Brochure

26 • FIREYE PRIMELINE PRODUCTS
E210 CONTROL Bulletin E-2101
The E210 (220VAC) and E211 (120VAC) meet European standards for single or dual fuel
fired burners, pilot ignited or direct ignited continuous duty. The ED510 Display Module
(built-in or remote use) indicates the program sequence and reasons for burner shut-
down in English, French, Spanish, Dutch, Swedish or German. The E210 with EP113 pro-
grammers (Eng. code 21 or higher), is compatible with the ED510 display module,
providing both current and historical burner information.
Several operational characteristics of the EP113 programmer modules (with Engineering
code 21 or later) are selectable via six dipswitches located on the side of the program-
mer. These characteristics include non-recycle or recycle operation (3-P circuit), inter-
rupted or intermittent operation of terminal 5, extended purge timing, and the option to
enable or disable the requirement that the 3-P running interlock circuit is proven open at
the start of the operating cycle. A “run-check” switch on the top of the programmers
(with Eng. code 21 or later) allows the operator to stop the program sequence at any
time except MTFI. This aids in the set-up and adjustment of the burner linkages, pilot
assembly, etc.
There are four different detection methods (infrared, flame rectification, ultraviolet, and
ultraviolet self-check) and a corresponding selection of scanners.
DIMENSIONS
PART NUMBER DESCRIPTION
E210 230VAC 50/60HZ Chassis. Display ordered separately. For use with EP113 programmers only.
E211 120VAC Chassis. Display ordered separately. For use with EP113 programmers only
EB720 Replacement Chassis for E210.
EB721 Replacement Chassis for E211.
ED510 2 Line x 16 Character LCD Display. Compatible with EP programmers with Eng. code 21 or higher.
48-1836 Mounting Screw (E210/E211)
48-1805 Mounting Screw (E200/201)
60-1386-2 Wiring base - Surface mount
60-1466-2 Wiring Base - Cabinet mount
14-64 Noise Line Filter for E210/E211.
7 9/32
(185)
6
(152)
1 7/8
(48)
5 3/4
(146)
1/2” KNOCKOUT
CONTROL WITH COVER
AND WIRING BASE
4 7/8
(123.8
5 11/
16
2 7/16
(61.9)
5 1/4
(133)
7
(177.8
11/16
(17.4)
3/4
(44.4)
25/32
(19.8)
1/4
TYP
(6.35)
390
TYP
(9.9)
KNOCKOUTS
FOR
1 1/16
(27)
1 3/16
(30.2)
WIRING BASE
MOUNTING HOLES
3 5/8 (92)