Manual

14 MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Product Description Features and Options
Telephone Line Active LEDs
Communication Confirmation (Kissoff) LED
Touchtone/Rotary dialing
Programmable Make/Break Ratio
EIA-232 Printer/PC interface (variable baud rate)
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History file with 1,000 event capacity
Advanced fire technology features:
Automatic drift compensation
Maintenance alert
Detector sensitivity test capability (NFPA 72 compliant)
Automatic device type-code verification
Point trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with two-
stage capability
Selectable strobe synchronization per NAC
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, ACS
annunciators or ANN-80 Remote annunciator
Auto-program (learn mode) reduces installation time. Reports two devices set to the same
address
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad or optional keyboard
Optional PK-CD (contains PS-Tools utility) for local or remote Upload/Download of program
and data
Compatible with Fire-Lite’s newer series devices in LiteSpeed and CLIP mode (refer to SLC
Wiring Manual for a list of compatible addressable devices)
Compatible with legacy Fire-Lite 300 Series devices in CLIP mode only (refer to the SLC
Wiring Manual for a list of compatible addressable devices)
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
Optional ZNAC-92 Class A converter module for NACs
ANN-BUS for connection to following optional modules (cannot be used if ACS annunciators
are used):
ANN-80 Remote Annunciator
ANN-80C Remote Indicator (Canadian Applications)
ANN-I/O LED Driver
ANN-S/PG Printer Module
ANN-RLY Form-C Relay Module
ANN-LED Annunciator Module annunciates alarm, trouble and supervisory (required for
Canada and emergency signaling)