. Note that It is permissible to mix old and new devices on the same loop but the FACP must be set for CLIP mode when older devices are installed. 3.6.
Programming Master Programming Level Trouble Reminder The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for alarms and troubles, after the panel has been silenced. Refer to “System Setup” on page 91, for a detailed description of this feature. Pressing 1 while viewing System Setup Screen #1 will cause the display to toggle to Trouble Rem On, which enables this feature. Each press of the 1 key will cause the display to toggle between Trouble Rem On and Trouble Rem Off.
Master Programming Level SYSTEM SETUP 1=TROUBLE REM 2=BANNER 3=TIME-DATE Programming Time-Date The control panel time and date can be changed by pressing 3 while viewing the System Setup Screen #1. The following screen will be displayed: System Setup Screen #1 TIME AND DATE 1=DAYLIGHT SAVINGS TIME AND DATE 1=TIME 10:00 AM 2=DATE 04-07-2006 3=CLOCK FORMAT 12HR Time-Date Screen #2 Time-Date Screen #1 Time To change the time, press 1 while viewing the Time-Date Screen.
Programming TIME AND DATE 1=DAYLIGHT SAVINGS Master Programming Level Daylight Savings Time Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed: Time & Date Screen #2 DAYLIGHT SAVINGS 1=END MONTH NOV 2=END WEEK WEEK-1 DAYLIGHT SAVINGS 1=ENABLED YES 2=START MONTH MAR 3=START WEEK WEEK-2 Daylight Savings Screen #2 Daylight Savings Screen #1 Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between Enabled Yes and Enabled N
Master Programming Level Programming Pre-signal Delay The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of 001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen #1. The following screen will be displayed: PRESIGNAL DELAY RANGE 0-180 SECONDS Pre-signal Delay Screen A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 009 for nine seconds.
Programming Master Programming Level A flashing cursor will appear in the lower left corner of the display. Type the two digit AC loss reporting delay in hours (00 to 23 hour delay). When the second digit is entered, the display will return to AC Loss Delay Screen #1. NOTE: Upon the loss of AC power at the control panel, relays programmed for ‘AC Loss’ will transfer immediately, regardless of the AC Loss Delay setting.
Master Programming Level Programming The following table contains NAC type codes and their functions: NAC Type Code Special Function Bell None Horn None Strobe None Synced Strobe Synchronized to manufacturer Strobe Sil Sync Same as Synced Strobe but Silence turns off audible & visual devices Future Use None Future Use None Future Use None Blank None Silenceable Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No.
Programming Master Programming Level Coding (only for NACs not programmed as Sync Strobe Type) The Coding feature allows the programmer to select the type of output that the main circuit board notification appliances will generate when activated.
Master Programming Level NAC # 1=ZONE 00 00 00 00 00 2=SIL INHIBITED NO NAC Screen #3 Programming Zone A maximum of five zones can be programmed to each main circuit board NAC. Pressing 1 while viewing NAC Screen #3 displays the following screen: ZONE ASSIGNMENT Z00 Z Z Z Z Zone Screen Note that Z** represents the Zone Number(s) corresponding to the selected NAC. The factory default for an unprogrammed device is Z00 for general alarm zone.
Programming SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS Master Programming Level Relays Pressing 3 while viewing System Setup Screen #2 will allow the programmer to configure two System Setup Screen #2 main circuit board Form-C relays from the following screen: RELAYS 1=RELAY 1 2=RELAY 2 3=RELAY 3 Relays Selection Screen To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no effect on its programming.
Master Programming Level Programming The Canadian Options configures the FACP with the following as required by Canada: • The following monitor module type codes are not available: monitor non-latching supervisory non-latching drill non-latching process monitor process monitor hazard tornado medical alert • The auto-silence timer is fixed at 20 minutes and cannot be changed. • Addressable ionization smoke detector sensitivity is automatically monitored using Canadian specifications.
Programming Master Programming Level Pressing 2 while viewing the Node Mode Setup Screen will allow the programmer to enter the address of the node on the Lite-Connect circuit.. NODE ADDRESS ENTER NODE ADDRESS RANGE 02-17 Node Mode Setup Screen A flashing cursor will appear in the lower left corner of the display. Enter the two-digit address which can be a value between 02 and 17. (Address 01 is reserved for the hub.
Master Programming Level Programming Erase History The Erase History option allows a user to erase all events from the history file. This will provide a clean slate in order to use the history file to track future events. Pressing 2 while viewing the History Screen will display the following screen: ERASE HISTORY PROCEED ? 1=YES 2=NO Erase History Screen Pressing 1 while viewing the Erase History Screen will erase all events from the History file.
Programming Master Programming Level Pressing 2 for View Points while viewing the Unit In Walktest screen will display one of the following screens: NO POINTS IN SYSTEM OR UNTESTED POINTS 010 1D001 SMOKE (PHOTO) NOT TESTED If the system has no points installed, the first screen will be displayed. If points are installed, the second screen will be displayed, which allows the viewing of all untested system points and their status relating to the current walktest session.
Master Programming Level Programming Annunciators Pressing 1 while viewing the Options Screen will cause the control panel to display the following screens: ANNUNCIATORS 1=TERM ENABLED NO 2=ACS OPTIONS 3=ANN-BUS OPTIONS An LCD-80F Terminal Mode annunciator, ACS BUS annunciator, or ANN-BUS annunciator/module can be installed in the MS-9200UDLS system. Refer to “Guidelines” on page 22 for rules governing the use of various annunciator types.
Programming Master Programming Level Annunciator addressing is specific to the MS-9200UDLS control panel. The following table describes the annunciator addresses and the corresponding addressable devices that will be annunciated at each annunciator address.
Master Programming Level ANNUNCIATORS 1=TERM ENABLED NO 2=ACS OPTIONS 3=ANN-BUS OPTIONS Programming ANN-BUS Options Pressing 3 for ANN-BUS Options, while viewing the Annunciators screen, will cause the following screens to be displayed:. Annunciators Screen #3 ANN-BUS SELECT 1=PRIMARY 2=SECONDARY 3=ANN-BUS OPTIONS ANN-BUS Select Screen A printer module, graphic annunciator module, LCD annunciator module, LED annunciator module and relay module can be programmed into the MS-9200UDLS system.
Programming Master Programming Level Press the number corresponding to the module/device type that is installed with the selected address. NOTE: If the module type selected is the ANN-80, ANN-S/PG, or ANN-ACC or if Not Installed is selected, the ANN-BUS Address Screen shown on the previous page will be displayed following the module selection.
Master Programming Level Programming ANN-I/O Zone Option If Zone is selected as the module option, the first ten LEDs on the first ANN-I/O module will display the system status information. The remaining 30 LEDs on the first module and 40 LEDs on the remaining modules will display the active/alarm status of each zone in the Zone Range programmed for that particular module. The LED assignments for each ANN-I/O module will be as follows.
Programming Master Programming Level ANN-I/O Point Option If Point is selected as the module option, the first ten LEDs on the first ANN-I/O module will display the system status information. The remaining 30 LEDs on the first module and 40 LEDs on each additional module will display the active/alarm status of each point in the Point Range programmed for that particular module.
Master Programming Level PRIMARY ANN-BUS 1=ENABLED YES 2=MODULES INSTALLED 3=AUTO-CONFIGURE ANN-BUS Screen #2 Programming ANN-LED Options Pressing 2 for Module Options while viewing the ANN-BUS Address Screen when the ANN-LED option is selected, will display the following screen: ANN-LED - ADDR X-1 SLC 1 DET 1-10 ALARM, TBL, SUPV ANN-LED Address Screen #1 ANN-LED - ADDR X-1 1=POINT/ZONE 2=ALARM/ATS ANN-LED - ADDR X-1 1=RANGE 2=DET/MOD ANN-LED Address Screen #2 ANN-LED Address Screen #3 The first
Programming Master Programming Level Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Zone 30 Active/Alarm Zone 31 Active/Alarm Zone 32 Active/Alarm Zone 33 Active/Alarm Zone 34 Active/Alarm Zone 35 Active/Alarm Zone 36 Active/Alarm Zone 37 Active/Alarm Zone 38 Active/Alarm Zone 39 Active/Alarm Zone 40 Active/Alarm Zone 41 Active/Alarm Zone 42 Active/Alarm Zone 43 Active/Alarm Zone 44 Active/Alarm Zone 45 Active/Alarm Zone 46 Active/Alarm
Master Programming Level Programming Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Zone 10 Active/Alarm Zone 11 Active/Alarm Zone 12 Active/Alarm Zone 13 Active/Alarm Zone 14 Active/Alarm Zone 10 Trouble Zone 11 Trouble Zone 12 Trouble Zone 13 Trouble Zone 14 Trouble Zone 10 Supervisory Zone 11 Supervisory Zone 12 Supervisory Zone 13 Supervisory Zone 14 Supervisory Zone 15 Active/Alarm Zone 16 Active/Alarm Zone 17 Active/Alarm Zone 18
Programming Master Programming Level Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Point 31 Active/Alarm Point 32 Active/Alarm Point 33 Active/Alarm Point 34 Active/Alarm Point 35 Active/Alarm Point 36 Active/Alarm Point 37 Active/Alarm Point 38 Active/Alarm Point 39 Active/Alarm Point 40 Active/Alarm Point 41 Active/Alarm Point 42 Active/Alarm Point 43 Active/Alarm Point 44 Active/Alarm Point 45 Active/Alarm Point 46 Active/Alarm Point
Master Programming Level Programming Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Point 11 Active/Alarm Point 12 Active/Alarm Point 13 Active/Alarm Point 14 Active/Alarm Point 15 Active/Alarm Point 11 Trouble Point 12 Trouble Point 13 Trouble Point 14 Trouble Point 15 Trouble Point 11 Supervisory Point 12 Supervisory Point 13 Supervisory Point 14 Supervisory Point 15 Supervisory Point 16 Active/Alarm Point 17 Active/Alarm Point 18 Act
Programming [SELECTED] ANN-BUS 1=ENABLED YES 2=MODULES INSTALLED 3=AUTO-CONFIGURE ANN-BUS Screen #2 Master Programming Level Auto-Configure The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed ANN-BUS modules online on the selected ANN-BUS. The software will search the selected circuit for all ANN-BUS modules and automatically program the device type and address into the system.
Master Programming Level Programming Pressing 3 for Parity while viewing ANN-S/PG Options screen #2 will cause a screen to appear which allows the user to select between No Parity, Even Parity, or Odd Parity. Pressing 1 for Stop Bits while viewing ANN-S/PG Options screen #3 will cause a screen to appear which allows the user to select between 1.0 or 2.0 Stop Bits.
Programming Master Programming Level The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether the Reset button on any installed ANN-80 annunciator will function normally or always be ignored. Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No (Reset button never functions).
Master Programming Level Programming To select the type, press 1 while viewing the Secondary Phone Line screen. The following screen will be displayed: PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 3=ROTARY 62/38 Secondary Phone Type Screen Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33, or 3 to select Rotary dialing with a make/break ratio of 62/38.
Programming Master Programming Level Trouble Call Limit (Dialer Runaway Prevention) The Call Limit option limits the number of DACT trouble calls to the Central Station, to a programmed amount between 0 and 99, for each unique trouble within a 24 hour period. Separate limit counters keep track of each unique type of trouble. Note that the number of phone line (communication) faults called to the Central Station are not limited by this feature.
Master Programming Level Programming Account Code Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following screen to be displayed: ACCOUNT CODE 4 CHAR RANGE 0-F Account Codes Screen The Account Code, which is assigned by a Central Station, depends on the communication format being used. The Account Code screen will have a flashing cursor in the lower left corner. Enter the supplied account code using 0 - 9 and A- F keys.
Programming Master Programming Level The Communication Format is determined by the type of receiver that the DACT is transmitting to. Consult your Central Station for proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the event codes. Select the Communication Format by pressing the corresponding number key while viewing the Comm Format screen.
Master Programming Level PHOTO W/HEAT DET-USER-DEF-5 DUCT SUPERVISORY DET-USER-DEF-6 PHOTO SUPERV DET-USER-DEF-7 PHOTO ADAPT DET-USER-DEF-8 PHOTO BEAM DET-USER-DEF-9 MONITOR MON-USER-DEF-3 SMOKE CONVEN MON-USER-DEF-5 HEAT CONVENTIONAL MON-USER-DEF-6 MEDIC ALERT MON-USER-DEF-7 HAZARD ALERT MON-USER-DEF-8 TORNADO ALRT MON-USER-DEF-9 MON-PHONE MON-USER-DEF-10 TAMPER MON-USER-DEF-11 MON SUPERVISORY MON-USER-DEF-12 MON SUPERV AUTO MON-USER-DEF-13 HVAC OVRRIDE POWER MON MON-USER-DEF-14 TROUBLE MON MON-USER-DEF-15
Programming Master Programming Level ACS/ANN-BUS FAULT LCD_80F FAULT NAC 1 DISABLE NAC 2 DISABLE NAC 3 DISABLE NAC 4 DISABLE CS CALC FAULT CHARGER FAULT OPTION CARD 1 FAULT REMOTE SYNC FAULT ZONE DISABLE NAC_KEY_FLT NO_DEVICES_INSTLLD OFF_NORMAL_MESSAGE 24_HOUR_TEST 24 HOUR ABNORMAL TES UPDOWN REQUEST UPLOAD SUCCESS DOWNLOAD SUCCESS UPDOWN FAILURE GENERAL_ALARM GENERAL_SUPERVISORY MNS OVERRIDE AUDIO MESSAGE 333 330 521 522 526 527 304 300 331 332 570 300 380 308 602 608 411 416 412 413 000 000 580 000 0
Master Programming Level OPTION MODULES 1=ANNUNCIATORS/UDACT 2=ON BOARD DACT 3=PRINTER/PC NO Option Module Screen Programming Printer/PC A Printer or a PC can be connected to the control panel. Pressing 3 while viewing the Option Module Screen will cause the following screen to appear: PRINTER-PC 1=PRINTER NO SU NO 2=PRINTER SU YES 3=PC NO Printer-PC Screen Pressing 1 while viewing the Printer-PC Screen will program the control panel for an unsupervised (NO SU) printer.
Programming Master Programming Level The following screen will appear when any change option is selected: ENTER NEW FIVE DIGIT PASSWORD Enter Password Screen A flashing cursor will appear in the center of the display. Enter a new five digit password (such as 10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed: VERIFY NEW PASSWORD Password Change Screen Re-enter the new password to accept the change.
Maintenance Programming Level PROGRAM CHECK 1=NACS NO INPUT 2=ZONES NO INPUT 3=ZONES NO OUTPUT Program Check Screen Programming Pressing 1 while viewing the Program Check screen will display an NAC screen similar to the following. NACS NO INPUT NAC 1 25 31 44 55 67 The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 and 67 but no input devices have been programmed to any of these zones.
Programming Maintenance Programming Level Note that in the preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key, as shown in the following screen. PROGRAMMING 1=WALKTEST 2=SYSTEM 3=ZONE SETUP 3.7.
Maintenance Programming Level Programming will be displayed on the screen. To view all of the selected events, press the up or down arrow keys to scroll through the list of events. If no events have occurred, the display will read NO EVENTS IN HISTORY.
Programming Maintenance Programming Level The Zone No Output feature allows the programmer to view the zones which have not been programmed to at least one output device (not including general alarm Zone 00). The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an addressable detector with an address of 001 on loop 1 but have not been programmed to any output devices. Use the up and down arrow keys to view all the zones without output assignments. 3.7.
Maintenance Programming Level Programming Pressing 3 for View Summary while viewing the Unit In Walktest screen will display a new screen which will show a total of the tested detectors, tested modules, untested detectors and untested modules for the current walktest session. To end the Walktest session, press the Escape key to return to the Walktest screen.
Programming Maintenance Programming Level Pressing 1 while viewing Zone Setup screen will display the following screen: Z ZONE TO ENABLE Enable Screen A flashing cursor appears to the right of the Z. To enable a zone, enter the two digit zone number (00 - 99). After the second digit is entered, the zone will be enabled and the cursor will return to the original position. The next zone to be enabled can then be entered. Press Esc (Escape) to return to the previous screen.
Section 4: Operating Instructions 4.1 Panel Control Buttons 4.1.1 Acknowledge/Step The first press of the Acknowledge/Step key silences the piezo sounder, changes flashing LEDs to steady and also changes the status field on the LCD display from capital letters to small letters. When the piezo is silenced, an acknowledge message is sent to the printer and the history file. Acknowledge also sends a silence piezo command to the optional annunciators connected to the FACP.
Operating Instructions Normal Operation Supervisory This is a yellow LED that flashes when one or more supervisory conditions occur, such as a sprinkler valve tamper condition. It illuminates steady when the Acknowledge/Step or Alarm Silence key is pressed. It turns off when the Reset key is pressed and remains off if all supervisory alarms have been cleared. Trouble This is a yellow LED that flashes when one or more trouble conditions occur.
Trouble Operation Operating Instructions Monitors AC input voltage and battery voltage Monitors and reports status of SLC loop, option cards and control panel Polls all devices on the SLC loop and flashes each device LED while checking for valid replies, alarms, troubles, etc. Refreshes LCD display and updates time Scans control panel keypad for key presses Performs autotest for all SLC devices Tests memory Updates and reads all communications busses (EIA-485, EIA-232, etc.) 4.
Operating Instructions Alarm Operation – OPEN - indicating an open circuit on an addressable device – DIRTY1 - maintenance alert indicating that a detector is near but below the allowed alarm limit and is in need of maintenance before the performance is compromised – DIRTY2 - maintenance alert indicating that a detector needs immediate maintenance since it has been within 80% of its alarm threshold for 24 hours – INVREP - maintenance alert indicating a hardware or communication problem in the detector – T
Supervisory Operation Operating Instructions • Terminate upload or download communications • Alarms must be Acknowledged before the FACP can be reset A typical alarm display would be as illustrated below: ALARM PULL STATION Z000 10:00A 010810 1M001 Note that the device type, which in this example is PULL STATION, can be any other programmable alarm type.
Operating Instructions Process Monitor Operation A typical Supervisory event would be displayed as illustrated in the following: ACTIVE SUPERVISORY Z000 10:00A 012110 1M001 Note that, like alarms, supervisory signals latch (except when programmed for supervisory autoresettable) and can be assigned to software zones. Supervisory alarms do not cause resound as do other alarm conditions.
Medical Alert Condition Operation Operating Instructions 4.9 Medical Alert Condition Operation Medical alert operation is: • not intended for nurse call stations (applications) per UL1069. • not intended for signaling professional medical staff. • to be used for summoning security guards or other trained personnel within the facility • intended for Manual activation.
Operating Instructions Programmed Zone Operation 4.12 Programmed Zone Operation Each addressable detector and monitor module can be assigned to a maximum of five software alarm zones. A general alarm zone Z00 may be listed for output (control) points, but it is not necessary to list Z00 for input points, since this is the default zone for all alarm input devices. Zone Z00 is not activated by supervisory points.
Time Functions: Real-Time Clock Operating Instructions 4.16 Time Functions: Real-Time Clock The MS-9200UDLS includes a crystal-based clock that provides time of day, date and day of week. Time is displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time change-over is programmable and automatic. If both AC and battery are lost, the time must be reset. 4.
Operating Instructions Positive Alarm Sequence second alarm occurring anytime during the time delay will cause immediate activation of all associated outputs Presignal does not affect monitor modules programmed as waterflow, supervisory, process monitoring or remote switches. Presignal operation requires the approval of the local Authority Having Jurisdiction. 4.
Special System Timers Operating Instructions 4.21.2 Autosilence Timer If Autosilence is selected, the notification appliances, programmed as silenceable, will automatically be silenced after a programmable duration of from 5 to 30 minutes. Pressing the Drill key will restart the timer. Autosilence operation requires the approval of the local Authority Having Jurisdiction. 4.21.
Operating Instructions Walktest 4.22 Walktest Walktest is a feature which allows one person to test the fire alarm system. An audible walktest will momentarily sound the Notification Appliance Circuits in the building and store the walktest information in a file at the panel. A silent walktest will not sound the NACs but will store the walktest information in a file which can be viewed at the panel. Disabled NAC devices will not activate during walktest.
Read Status Operating Instructions The following screens will be displayed: READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER READ STATUS 1=TROUBLE REMINDER 2=TIMERS 3=NACS Read Status Screen #1 Read Status Screen #2 READ STATUS 1=ANNUNCIATORS 2=PHONE LINE 3=CENTRAL STATION READ STATUS 1=SERVICE TERMINAL 2=PRINTER/PC 3=PRINT READ STATUS 1=RELAYS 2=PROGRAM CHECK 3=HISTORY Read Status Screen #3 READ STATUS 1=TIME-DATE Read Status Screen #5 Read Status Screen #4 Read Status Screen #6 4.23.
Operating Instructions Read Status • Pre-Signal Yes/No (for detectors and monitor modules) • Zone Assignments (five maximum) • Chamber Value • Adjective/Noun descriptor • Silenceable Yes/No (for control modules) • MNS Override Enabled/Disabled (for control modules) 4.23.
Read Status Operating Instructions 4.23.4 Trouble Reminder READ STATUS 1=TROUBLE REMINDER 2=TIMERS 3=NAC Pressing 1 while viewing Read Status Screen #2 will display the following screen: TROUBLE REMINDER TROUBLE REM ON Read Status Screen #2 The screen indicates whether the Trouble Reminder feature is On or Off. 4.23.
Operating Instructions Read Status The operator can view the programmed option for each relay by pressing the corresponding number key. 4.23.
Read Status Operating Instructions Pressing 3 for ANN-BUS Options while viewing the Annunciator Screen will display the following screens: ANN-BUS ENABLED NO 2=MODULES INSTALLED 3=ANN-S/PG OPTIONS ANN-BUS Screen #1 ANN-BUS 1=ANN-80 OPTIONS ANN-BUS Screen #2 The ANN-BUS Screen #1 indicates if the ANN-BUS has been enabled YES or disabled NO. Pressing 2 for Modules Installed while viewing ANN-BUS Screen #1 will display screens for ANN-BUS Addresses 1 -8 and the devices installed at each address.
Operating Instructions Read Status • Communication Format • Event Codes 4.23.13 Service Terminal READ STATUS 1=SERVICE TERMINAL 2=PRINTER/PC 3=PRINT Pressing 1 while viewing Read Status Screen #5 will display the following screens: SERVICE TERMINAL RING COUNT Read Status Screen #5 Service Terminal Screen The Ring Count is displayed in the Service Terminal Screen. 4.23.
Read Status Operating Instructions DEVICE # DEVICE TYPE 1D001 1D002 1D003 1D004 1D005 1D006 1D007 1D008 1D009 SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) SMOKE (PHOTO) % DRIFT COMP 20 20 21 20 21 20 20 20 20 CHAMBER 1281 1281 1259 1309 1281 1322 1280 1215 1310 TIME/DATE 12:01 AM 01-08-2001 12:01 AM 01-08-2001 12:01 AM 01-08-2001 12:02 AM 01-08-2001 12:02 AM 01-08-2001 12:02 AM 01-08-2001 12:02 AM 01-08-2001 12:02 AM 01-08-2001 12:02
Operating Instructions Read Status Figure 4.1 illustrates a graphic representation of the maintenance levels: Maintenance Urgent DIRTY Maintenance Alert Acceptable Range Low Chamber Reading LOW VALUE Figure 4.1 Diagram of Maintenance Levels 4.23.16 Time-Date READ STATUS 1=TIME-DATE Read Status Screen #6 The operator can view the daylight savings time and the month and week when daylight savings time will begin and end.
Section 5: Central Station Communications The control panel transmits zone and system status reports to Central Stations via the public switched telephone network. Two supervised telephone line connections are made to interface the control panel to the telephone lines. Two optional 7 foot telephone cords are available for this purpose and can be purchased separately. The control panel supervises both telephone lines for proper voltage.
Central Station Communications Transmittal Priorities 5.1 Transmittal Priorities The integral communicator transmits highest priority events first. Events, in terms of priority, are listed below in descending order: 1. Alarms (highest priority level) Pull stations Waterflow Smoke detector Other alarm types 2. 3.
Transmittal Priorities Central Station Communications Radionics 6600 (6) 1 SIA-DCS-20 2 Ademco Contact ID Ademco 685 (1) FBI CP220FB (10) Osborne Hoffman 2000E (5) SurGard MLR-2000 (9) Silent Knight 9800 (4) SIA-DCS-8 SurGard System III (8) Silent Knight 9500 (3) 0 Format SurGard MLR2 (7) Ademco MX8000 (2) The table below shows UL listed receivers which are compatible with the MS-9200UDLS. Table 5.
Section 6: Remote Site Upload/Download Important! The FACP will automatically reset 2 minutes after completion of a user program download via the PS-Tools programming utility. To prevent program corruption, the operator must wait until this panel reset occurs before performing any panel operations. The control panel may be programmed or interrogated off-site via the public switched telephone network or locally using a USB cable.
Transferring a Program Remote Site Upload/Download Pressing 1 for Proprietary No (factory default setting), while viewing the Remote Download screen, will cause the display to toggle from Proprietary No to Proprietary Yes. Each press of the 1 key will cause the display to toggle between Proprietary No and Proprietary Yes.
Remote Site Upload/Download Transferring a Program Time-out at Control Panel Upon answering an incoming call on the primary Central Station phone line, the control panel will listen for a modem connection signal. If this signal is not received within 50 seconds, the control panel will disconnect the call. Upon successful connection (secret code verified), if no communication occurs within 30 minutes, the panel will disconnect the call.
Section 7: Power Supply Calculations 7.1 Overview This section contains instructions and tables for calculating power supply currents in alarm and standby conditions. This is a four-step process, consisting of the following: 1. Calculating the total amount of AC branch circuit current required to operate the system 2. Calculating the worst-case system current load on the control panel, when primary (AC) power is applied, to assure that the limit of the its internal power supply will not be exceeded.
Power Supply Calculations Calculating the System Current Load All currents are given in amperes (A). Table 7.2 shows how to convert milliamperes and microamperes to full amperes. To convert... Multiply Example Milliamperes (mA) to amperes (A) mA x 0.001 3 mA x 0.001 = 0.003A Microamperes (µA) to amperes (A) µA x 0.000001 300 µA x 0.000001 = 0.0003 A Table 7.2 Converting to Full Amperes 7.3.2 How to Calculate System Current Load Use Table 7.
Calculating the System Current Load Power Supply Calculations Table 7.3 contains columns for calculating current load. For each column, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 7.4 on page 162. For maximum output current available per circuit and per panel, refer to Section 1.2, “Specifications”, on page 15.
Power Supply Calculations Calculating the Battery Size 7.4 Calculating the Battery Size Use Table 7.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in AH), required to support the system upon loss of primary (AC) power. Complete Table 7.4 as follows: 1. Enter the totals from Table 7.3 on page 161, Calculation Columns 2 and 3 where shown 2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below) 3.
Appendix A: Software Zones A.1 Correlations Setup and configuration of an addressable system is different than a conventional system. In a conventional system, assignment of input devices (smoke detectors, pull stations, heat detectors, etc.) to zones is accomplished through wiring. The wiring is direct from clearly marked panel terminals to any device assigned to a particular zone. Connection of output devices (horns, bells, strobes, etc.
Software Zones Correlations Correlation of Input and Output Zones Input Devices Zones SD355 01 Output Devices CMF-300 13 SD355 02 CMF-300 05 ZONE 01 MMF-300 01 CMF-300 06 MMF-302 02 CMF-300 07 CMF-300 09 MMF-302 03 CP355 03 ZONE 02 CMF-300 08 CMF-300 10 CP300 04 SD355 05 CMF-300 11 SD355 06 SD355 07 MMF-302 04 ZONE 03 CMF-300 12 The zone correlations which are shown graphically above are also presented in Table A.1 on page 165 and Table A.2 on page 166.
Correlations Software Zones DETECTOR ZONE ASSIGNMENT Address Device Type Zone Number 01 SD355 1 FIRST HALL 51 02 SD355 1 ELEV. LOBBY 52 03 CP355 2 2ND FLOOR 53 04 CP355 2 ROOM 210 54 05 SD355 3 3RD FLOOR 55 06 SD355 3 MEZZANINE 56 07 SD355 3 MECH.
Software Zones Correlations MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address Device Type Zone Number 01 MMF-300 1 51 02 MMF-302 1, 2 52 03 MMF-302 1, 2 53 04 MMF-302 3 54 05 CMF-300 1 55 06 CMF-300 1 56 07 CMF-300 1 57 08 CMF-300 2 58 09 CMF-300 1, 2, 3 59 10 CMF-300 2 60 ADJ/NOUN Address 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74 25 75 26 76 27 77 28 78 29 79 30 80 31 81 32 82 3
Correlations Software Zones DETECTOR ZONE ASSIGNMENT Address Device Type Zone Number ADJ/NOUN Address 01 51 02 52 03 53 04 54 05 55 06 56 07 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74 25 75 26 76 27 77 28 78 29 79 30 80 31 81 32 82 33 83 34 84 35 85 36 86 37 87 38 88 39 89 40 90 41 91 42 92 43 93 44 94 45 95 46 96 47 97 48 98 49 99 Device Type
Software Zones Correlations MONITOR/CONTROL MODULE ZONE ASSIGNMENT Address Device Type Zone Number ADJ/NOUN Address 01 51 02 52 03 53 04 54 05 55 06 56 07 57 08 58 09 59 10 60 11 61 12 62 13 63 14 64 15 65 16 66 17 67 18 68 19 69 20 70 21 71 22 72 23 73 24 74 25 75 26 76 27 77 28 78 29 79 30 80 31 81 32 82 33 83 34 84 35 85 36 86 37 87 38 88 39 89 40 90 41 91 42 92 43 93 44 94 45 95 46 96 47 97 48 98 49 9
Appendix B: Default Programming The following table provides a list of the programming options and their factory default settings. Program Option Factory Default Program Option Factory Default Detector Programming Detector Type Detector Verification Detector Walktest Detector PAS Detector Presignal Detector Zone Assign. Detector Adj/Noun Module Programming Module Type Module Walktest Module Presignal Module Zone Assign. Module Adj/Noun Zone 0 Enable Zone 1 Enable Zone 2 Enable Zone 3 Enable ............
Appendix C: NFPA Standard-Specific Requirements The MS-9200UDLS has been designed for use in commercial, industrial, and institutional applications and meets the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this Appendix.
NFPA Standard-Specific Requirements NFPA 72 Auxiliary Fire Alarm System All connections are power-limited and supervised. This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions. Notes: 1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box. 2. Cut JP3 on the MS-9200UDLS main circuit board to supervise placement of 4XTMF module and circuit. 3.
NFPA Standard-Specific Requirements NFPA 72 Remote Station Protective Signaling System Notes: 1. Cut Jumper JP3 on the MS-9200UDLS main circuit board to supervise placement of the 4XTMF module. 2. Refer to “4XTMF Transmitter Module Installation” on page 39 for detailed information. RS82 Remote Station Receiver UL listed. Refer to Instruction Manual for Remote Station Receiver Model RS82. + - Polarity Shown is Normal Standby + Power-limited (Dummy load with a 4.
NFPA Standard-Specific Requirements NFPA 72 Proprietary Protective Signaling Systems MS-9200UDLS Addressable Fire Control Panel MS-9200UDLS Main Board Form-C Alarm contact programmed to activate on General Alarm. Form-C Trouble contact which will automatically activate on any Trouble condition. Form-C relay contact programmed to activate on Supervisory condition. Notes: 1. Connection between the MS-9200UDLS and the transmitter are supervised by the transmitter. 2.
NFPA Standard-Specific Requirements Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts C.1 Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value determined by the Transmitter manufacturer.
MBT-1 Municipal Box Trip - Silenceable NFPA Standard-Specific Requirements C.2 MBT-1 Municipal Box Trip - Silenceable The following figure illustrates the connection of the MBT-1 (Municipal Box Trip) between the FACP and a Local Energy Municipal Box. The use of an addressable control module programmed for General Alarm and Silenceable allows silencing of the Municipal Box without resetting the panel or box. The addressable Control Module must be programmed as Silenceable and General Alarm.
Appendix D: FACP with Keltron The following figure illustrates the connections between the FACP and Keltron Receiver/Transmitter. ! CAUTION: POSSIBLE EQUIPEMENT DAMAGE FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON MODULES ARE NOT SHOWN IN ACTUAL ORDER.
Appendix E: Wire Requirements T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations. The total resistance of any branch cannot exceed 40 ohms. The total wire length of all branches cannot exceed 10,000 feet (3,000 m). Connecting external system accessories to the MS-9200UDLS main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, gauge and run length for each MS-9200UDLS circuit.
Wire Requirements CIRCUIT CONNECTIONS Circuit Type Circuit Function SLC loop Connects to (power-limited) Addressable Devices WIRE REQUIREMENTS Recommended Wire Type and Limitations Max. Distance Feet (meters) Twisted, shielded pair 40 ohms maximum per length of Style 6 and 7 loops. 40 ohms per branch maximum for Style 4 loops 10,000 (3,000 m) 8,000 (2,400 m) 4,875 (1,450 m) 3,225 (980 m) 12 AWG (3.25 mm2): Genesis 4410, Signal 98230, Belden 9583, WPW999 14 AWG (2.
NAC Wiring Wire Requirements E.1 NAC Wiring The following table lists NAC wiring requirements for the FACP. NAC Load (Amps) Max. allowable total loop resistance (ohms) CLASS-B Max. allowable wire pair length (feet) CLASS-A Max. allowable wire pair length (feet) AWG 12 solid AWG 14 solid AWG 16 solid AWG 18 solid AWG 12 solid AWG 14 solid AWG 16 solid AWG 18 solid 0.25 12.72 3295 2072 1301 819 1648 1036 650 409 0.5 6.36 1648 1036 650 409 824 518 325 205 0.75 4.
Appendix F: HVAC Control The FACP can be programmed to shut down a building’s HVAC fans in the event of a fire. The fans cannot be restarted until the fire alarm condition has been cleared and the FACP has been reset to a normal (non-alarm) condition. IMPORTANT! This HVAC feature is not to be used for smoke control. It is only designed to shut down fans during a fire alarm condition. F.1 Control Module Operation F.1.
Monitor Module Operation HVAC Control F.2.2 HVAC OVRRIDE The HVAC OVRRIDE type code can be assigned to any addressable monitor module for the purpose of overriding or preventing the HVAC SHUTDN control modules from activating. The HVAC OVRRIDE monitor module acts globally throughout the FACP system and therefore is not programmed to a particular software zone.
Appendix G: Ademco Contact ID Format Event Code Descriptions This appendix describes the various Event Codes and their messages which are available for the Ademco Contact ID Format. G.
Ademco Contact ID Typical Printout Ademco Contact ID Format Event Code Descriptions EVENT CODE CLASSIFICATIONS 100 ALARMS Medical Fire Panic Burglary General 24 Hour 200 SUPERVISORY Fire 300 TROUBLES System Sounder/Relay System Peripheral Communication Protective Loop Sensor 400 OPEN/CLOSE REMOTE ACCESS Open/Close Remote Access Access Control EVENT MESSAGE Medical Alarms - 100 100 Medical 101 Pendant Transmitter 102 Fail to report in EMERG - Personal Emergency - # EMERG - Personal Emergency - # EM
Ademco Contact ID Format Event Code Descriptions Ademco Contact ID Typical Printout EVENT MESSAGE 151 Gas detected 152 Refrigeration 153 Loss of heat 154 Water leakage 155 Foil break 156 Day trouble 157 Low bottled gas level 158 High Temp 159 Low Temp 161 Loss of air flow ALARM - Gas Detected - # ALARM - Refrigeration - # ALARM - Heating System - # ALARM - Water Leakage - # ALARM - Foil Break - # ALARM - Day Zone - # ALARM - Low Gas Level - # ALARM - High Temperature - # ALARM - Low Temperature - # ALA
Ademco Contact ID Typical Printout Ademco Contact ID Format Event Code Descriptions EVENT MESSAGE Protection Loop Troubles - 370 370 Protection loop 371 Protection loop open 372 Protection loop short 373 Fire trouble TROUBLE - Protection Loop - # TROUBLE - Protection Loop Open - # TROUBLE - Protection Loop Short - # TROUBLE - Fire Loop - # Sensor Troubles - 380 380 Sensor trouble 381 Loss of supervision - RF 382 Loss of supervision - RPM 383 Sensor tamper 384 RF transmitter low battery TROUBLE - Sens
Ademco Contact ID Format Event Code Descriptions 186 Ademco Contact ID Typical Printout EVENT MESSAGE Test Misc.
Appendix H: Central Station Points The control panel transmits Central Station Reports in a numerical format which indicates the FACP addressable device address that is reporting. The following table indicates the Central Station Report (CS Report) number that will be transmitted and the addressable device address it represents.
Central Station Points CS Report Module Address CS Report Module Address CS Report Module Address CS Report Module Address 160 001 192 033 224 065 256 097 161 002 193 034 225 066 257 098 162 003 194 035 226 067 258 099 163 004 195 036 227 068 164 005 196 037 228 069 165 006 197 038 229 070 166 007 198 039 230 071 167 008 199 040 231 072 168 009 200 041 232 073 169 010 201 042 233 074 170 011 202 043 234 075 171 012 203 044
Appendix I: Canadian Application • The MS-9200UDLSC is supplied with the DP-9692 Dress Panel. • When installing and programming the FACP, the Canadian Option must be set to ON prior to any other panel programming (refer to “Canadian Option” on page 100 of the Programming Section of this manual). • ACS Series annunciators are not compatible for Canadian applications. • At least one ANN-LED must be installed adjacent to the FACP as it is part of the primary operator interface.
Canadian Application Optional Secondary ANN-BUS (data on connector TB8, power on TB1 Terminals 3&4 with JP6 pins 1&2 jumpered) Primary ANN-BUS (data on connector TB9, power on TB1 Terminals 1&2) in metal conduit (adjacent to FACP) ANN-LED ANN-LEDs ANN-80C FACP ANN-I/O ANN-S/PG 9200ulsc-annled8.wmf ANN-RLY ALL FIRE SYSTEM ACTIVE SYSTEM CONTROL CALL 1 13 14 2 3 15 4 16 5 17 6 18 7 19 8 20 9 21 10 22 11 23 12 24 FI When using an audio system, 6 ANN-LEDs can be used.
Canadian Application + (to remote station receiver) - + T11 T10 T9 T8 T7 T6 T11 T10 T9 T8 T7 T6 * T1 T2 T3 T4 T5 - B- + B+ * T1 T2 T3 T4 T5 + + * Terminal IDs T10 - Comm2 T1 - SLC T9 - N.C. 2 T2 - SLC + T8 - N.O. 2 T7 - Comm1 T6 - N.C. 1 T5 - N.O. 1 TB10SLC Loop Output red (+) violet black (-) violet EOLR-1 Non-resettable Aux Power 24 VDC- TB1 revpol.wmf Notes: 1. The and the must be mapped to the same zone which is programmed for supervisory operation. 2.
Index Numerics 24 Hour Test Time 121 300 Series addressable devices 20 4XTMF module 171, 172 coil resistance 39 current 39 installation 39 installation steps 40 see also Transmitter Module 14, 20 supervisory relay configuration 41 voltage 39 A AC Branch Circuit calculations 159 AC Loss Delay 95 AC Power 32 current 15 current, maximum 32 voltage 15 wiring 15, 32 Account Code 121 Acknowledge/Step 18, 133 ACM Series see also annunciator 24 ACM-16ATF Annunciator 24 ACM-32AF Annunciator 24 ACM-8RF 15 contact ra
Index C–D BB-26 19 BB-55F see also battery box 19, 21 availability 17 maximum 17 Current Draw Calculations 161 C D cabinet dimensions 30, 31 cabinet mounting 28 Calculate System Current Draw 160 Calculating the Battery Size 162 Canadian Applications 27, 189 Canadian Option 91, 100, 189 Central Station 119, 158 account code 121 communications 153 phone number 121 Phone Numbers 120 point assignments 187 report style 124 Central Station Reports 187 CHG-120F see also battery charger 22 see also remote bat
E–M Index E earth ground 32 ECC-50/100 22, 62, 101 ECC-FFT 22, 61 edit control module 82 detector 68 detector screens 69 module, monitor 76 EIA-232 60 for PC/Printer connection 16 see also Printer/PC interface 14 EIA-485 for ACS annunciators 16 for LCD-80F 16 Emergency Command Center 13 Enable 87 Enable/Disable control module 82 detector 70 module, monitor 77 End-of-Line Resistor Assembly 20 Enter key 65 EOL-C(R/W) Mounting Plate 20 Erase History 103 Error Checking 158 event code classification 183 event
Index N–P Manual programming 64 Master Program Level 1 65, 66 Medical Alert 139 MNS Override 86, 91, 99, 101 Mode key 65 Module add 75 addressing 19 delete 75 edit monitor 76 enable/disable 77 see also addressable modules 19 Module Programming 75 Monitor module 19 adjective 80 enable/disable 77 noun 80 noun/adjective 79 type 77 type action 78 Type list 77 type selection 78 Mounting cabinet 28 main circuit board 28 municipal box transmitter see also 4XTMF module 39 N NAC 15, 96, 139 Auto Silence 97 coded
R–R Index Phone Number 121 Piezo see also sounder 18 PK-CD Programming Utility 20 point assignments 187 Point Program 67 Positive Alarm Sequence 71, 142 see also PAS 14 power NAC 13 nonresettable 16 resettable 16 power supply calculations 159 power-limited relay connections 33 Power-up first time 65 Pre-signal 14, 71, 88 function 141 selection 79 Pre-signal Delay timer 95 Pre-signal timer 94 primary ANN- BUS 16, 107, 189 Primary Phone 118 primary power see also AC Power 32 printer baud rate 125 configurat
Index S–T resettable power 16, 33 current 33 Ring Count 119 Ringer Equivalence Number 25 ROME Series 57 S secondary ANN- BUS 16, 107, 189 Secondary Phone 118 Secondary Power Requirements 162 Secret Code 157 Security Features 157 sensitivity 140, 151 see also smoke detector sensitivity 140 Service Terminal 119 Signal rate 14 Signaling Line Circuit see also SLC 15 Silence Inhibit 14, 99, 142 Silenceable control module 83 NAC 97 waterflow 101 Silenceable Alarm Relay 100 silenceable circuits synchronized sig
U–Z Index U UL power-limited wiring requirements 36 see also power-limited and nonpower-limited 33 Upload/Download 156 V Verification detector 70 Verify Loops 102 View Events 102 voltage measurements 146 ranges 146 list 89 Zone Z97 71 Zone Z98 pre-signal zone 72 Zones 146, 163 see also software zones 13 Zones Disabled 88 Zones Enabled 88 Zones Installed 88 zones per device 72 W Walktest 14, 71, 83, 103 audible 103 Maintenance Level 130 operation 144 selection 79 silent 103 waterflow nonsilenceable 89,
Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009).
World Headquarters 1 Firelite Place Northford, CT 06472-1653 USA 203-484-7161 fax 203-484-7118 www.firelite.