10 • FIREYE PRIMELINE PRODUCTS
EP PROGRAMMER MODULES Bulletins EP1601, EP2601, EP3801
The Fireye EP Programmer Modules are used with the E100 and E110 Flame-Monitor
controls. They provide start-up programming, safe-start-check, and flame monitoring
supervision. They prove high-fire purge interlock (EP100 series only), low-fire start posi-
tion and fuel valve end-switch safety checks. A running interlock circuit monitors the limit
switches, air flow switches, and fuel pressure switches.
The EP programmers de-energize all fuel valve circuits with 4 seconds (max.) following a
flame failure(2 seconds for the EP165, EP166, EP265), or at the end of the pilot-trial-for-
ignition period if no flame is detected. A modulator motor circuit is provided (EP100 and
EP200 series only). The programmers have a Check-Run switch to stop the control
sequence to aid in the set-up and check out of the burner and its associated interlocks.
The programmers store the burner cycles, hours, and lockout history.
The EP programmers offer the following selectable functions: purge timing, prove the
Running Interlock circuit is open at the start of the cycle, recycle or non-recycle operation
(EP300 series only), intermittent or interrupted operation of terminal 6 (EP300 series
only). The programmers include an RJ45 connector for the ED510 display module, and
two RJ12 connectors for Modbus Communications.
PART NUMBER DESCRIPTION
EP160 30 Sec. Purge, 10 & 15 Sec. TFI, 4 Sec FFRT, Non-Recycle, Modulation
EP161 30 Sec. Purge, 10 & 30 Sec. TFI, 4 Sec FFRT, Non-Recycle, Modulation
EP163 Selectable Purge (30 sec min.), selectable TFI via ED510 display, Non-Recycle.
EP165 30 Sec. Purge, 10 Sec. TFI, 2 Sec FFRT, Pilot Stabilization, Non-Recycle, Modulation.
EP166 Selectable Purge (30 sec min.), Pilot Stabilization, Non-Recycle, 10 and 15 sec TFI programmer.
EP170 30 Sec. Purge, 5 & 10 Sec. TFI, 4 Sec FFRT, Early Spark Termination, Non-Recycle, Modulation
EP174 Selectable Purge (30 sec min.), 5 and 10 sec. TFI, Non-Recycle, Early Spark Termination.
M-D circuit must be proven through the completion of MTFI.
EP177 Early Spark Termination. ED510 to Select Purge (30 sec min.), Prove Air Flow, Prove High Fire,
Prove Low Fire, and Post Purge. Early Spark Termination. Infinite Hold on M-D circuit.
EP100F Selectable Purge, Selectable TFI, 4 Sec FFRT, Non-Recycle, Modulation, French language.
EP100S Selectable Purge, Selectable TFI, 4 Sec FFRT, Non-Recycle, Modulation, Spanish language.
EP260 30 Sec. Purge, 10 & 15 Sec. TFI, 4 Sec FFRT, Recycle, Modulation
EP265 30 Sec. Purge, 10 & 15 Sec. TFI, 2 Sec FFRT, Pilot Stabilization, Recycle, Modulation.
EP270 30 Sec. Purge, 5 & 10 Sec. TFI, 4 Sec FFRT, Early Spark Termination, Recycle, Modulation
EP200F Selectable Purge, Selectable TFI, 4 Sec FFRT, Recycle, Modulation, French language.
EP200S Selectable Purge, Selectable TFI, 4 Sec FFRT, Recycle, Modulation, Spanish language.
EP380 30 Sec. Purge, 5 & 10 Sec. TFI, 4 Sec FFRT, Recycle, No Modulation
EP381 15 Sec. Purge, 5 & 10 Sec. TFI, 4 Sec FFRT, Recycle, No Modulation
EP382 0 Sec. Purge, 5 & 10 Sec. TFI, 4 Sec FFRT, Recycle, No Modulation
EP383 Selectable Purge, 5 and 10 Sec. TFI, Selectable Recycle / Non-Recycle via ED510, No Modulation,
No Agency Approvals.
EP387 Selectable Purge (15 sec. min.), Selectable TFI, Selectable Recycle / Non-Recycle, No Modulation,
infinite hold on M-D circuit.
EP390 90 Sec. Purge, 5 & 10 Sec. TFI, 4 Sec FFRT, Recycle, No Modulation
EP300F 4 Sec FFRT, Selectable Purge, Selectable Recycle, Non-Recycle, No Modulation, French language.
EP300S 4 Sec FFRT, Selectable Purge, Selectable Recycle, Non-Recycle, No Modulation, Spanish language.
PROGRAMMERS FOR USE WITH INTEGRATED FLAME SCANNERS
EP178 Keypad adjustable purge time, PTFI, MTFI, post purge, early spark termination, pilot proving period, and indefinite hold on
low fire start. Non-Recycle, Modulation. For use with EDC1 and EDC2 amplifiers and 85UVF4-1QDWR, 85IRF4-
1QDWR,or InSight scanners (with 59-497-020WR cable).
EP378 Keypad adjustable purge time, PTFI, MTFI, post purge, early spark termination, pilot proving period, and indefinite hold on
low fire start. Selectable Recycle, Non-Recycle. No modulation. For use with EDC1 and EDC2 amplifiers and 85UVF4-
1QDWR, 85IRF4-1QDWR or InSight scanners (with 59-497-020WR cable).