Flame Safeguard & Combustion Controls Primeline Catalog
FLAME SAFEGUARD CONTROLS Primeline Products For over 70 years, Fireye has manufactured quality combustion control products for the commercial and industrial markets. With more than a million installations throughout the world, we are proud of our global reputation and worldwide market position. Dedicated to a constant process of innovation and service, we consistently provide safe and reliable products to our customers.
©Fireye, Inc. 2013 The names FIREYE, MicroM, SIGNATURE SCANNER, FIRETRON and FLAME-MONITOR are registered trademarks of Fireye, Inc. Products in this catalog are not necessarily shown to scale. For additional information visit our web site at www.fireye.
IMPORTANT NOTICE Periodically, Fireye receives inquiries from the field concerning the use of rebuilt controls. In years past, Fireye and other manufacturers of flame safety devices did rebuild controls. These rebuilt controls were certified by a “nationally recognized testing agency” (UL) and subject to different standards than new equipment. Essentially, all components were replaced with the exact components that were used in a new control. Only the housings and lenses (if applicable) were reused.
PART NUMBER INDEX PART NUMBER PART NUMBER PAGE PART NUMBER PAGE PAGE 59-509-20 19 65UV5-1004E 37 4-263-1 45 59-509-25 19 37 4-314-1 45 59-562-2 25 65UV51004ECEX 10-88 45 59-565 25 69ND1-1000K4 40, 44 14-64 8, 26 59-565-6 25 69ND1-1000K6 40, 44 40, 44 23-176 35 59-565-40 25 69ND1-1000K8 23-183 35 60-302 45 70D10 29 35-69 45 60-801 45 70D20 29 35-127-1 45 60-1199-1 46 70D21 29 35-127-3 45 60-1199-2 46 70D30 29 35-381-2 25 60-1257 46 70D40 29 38
PART NUMBER PAGE PART NUMBER PAGE PART NUMBER PAGE BLD500 15, 17 EP113E 27 EPD390 11 BLL510 15, 17 EP113ES 27 ERT1 12, 27 BLPS-15 25 EP113F 27 EUV1 12, 27 BLPS-25 25 EP113NL 27 EUVS4 12, 27 BLPS-30 25 EP113NR 27 FX04 25 BLPS-200 25 EP113SW 27 FX04-1 25 BLPS-300 25 EP160 10 FX20 25 BLV512 15, 17 EP161 10 FX20-1 25 E1R1 12, 27 EP163 10 FX50 25 E1R2 12 EP165 10 FX50-1 25 E1R3 12, 27 EP166 10 IT1000 15, 17, 19 E100 8 EP170 10 MART1 35
PART NUMBER PAGE PART NUMBER PAGE PART NUMBER PAGE MEC230 31 MEP236 32 NXC20 21, 23 MEC230RC 31 MEP237 33 NXC40 21, 23 MEC320 32 MEP238 32 NXCESO2-8 25 MEC320C 32 MEP290 32 NXCESO2-16 25 MEC320D 32 MEP300 33 NXCESO2-30 25 MEC320R 32 MEP304 33 NXCESO2P42, -1 25 MEC320RC 32 MEP397 33 NXCESVFD 25 MEC320RD 32 MEP437 32 NXD410 25 MEC320TS 32 MEP536 32 NXDBMB 21, 23 MEC480 32 MEP537 32 NXDBVSD 21, 23 MECD1 33 MEP560 32 NXIATS 21, 23 MECD4 33
PART NUMBER PAGE PART NUMBER PAGE UV1A3 44 ZB230IR 17 UV1A6 44 ZB230UV 17 UV1A50 44 ZB230UVSC 17 UV2 44 UV7A4 40 UV7A4W 40 UV7R4 40 UV7SC 40 UV8A 44 UV90-3 44 UV90-6 44 UV90-9 44 YB110DC 15 YB110FR 15 YB110IR 15 YB110IR2 15 YB110UV 14 YB110UVSC 14 YB230DC 15 YB230FR 15 YB230IR 15 YB230UV 15 YB230UVSC 15 YP100 15, 17 YP102 15, 17 YP113 15, 17 YP118 15, 17 YP138 15, 17 YP200 15 YP202 15 YP300 15 YP302 15 YZ300 18 YZ300P 18 YZ320 18
FLAME-MONITOR™ CONTROL Bulletin E-1101 The Flame-Monitor Series provides the proper burner sequencing, ignition and flame monitoring protection on automatically ignited oil, gas and combination fuel burners. On a safety shutdown, the display module will advise the operator that the control is in “Lockout” and indicate the cause as well as the position in the operating sequence that it occurred. Interchangeable programmer and flame amplifier modules allow complete versatility in selecting control function.
ED510 Display Module Bulletin ED-5101 The ED510 Display Module is designed to operate with the Flame-Monitor Burner Management Control System using the EP and EPD style programmer modules.1 The ED510 display is optional for EPD programmers, but is required for the EP style programmers. The ED510 display module provides the following features and capabilities • LCD backlit display with two (2) lines of sixteen (16) characters each.
EP PROGRAMMER MODULES Bulletins EP1601, EP2601, EP3801 The Fireye EP Programmer Modules are used with the E100 and E110 Flame-Monitor controls. They provide start-up programming, safe-start-check, and flame monitoring supervision. They prove high-fire purge interlock (EP100 series only), low-fire start position and fuel valve end-switch safety checks. A running interlock circuit monitors the limit switches, air flow switches, and fuel pressure switches.
EPD Programmer Modules Bulletins EPD-1601, EPD-2601, EPD-3801 The EPD programmers offer a cost effective version of the Flame-Monitor control. EPD style programmers provide the same start-up programming, safe start check, and flame monitoring supervision as their counterpart EP style programmers.
FLAME AMPLIFIER MODULES Bulletin EAMP-1 The Fireye Flame Amplifier Modules are used in conjunction with the appropriate flame scanner to provide flame scanning capability in the FLAME-MONITOR system. Fireye offers ultraviolet amplifiers (EUV1), self-check ultraviolet amplifiers (EUVS4), flame rectification amplifiers for use with flame rods and photocells (ERT1), and auto-check infrared amplifiers: E1R1 (standard model), E1R2 (high sensitivity - consult factory before use), and E1R3 (for solid fuels).
E300 EXPANSION MODULE Bulletin E-3001 The Fireye E300 Expansion Module provides increased interlock supervision capability of the Flame-Monitor control system. By wiring any of 16 interlock switches into the Expansion Module (three additional recycling interlocks and 13 additional running safety interlocks), the Flame-Monitor will automatically act as a “first out” annunciator for these interlocks.
YB110/YB230 FIREYE BURNERLOGIX™ CONTROL Bulletin BL-1001 The Fireye® BurnerLogix™ System is a microprocessor based burner management control system designed to provide the proper burner sequencing, ignition and flame monitoring protection on automatically ignited oil, gas, and combination fuel burners. In conjunction with limit and operating controls, it programs the burner/blower motor, ignition and fuel valves to provide for proper and safe burner operation.
PART NUMBER DESCRIPTION YB110IR 120 VAC input with IR auto-check amplifier YB110IR2 120 VAC input with IR auto-check amplifier (special application only -consult factory) YB110FR 120 VAC input with flame rectification amplifier YB110DC 120 VAC input with direct coupled amplifier for use with 85UVF4-1QDWR or InSight scanner (with 59497-020WR cable) YB230UV 230 VAC input with UV non self-check amplifier YB230UVSC 230 VAC input with UV self-check amplifier YB230IR 230 VAC input with IR auto-chec
ZB110/ZB230 FIREYE BURNERLOGIX™ Z CONTROL Bulletin BLZ-1001 The Fireye® BurnerLogix™ Z System expands on the standard BurnerLogix Y System by combining boiler control functions with the same burner management control found in the Y system. The result is a single compact package that can directly control the boiler's output firing rate based on either input pressure or temperature or both.
Additional functions of the BurnerLogix Z System include: • A non-volatile memory which allows the control to remember its history and present position even when power is interrupted. • A consistent flame signal read-out via display module or 4-20 mA output. • Read-out of main fuel operational hours and complete cycles via display module. • Modbus communications via RS485 multi-drop link. • Proof of fuel valve closure during off cycle.
YZ300/YZ320 FIREYE INTERLOCK ANNUCIATOR Bulletin YZEM-3001 The FIREYE YZ300 (YZ320) Interlock Annunciator Module provides increased interlock supervision capability of the BurnerLogixSystem. The Interlock Annunciator Module connects to any YB110 (YB230) or ZB110 (ZB230) BurnerLogix chassis/amplifier by means of a cable, ( P/N ED580-4, ED580-8).
INTOUCH WIRELESS MONITORING SYSTEM Bulletin INT-1000 The inTouch Wireless Monitoring System provides continuous monitoring up to 10 FlameMonitor and/or MicroM flame safeguard controls. The inTouch System also provides 4 drycontact and 4 AC power inputs. In the event of a lockout or contact closure, the inTouch system reports the condition causing the lockout and also the make, model and location of the equipment over the wireless cellular network using a wide variety of delivery methods, i.e.
NEXUS NX6100 INTEGRATED BURNER CONTROLER Bulletin NEX-6100 The Fireye NEXUS NX6100 Integrated Controller is a microprocessor based, Flame Safeguard and Parallel Positioning Combustion Controller built into one compact, user configurable package. The system consists of the Controller, Display, Temperature / Pressure Sensors, Servo-Motors and optional Comfire Software.
PART NUMBER SERVO-MOTORS FOR NX6100 NXC20 4 wire CANbus Servo-motor, 14.75 ft lbs., 20 Nm, 50/60 Hz, 24 VAC. NXC40 4 wire CANbus Servo-motor, 29.5 ft lbs., 40 Nm, 50/60 Hz, 24 VAC. PART NUMBER EXPANSION INTERFACE MODULES FOR NX6100 NXDBMB Modbus RTU interface card for PPC6000 / NX6100.
NEXUS PPC6000 SERIES FUEL AIR RATIO CONTROLER Bulletin PPC-6001 The Fireye NEXUS PPC6000 is a state of the art stand-alone parallel position system for all types of liquid or gaseous fuel fired combustion systems. When combined with a Fireye flame safeguard system such as the Fireye BurnerLogix control, the PPC6000 offers the most compact and advanced parallel positioning system available.
PART NUMBER DISPLAY MODULES FOR PPC6000 NX600 Basic CANbus display for PPC6000. No upload/download capability. NX610 CANbus display for PPC6000 with upload/download of PPC6000 data and three programmable relays PART NUMBER SERVO-MOTORS FOR PPC6000 NXC04 4 wire CANbus Servo-motor, 3 ft lbs., 4 Nm, 50/60 Hz, 24 VAC. NXC12 4 wire CANbus Servo-motor, 9 ft lbs., 12 Nm, 50/60 Hz, 24 VAC. NXC20 4 wire CANbus Servo-motor, 14.75 ft lbs., 20 Nm, 50/60 Hz, 24 VAC. NXC40 4 wire CANbus Servo-motor, 29.
NEXUS PPC4000 SERIES FUEL AIR RATIO CONTROLER Bulletin PPC-4001 The Fireye NEXUS PPC4000 is a state of the art stand-alone parallel positioning system for all types of liquid or gaseous fuel fired combustion systems. When combined with a Fireye flame safeguard system such as the Fireye BurnerLogix control, the PPC4000 offers the most compact and advanced parallel positioning system available.
Part Number Control PPC4000 Stand-alone parallel positioning controller, with up to ten (10) selectable function Modbus servo-motor outputs. User interface ordered separately. NXCESVFD Plug-in assembly provides variable frequency (VFD/VSD) capability 60-2926 Enclosure, 12.5” x 10.5” x 6.
E210 CONTROL Bulletin E-2101 The E210 (220VAC) and E211 (120VAC) meet European standards for single or dual fuel fired burners, pilot ignited or direct ignited continuous duty. The ED510 Display Module (built-in or remote use) indicates the program sequence and reasons for burner shutdown in English, French, Spanish, Dutch, Swedish or German. The E210 with EP113 programmers (Eng. code 21 or higher), is compatible with the ED510 display module, providing both current and historical burner information.
PART NUMBER AMPLIFIERS EUV1 UV Amplifier for UV1A, UV8A, UV2, 45UV3 ElR1 Infrared Amplifier for 48PT2 Scanner ElR3 Infrared Amplifier (w/o Oil Fog Rejection Circuit) for 48PT2 Scanner EUVS4 ERT1 PART NUMBER Self-Check Amplifier for 45UV5-1007,-1008, -1009 Rectification Amplifier for 45CM1, 69ND1 PROGRAMMERS EP113E English, selectable purge, selectable recycle/nonrecycle, selectable intermittent/interrupted operation, 3 & 5 sec. MTFI.
E320 EXPANSION MODULE Bulletin E-3001 The Fireye E320 Expansion Module provides increased interlock supervision capability of the Flame-Monitor system. The Expansion Module connects to any EB720 Flame-Monitor chassis with a ribbon cable. It is used exclusively with the 220V/240V Flame-Monitor system. By wiring any of sixteen interlock switches into the expansion module, the Flame-Monitor display will automatically act as a “first-out” annunciator for these interlocks.
D-SERIES SOLID STATE BURNER MANAGEMENT CONTROLS Bulletin D-4041 FIREYE® Series D40-41 Burner Management Controls provide ignition and flame failure protection for manually started oil or gas burners. Plug-in Amplifier Modules permit the selection of ultraviolet, repetitive self-check ultra-violet, AUTOCHECK infrared, or rectification methods of flame detection. The control system includes a safe start check, effective on each start.
DIRECT REPLACEMENT UPGRADES No wiring changes necessary (see Notes) Use existing wiring base and flame scanner.
MicroM SERIES Bulletins MC-5000, MAMP-1, MOPT-1, MP-5201, UM-2 The Fireye MicroM Flame Safeguard controls are compact, modular burner management systems designed to provide automatic ignition and continuous flame monitoring for commercial sized heating and process burners firing any type of fuel. The MicroM is designed to be backward compatible with existing M-Series controls.
PART NUMBER MicroM Programmer Models, for use with MEC120/MEC230 chassis MEP100 Relight operation, 10 sec. PTFI MEP101 Relight operation, allow flame signal during “off cycle” MEP102 Non-recycle on flame fail, 5 second PTFI MEP103 Fixed 10 second PTFI, 10 second MTFI, re-try once on pilot failure, post purge MEP104 Non-recycle on flame fail, 10 second PTFI MEP105 Non-recycle on flame fail, lockout on air flow open with flame present, 10 FTFI.
PART NUMBER Programmers for use with MEC320 / MEC480 Chassis MEP300 Relight operation on main flame fail, lockout on PTFI and MTFI flame fail, 10 sec PTFI (fixed), 5 sec pilot proving, 5 sec MTFI. MEP304 5 sec purge, 10 sec PTFI (fixed), 5 sec pilot proving, 10 sec MTFI, interrupted pilot, interrupted ignition, non-recycle on flame fail. MEP397 15 sec purge, provides interrupted ignition, interrupted pilot, non re-cycle on flame fail.
M-SERIES II Bulletins C -4000, C -4001, C -4002 CHASSIS (shown with Programmer Module) Fireye modular M-Series II Flame Safeguard controls are compact, modular burner management systems. They provide automatic ignition and continuous flame monitoring for commercial-sized heating and process burners using gas and/or light oil fuels.
PART NUMBER DESCRIPTION MC120 120 VAC 50/60 Hz Chassis. MC120E 120 VAC 50/60 Hz Chassis. Meets European EN230, EN298 approval. MC120P 120 VAC 50/60 Hz Chassis with Remote Reset and Post Purge Capability. MC120R 120 VAC 50/60 Hz Chassis with Remote Reset Capability. MC120RE 120 VAC 50/60 Hz Chassis with Remote Reset Capability. Meets European EN230, EN298 approval. MC230 230 VAC Chassis. MC230R PART NUMBER 230 VAC Chassis with Remote Reset Capability.
M-SERIES TO M-SERIES II TO MICROM CROSS REFERENCE LISTING M-SERIES M-SERIES II REPLACEMENT MODULES MicroM REPLACEMENT MODULES Part Number Chassis Amplifier Programmer Programmer Dipswitch #8 UVM1D MC120 MAUV1T MP100 N/A MEC120 MEUV1 MEP100 N/A UVM1F MC120 MAUVI MP100 N/A MEC120 MEUV4 MEP100 N/A TFM1D MC120 MART1T MP100 See Note #1 MEC120 MERT1 MEP100 N/A TFM1F MC120 MART1 MP100 See Note #1 MEC120 MERT4 MEP100 N/A UVM2 MC120 MAUV1 MP230 OFF MEC120 MEUV4 MEP2
65UV5 INTEGRATED FLAME SCANNER WITH INTERNAL FLAME RELAY Bulletin CU-104 The 65UV5 flame scanner is a micro-processor based flame scanner that incorporates an internal single pole, single throw (normally open) flame relay with a fixed on/off threshold to provide flame on/flame off indication, eliminating the need of an external flame amplifier. The scanner utilizes an ultra-violet tube type sensor, and electromechanical self-checking shutter mechanism.
MB Series MULTI-BURNER CONTROL Bulletin MB-6001 The Fireye Multi-Burner Monitoring System controls the start-up sequence and monitors the flame of up to 20 individual gas, oil, or combination gas/oil burners connected to a common valve train. Its dynamic on-board testing checks for faulty relays, proof of valve closure, high and low fire switch interlocks, and shorted air switch. Exclusive to the unit is its ability to specifically identify which burner caused the initial flame failure.
MB SERIES FLAME SENSOR MODULES Bulletin MBPF-1001 The MBPF-100S, MB-600PF, MBPF-200S and MBPF-202S modules provide visual indication and electrical output that signal the user regarding flame presence in a combustion chamber. The module uses Fireye optical ultra-violet scanners and/or flame rod to sense flame presence independently or as components in a burner management system.
PART NUMBER DESCRIPTION Scanners for use with MB Series UV7A4 UV7A4W Ultra-violet scanner, non-self check applications, 1/2” NPT mount, 4’ lead with insulating coupling. Ultra-violet scanner, non-self check applications, NEMA 4, 1/2” NPT mount, 4’ lead with insulating coupling. UV7R4 Ultra-violet scanner, non-self check applications, 1/2” NPT, 90°, 6’ lead with insulating coupling. UV7SC Ultraviolet scanner, self check applications, 120VAC, 1” NPT mount. (MBPF-100S only).
Blank Page FIREYE PRIMELINE PRODUCTS • 41
FLAME SCANNERS AND APPLICATIONS The following Fireye flame scanners are used in conjunction with the appropriate Fireye flame safeguard controls to provide reliable flame detection on a variety of burner applications and fuel types. UVIA Bulletin SC-102 Ultraviolet miniature non self-checking scanners. The UV1A is suitable for fuel gases and no. 2 oil. Non-replaceable tube. Mounting collar 1/2" NPT. Available with 3 ft (UV1A3), 6 ft. (UV1A6), or 50 ft. (UV1A50) of tray-rated cable.
UV3-1050 Bulletin SC-103 A rugged diecast housing that mounts on 3/4 inch pipe with setscrew. Vertical mounting of UV tube provides greater sensitivity. UV tube is replaceable (4-314-1). Scanner is non self-checking. 4 ft (1200mm) lead wires. Must be installed with metal shielding over this canner leads. 55UV5-1007, -1009 Bulletin SC-106 Self-checking ultraviolet scanner is for continuously fired applications where recycling is infrequent or absent.
PART NUMBER DESCRIPTION USE WITH BULLETIN Ultraviolet Scanners UV1A-1-CEX UV1A3 UV1A6 ATEX Exd IIC T6 explosion-proof housing with UV1A scanner. 1 /2" NPT Connector, 3 ft. (914mm) tray-rated cable. Non self-checking. 1 /2" NPT Connector, 6 ft. (1828mm) tray-rated cable. Non self-checking. 1 UV1A50 UV2 UV8A /2" NPT Connector, 50 ft. tray-rated cable.Non self-checking. 3 /8" NPT Connector, 3 ft. (914mm) tray-rated cable. Non self-checking. 1 /2" NPT 90 head, 6 ft. wire, no cable.
ACCESSORIES FOR FIREYE PRODUCTS 4-263-1 Firetron Cell for 48PT2 Infrared Scanner. C-Series, D-Series and Flame-Monitor. 35-69 4-314-1 10-88 Ultraviolet Tube for use in 45UV5-1005, 1009, 45UV2, 45UV3-1050, C-Series, DSeries and Flame-Monitor controls. 35-127-1 (NPT) 35-127-3 (BSP) Set of 3 Orifice Plugs. Drilled 1/16”, 1/8”, 3/ 16”, 1/2”. Pipe Thread. Also available: 1015, Blank orifice plug for drilling to any size required.
60-1199-1,2 Sealing coupling with quartz window. Seals scanner sight pipe against excessive firebox pressure. 1" pipe thread. Used with 45UV1, 45UV2, 45UV3, 45UV5. 60-1199-1 (NPT), 60-1199-2 (BSP) 61-2914-1 60-1257, 60-1290 Sealing union with quartz window (601257). 60-1290 has quartz lens to increase scanner sensitivity. For use with UV1A/UV1B scanners. 61-3263-1 Shutter, Bracket, and Lens Assembly for 45UV5-1005 thru -1009.
CROSS REFERENCE TABLE Notes are referenced at the end of the table.
CURRENT MODEL COMBINATIONS OBSOLETE TYPE AND MODEL NOTES CONTROL 26CF6-5023 2, 4 26CF6-RC-3A 1, 2, 3, 4 DISPLAY PROGRAMMER AMPLIFIER E110 ED510 EP260 E1R1 14 E110 ED510 EP260 E1R1 26RJ8-CB-3 14 E110 ED510 EP160 E1R1 26RJ8-1000 14, 15, 16 26RJ8-1001 14, 15, 16 26RJ8-1002 14, 15, 16 26RJ8-1003 14, 15, 16 26RJ8-1004 14, 15, 16 26RJ8-1006 14, 15, 16 26RJ8-1008 14, 15, 16 E110 ED510 EP260 E1R1 E110 ED510 EP160 E1R1 E110 ED510 EP260 E1R1 E110 ED510 EP260 E1R1
OBSOLETE TYPE AND MODEL CURRENT MODEL COMBINATIONS NOTES CONTROL 26SJ5-5910 CONSULT FACTORY 29RF5-1000 14, 15 29RF5-1001 14, 15 29RF5-1002 14, 15 29RF5-1005 14, 15 29RF5-1009 14, 15 29RF5-1015 14, 15 29RF5-1103 14, 15 29RF5-6009 14, 15 29RF5-6015 14, 15 29RF5-6103 14, 15 DISPLAY PROGRAMMER AMPLIFIER E110 ED510 EP260 E1R1 25 MEC120 — MEP100 MERT4 TFM1F 25 MEC120 — MEP100 MERT4 TFM2 23, 25 MEC120 — MEP230 MERT4 MEC120 — MEP230H MERT4 MEC120 — MEP230 MEUV4
NOTES FOR CROSS REFERENCE TABLE 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. Requires new wiring base 60-1466-2 or 60-1386-2. Re-use existing scanner. Add timer if terminal 10 is used for open damper (30 seconds I.C.T.O). Make earth ground connection. E110 requires terminal 13 to be powered on call for heat. If there is no fuel valve end switch, make sure terminal 13 is powered from terminal 3. Refer to bulletin C-500 for starting circuit change.
GENERAL REFERENCE TABLES NEMA Standard Classification Codes for Flame Safety Control Enclosures NEMA 1— NEMA 2— NEMA 3— NEMA 4 — NEMA 5 — NEMA 6 — NEMA 7— NEMA 8 — NEMA 9 — NEMA 10 — NEMA 11 — NEMA 12 — General Purpose. For indoor protection, where conditions are not unusually severe. Driptight. Designed to exclude falling moisture or dirt. Particularly applicable to cooling rooms, laundries, etc., where condensation is prevalent. For indoor use. Weather Resistant (weatherproof).
Conversion Factors for Boiler Ratings 1. 2. 3. 4. 5. 6. Boiler Horsepower Pounds Steam Per Hour BTU/Hour (Output) Megawatts Output 20 690 660,500 .20 40 1,380 1,339,000 .39 60 2,070 2,008,500 .59 Boiler Horsepower 33,475 BTU’s per hour (output) 34.5 lbs. steam per hour (from and at 210o F to 100o C. 9810.6 watt (output) 1 lb. steam per hour 970 BTU’s per hour (output) (from 212o F or 100o C) 284.3 watts (output) 80 2,760 2,678,000 .78 100 3,450 3,347.500 .98 150 5,200 5.
LITERATURE LIST FOR FIREYE PRODUCTS PART NUMBER DESCRIPTION BD-5001 BLV512, BLL510 display modules for use with BurnerLogiX BL-1001 YB110/YB230 Fireye® BurnerLogiX™ BLZ-1001 ZB110/ZB230 Fireye® BurnerLogiX™ BLZPTS-1 Pressure and temperature sensors for the BurnerLogiX CG-14 Domestic Price Sheet CG-14X Export Price Sheet CP-47 Test Unit for Flame Monitor, C and D Series C-4000 Modular M-Series II C-4001 Programmer Modules M-Series II C-4002 Amplifier Modules M-Series II C-90 Test Unit
PART NUMBER DESCRIPTION MBPF-1001 MBPF-100S, 200S, 202S, MB-600PF Sensor Modules MC-5000 MicroM Controller-Installation Manual MOPT1 MicroM Plug-In Option Boards MP-5201 MicroM Programmer Modules MM-2 Modernization Adapter 60-1765 MTS-1 M-Series II Trouble Shooting Guide NEX-6101 NEXUS NX6100 Integrated Burner Control System PPC-6001 PPC6000 fuel air ratio controller PPC-4001 NEXUS PPC4000 fuel air ratio controller NEX-3004 Nexus FX04 series 4 Nm servo motor for PPC4000 NEX-3020 Nexus
HOW TO IDENTIFY FIREYE CONTROLS Beginning January 1976 Fireye adopted the US national standard date coding for all units whereby the first two digits identify the year and the second two digits identify the week of the year. Example 9212—twelfth week of 1992. “M” Series Controls “C” Series Controls UVM, TFM Controls have their date code stamped on the side of the chassis.
FIREYE TERMS AND CONDITIONS OF SALE shall be shipped with shipping charges prepaid and securely packed so as to THE FOLLOWING TERMS AND CONDITIONS SHALL GOVERN THE ENTIRE RELATIONSHIP BETWEEN FIREYE (FIREYE) AND THE PURCHASER INCLUDING, BUT NOT LIMITED TO, ALL NEGOTIATIONS, ORDERS, ACCEPTANCES, SALES AND DELIVERIES.
FIREYE DISTRICT SALES OFFICES UNITED STATES SALES OFFICES Boston Area 3 Manchester Road Derry, NH 03038 (603) 432-4100 FAX: (603) 432-1570 Cleveland Area 5258 Transportation Blvd. Garfield Heights, OH 44125 (216) 518-2950 FAX: (216) 274-9117 Columbus Area 1356 Norton Avenue Columbus, OH 43212 (614) 291-5380 FAX: (216) 274-6379 Minnesota Area 2914 Pennsylvania Avenue, South St. Louis Park, MN 55426 (952) 926-3088 FAX: (952) 926-3374 New York Area 151 W.
3 Manchester Rd. • Derry, NH 03038 • USA Tel: 603-432-4100 • Fax: 603-432-1570 • www.fireye.