Product Overview

1
®
IMPORTANT NOTE
The information provided in this bulletin is directed to competent boiler and combustion service
technicians who are experienced in the installation and operation of Fireye Flame Safety equipment.
Persons not familiar with Fireye products should contact the nearest Fireye representative or other
qualified service group.
The 45UV5 scanners as well as all other Fireye scanners, are designed to be used exclusively with
the appropriate Fireye Flame Safeguard and Burner Management controls. The application of these
scanners to other than Fireye equipment should be reviewed for approval by Fireye.
APPLICATION
Fireye 45UV5 self-checking scanners are used to detect ultraviolet emissions from fossil fuel flames
such as natural gas, coke oven gas, propane, methane, butane, kerosene, light petroleum distillates
and diesel fuels.
These 45UV5 models are used only with the Flame-Monitor, BurnerLogix, D-Series, FlameWorx,
MicroM and some P-Series Fireye control models to provide flame safeguard and monitoring sys-
tems for supervised manual, semi-automatic and fully automatic single burner boilers, process ovens
and heaters.
PRINCIPLES OF OPERATION
The 45UV5 scanners use a UV-eye detector. This detector is a sealed, gas filled, UV-sensitive tube
containing two electrodes connected to a source of AC voltage. When UV radiation of sufficient
energy falls upon the electrodes, electrons are released and the inter-electrode gas becomes conduc-
tive, resulting in an electric current flow from one electrode to the other. The current flow starts and
ends abruptly and is known as an “avalanche.”
A very intense source of UV radiation will produce several hundred avalanches or pulses per second.
With less radiation there will be fewer pulses per second. Upon total disappearance of flame, the
detector output ceases. Thus, the presence or absence of pulses is an indication of the presence or
DESCRIPTION
AND
INSTALLATION
For 45UV5 UV self-checking Scanner Models:
45UV5-1005, 45UV5-1006,
45UV5-1007, 45UV5-1008,
45UV5-1009 and 45UV5-1105
For use only with designated Fireye
®
controls
For Infrared Photocell Scanners use SC103
For non self-checking UV Scanners use SC102
SC-101
JUNE 30, 2006
APPROVED