Use and Care Manual

5 6 7
REGULAR MAINTENANCE
T
his unit has been designed to be as maintenance-free as possible, but there
a
re a few simple things you must do to keep it working properly:
Test it at least once a week.
Clean the Alarm at least once a month; gently vacuum the outside of the
A
larm using your household vacuum’s soft brush attachment. Test the
A
larm. Never use water, cleaners or solvents since they may damage the
u
nit.
Relocate the unit if it sounds frequent unwanted alarms. See “Where This
A
larm Should Not Be Installed” for details.
When the battery back-up becomes weak, the Alarm will “chirp” about
o
nce a minute (the low battery warning). You should replace the battery
i
mmediately to continue your protection. This Alarm must have AC or
b
attery power to operate. If AC power fails, and the battery is dead
o
r missing, the Alarm cannot operate.
DO NOT spray cleaning chemicals or insect sprays directly on or near the
Alarm. DO NOT paint over the Alarm. Doing so may permanently damage the
Alarm.
C
HOOSING A REPLACEMENT BATTERY:
T
his CO Alarm requires two standard AA batteries. The following batteries
a
re acceptable as replacements: Duracell MN1500. These batteries are
a
vailable at many local retail stores.
Always use the exact batteries specified by this User’s Manual.
D
O NOT use rechargeable batteries. Clean the battery contacts and
a
lso those of the device prior to battery installation. Install batteries
c
orrectly with regard to polarity (+ and -).
Please dispose of or recycle used batteries properly, following any
l
ocal regulations. Consult your local waste management authority
o
r recycling organization to find an electronics recycling facility in
y
our area. DO NOT DISPOSE OF BATTERIES IN FIRE. BATTERIES
M
AY EXPLODE OR LEAK.
Keep battery out of reach of children. In the event a battery is
swallowed, immediately contact your poison control center, your
physician, or the National Battery Ingestion hotline at 202-625-3333
as serious injury may occur.
Actual battery service life depends on the Alarm and the environment in which
it is installed. All the batteries specified above are acceptable replacement
batteries for this unit. Regardless of the manufacturer’s suggested battery life,
you MUST replace the battery immediately once the unit starts “chirping” (the
“low battery warning”).
WHAT YOU NEED TO KNOW ABOUT CO
W
HAT IS CO?
CO is an invisible, odorless, tasteless gas produced when fossil fuels do not
burn completely, or are exposed to heat (usually fire). Electrical appliances
t
ypically do not produce CO.
T
hese fuels include: Wood, coal, charcoal, oil, natural gas, gasoline, kerosene,
a
nd propane.
C
ommon appliances are often sources of CO. If they are not properly main-
t
ained, are improperly ventilated, or malfunction, CO levels can rise quickly.
C
O is a real danger now that homes are more energy efficient. “Air-tight”
h
omes with added insulation, sealed windows, and other weatherproofing
c
an “trap” CO inside.
SYMPTOMS OF CO POISONING
T
hese symptoms are related to CO POISONING and should be discussed
w
ith ALL household members.
M
ild Exposure: Slight headache, nausea, vomiting, fatigue (“flu-like” symptoms).
M
edium Exposure: Throbbing headache, drowsiness, confusion, fast heart rate.
E
xtreme Exposure: Convulsions, unconsciousness, heart and lung failure.
E
xposure to Carbon Monoxide can cause brain damage, death.
T
his CO Alarm measures exposure to CO over time. It alarms if CO levels
a
re extremely high in a short period of time, or if CO levels reach a certain
m
inimum over a long period of time. The CO Alarm generally sounds an alarm
b
efore the onset of symptoms in average, healthy adults. Why is this impor-
t
ant? Because you need to be warned of a potential CO problem while you
c
an still react in time. In many reported cases of CO exposure, victims may be
a
ware that they are not feeling well, but become disoriented and can no longer
r
eact well enough to exit the building or get help. Also, young children and
p
ets may be the first affected. The average healthy adult might not feel any
s
ymptoms when the CO Alarm sounds. However, people with cardiac or
r
espiratory problems, infants, unborn babies, pregnant mothers, or elderly
p
eople can be more quickly and severely affected by CO. If you experience
e
ven mild symptoms of CO poisoning, consult your doctor immediately!
WEEKLY TESTING
NEVER use an open flame of any kind to test this unit. You might
a
ccidentally damage or set fire to the unit or to your home. The
b
uilt-in test switch accurately tests the unit’s operation as required
b
y Underwriters Laboratories, Inc. (UL). NEVER use vehicle exhaust!
E
xhaust may cause permanent damage and voids your warranty.
DO NOT stand close to the Alarm when the horn is sounding.
Exposure at close range may be harmful to your hearing. When
testing, step away when horn starts sounding.
I
t is important to test this unit every week to make sure it is working
p
roperly.
P
ress the Test/Silence button on the Alarm cover until alarm sounds.
I
f the Alarm does not test properly:
1
. Make sure the AC power is applied and batteries are fresh and installed
c
orrectly.
2. Test the unit again.
If the Alarm is still not working properly, replace it immediately. Refer to the
“Limited Warranty” at the end of this manual.
If there is still a problem, do not try to fix the Alarm yourself. This will
void your warranty!
H
OW CAN I PROTECT MY FAMILY FROM CO
POISONING?
A
CO Alarm is an excellent means of protection. It monitors the air and sounds
a
loud alarm before Carbon Monoxide levels become threatening for average,
h
ealthy adults.
A
CO Alarm is not a substitute for proper maintenance of home appliances.
T
o help prevent CO problems and reduce the risk of CO poisoning:
Clean chimneys and flues yearly. Keep them free of debris, leaves, and
nests for proper air flow. Also, have a professional check for rust and
corrosion, cracks, or separations. These conditions can prevent proper
air movement and cause backdrafting. Never “cap” or cover a chimney
in any way that would block air flow.
Test and maintain all fuel-burning equipment annually. Many local gas
or oil companies and HVAC companies offer appliance inspections for
a nominal fee.
Make regular visual inspections of all fuel-burning appliances. Check
appliances for excessive rust and scaling. Also check the flame on the
burner and pilot lights. The flame should be blue. A yellow flame means
fuel is not being burned completely and CO may be present. Keep the
blower door on the furnace closed. Use vents or fans when they are
available on all fuel-burning appliances. Make sure appliances are
vented to the outside. Do not grill or barbecue indoors, or in garages
or on screen porches.
Check for exhaust backflow from CO sources. Check the draft hood on
an operating furnace for a backdraft. Look for cracks on furnace heat
exchangers.
Check the house or garage on the other side of shared wall.
Keep windows and doors open slightly. If you suspect that CO is
e
scaping into your home, open a window or a door. Opening windows
a
nd doors can significantly decrease CO levels.
I
n addition, familiarize yourself with all enclosed materials. Read this
m
anual in its entirety, and make sure you understand what to do if your
C
O Alarm sounds.
REGULATORY INFORMATION FOR CO ALARMS
WHAT LEVELS OF CO CAUSE AN ALARM?
Underwriters Laboratories Inc. Standard UL2034 requires residential CO
Alarms to sound when exposed to levels of CO and exposure times as
described below. They are measured in parts per million (ppm) of CO over
time (in minutes).
UL2034 Required Alarm Points*:
If the alarm is exposed to 400 ppm of CO, IT MUST ALARM BETWEEN
4 and 15 MINUTES.
If the alarm is exposed to 150 ppm of CO, IT MUST ALARM BETWEEN
1
0 and 50 MINUTES.
If the alarm is exposed to 70 ppm if CO, IT MUST ALARM BETWEEN
60 and 240 MINUTES.
* Approximately 10% COHb exposure at levels of 10% to 95% Relative
H
umidity (RH).
T
he unit is designed not to alarm when exposed to a constant level of 30 ppm
f
or 30 days.
C
O Alarms are designed to alarm before there is an immediate life threat.
S
ince you cannot see or smell CO, never assume it’s not present.
An exposure to 100 ppm of CO for 20 minutes may not affect average,
healthy adults, but after 4 hours the same level may cause headaches.
An exposure to 400 ppm of CO may cause headaches in average, healthy
a
dults after 35 minutes, but can cause death after 2 hours.
Standards: Underwriters Laboratories Inc. Single and Multiple Station carbon
monoxide alarms UL2034.
A
ccording to Underwriters Laboratories Inc. UL2034, Section 1-1.2: “Carbon
m
onoxide alarms covered by these requirements are intended to respond to
t
he presence of carbon monoxide from sources such as, but not limited to,
e
xhaust from internal-combustion engines, abnormal operation of fuel-fired
a
ppliances, and fireplaces. CO Alarms are intended to alarm at carbon
m
onoxide levels below those that could cause a loss of ability to react to the
d
angers of Carbon Monoxide exposure.” This CO Alarm monitors the air at
t
he Alarm, and is designed to alarm before CO levels become life threatening.
T
his allows you precious time to leave the house and correct the problem.
T
his is only possible if Alarms are located, installed, and maintained as
d
escribed in this manual.
Gas Detection at Typical Temperature and Humidity Ranges: The CO
Alarm is not formulated to detect CO levels below 30 ppm typically.
Audible Alarm: 85 dB minimum at 10 feet (3 meters).
POTENTIAL SOURCES OF CO IN THE HOME
Fuel-burning appliances like: portable heater, gas or wood burning fireplace,
gas kitchen range or cooktop, gas clothes dryer.
Damaged or insufficient venting: corroded or disconnected water heater
vent pipe, leaking chimney pipe or flue, or cracked heat exchanger, blocked
or clogged chimney opening.
Improper use of appliance/ device: operating a barbecue grill or vehicle in
an enclosed area (like a garage or screened porch).
Transient CO Problems: “transient” or on-again-off-again CO problems can
be caused by outdoor conditions and other special circumstances.
The following conditions can result in transient CO situations:
1. Excessive spillage or reverse venting of fuel appliances caused by outdoor
conditions such as:
Wind direction and/or velocity, including high, gusty winds. Heavy air in
the vent pipes (cold/humid air with extended periods between cycles).
Negative pressure differential resulting from the use of exhaust fans.
• Several appliances running at the same time competing for limited fresh
air.
Vent pipe connections vibrating loose from clothes dryers, furnaces, or
water heaters.
Obstructions in or unconventional vent pipe designs which can amplify
the above situations.
2. Extended operation of unvented fuel burning devices (range, oven, fireplace).
3. Temperature inversions, which can trap exhaust close to the ground.
4. Car idling in an open or closed attached garage, or near a home.
These conditions are dangerous because they can trap exhaust in your home.
Since these conditions can come and go, they are also hard to recreate during
a CO investigation.
FINDING THE SOURCE OF CO AFTER AN ALARM
Carbon monoxide is an odorless, invisible gas, which often makes it difficult to
locate the source of CO after an alarm. These are a few of the factors that can
make it difficult to locate sources of CO:
House well ventilated before the investigator arrives.
Problem caused by “backdrafting.”
Transient CO problem caused by special circumstances.
Because CO may dissipate by the time an investigator arrives, it may be difficult
to locate the source of CO. BRK Brands, Inc. shall not be obligated to pay
for any carbon monoxide investigation or service call.
GENERAL LIMITATIONS OF CO ALARMS
T
his CO Alarm is intended for residential use. It is not intended for use in
i
ndustrial applications where Occupational Safety and Health Administration
(
OSHA) requirements for Carbon Monoxide Alarms must be met. This device
i
s not intended to alert hearing impaired residents.
C
O Alarms may not waken all individuals. If children or others do not readily
w
aken to the sound of the CO Alarm, or if there are infants or family members
w
ith mobility limitations, make sure that someone is assigned to assist them
i
n the event of an emergency.
This CO Alarm will not sense CO that does not reach the sensors. It will
only sense CO at the sensor. CO may be present in other areas. Doors or
other obstructions may affect the rate at which CO reaches the sensors.
C
O Alarms may not be heard. The alarm horn loudness meets or exceeds
c
urrent UL standards of 85 dB at 10 feet (3 meters). However, if the CO Alarm
i
s installed outside the bedroom, it may not wake up a sound sleeper or one
w
ho has recently used drugs or has been drinking alcoholic beverages. This
i
s especially true if the door is closed or only partly open. Even persons who
a
re awake may not hear the alarm horn if the sound is blocked by distance or
c
losed doors. Noise from traffic, stereo, radio, television, air conditioner, or
o
ther appliances may also prevent alert persons from hearing the alarm horn.
T
his CO Alarm is not intended for people who are hearing impaired.
This CO Alarm is not a substitute for life insurance. Though this CO Alarm
warns against increasing CO levels, BRK Brands, Inc. does not warrant or
imply in any way that they will protect lives. Homeowners and renters must
still insure their lives.
This CO Alarm is not foolproof. Like all other electronic devices, this CO
Alarm has limitations. It can only detect CO that reaches the sensors. It may
not give early warning if the source of CO is in a remote part of the home,
away from the alarm device.
T
his CO Alarm has a limited life. Although this CO Alarm and all of its
p
arts have passed many stringent tests and are designed to be as reliable as
p
ossible, any of these parts could fail at any time. Therefore, you must test this
d
evice weekly. The unit should be replaced immediately if it is not operating
p
roperly.
Once a minute, the alarm sounds 3 “chirps”, and
the Green light flashes three times.
MALFUNCTION SIGNAL.
Based on its Self Test
diagnostics, the unit has detected a malfunction.
The unit needs to be replaced.
Units under warranty should be returned to
manufacturer for replacement. See “Limited
Warranty” for details.
The horn “chirps” once a minute. Low battery warning. Battery is low or missing. Replace the battery. Avoid interrupting AC power.
If your Alarm does this... It means... You should...
G
reen light is OFF. Unit will not alarm when you
p
ress the Test/Silence button.
U
nit may not be receiving any power. Check the AC power supply. Make sure fresh
b
atteries are installed to power the battery back-up*.
Green light flashes ON, once a minute (horn is silent).
Alarm is not receiving AC power.
Unit is operating on
battery back-up.
Check the AC power supply.
TROUBLESHOOTING GUIDE
Alarm goes back into alarm after you pressed the
Test/Silence button.
CO levels are still potentially dangerous. Refer to “If Your CO Alarm Sounds” for details on
how to respond to an alarm. If anyone is feeling ill,
EVACUATE your home immediately and call 911.
If you have any questions that cannot be answered by reading this manual, call Consumer Affairs: 1-800-323-9005.
*For a list of acceptable replacement batteries, see “Regular Maintenance.”
The light flashes (Green) and the horn sounds
5 “chirps” every minute.
END OF LIFE SIGNAL.
CO Alarm needs to be replaced.
Immediately replace the CO Alarm.
The horn sounds constantly with no pattern and
cannot be silenced.
Unit malfunction. Unit needs to be replaced. Units under warranty should be returned to
manufacturer for replacement. See “Limited
Warranty” for details.
Alarm sounds frequently even though no high levels
of CO are revealed in an investigation.
The Alarm may be improperly located. Refer to
“Where to Install This Alarm.”
Relocate your alarm. If frequent alarms continue,
have home rechecked for potential problems. You
may be experiencing an intermittent CO problem.
LIMITED WARRANTY
BRK Brands, Inc., ("BRK") the maker of First Alert
®
brand products warrants that for a period of seven years from the date of purchase, this product will be free from
defects in material and workmanship. BRK, at its option, will repair or replace this product or any component of the product found to be defective during the warranty
period. Replacement will be made with a new or remanufactured product or component. If the product is no longer available, replacement may be made with a similar
product of equal or greater value. This is your exclusive warranty.
This warranty is valid for the original retail purchaser from the date of initial retail purchase and is not transferable. Keep the original sales receipt. Proof of purchase is
required to obtain warranty performance. BRK dealers, service centers, or retail stores selling BRK products do not have the right to alter, modify or any way change
the terms and conditions of this warranty.
This warranty does not cover normal wear of parts or damage resulting from any of the following: negligent use or misuse of the product, use on improper voltage or
current, use contrary to the operating instructions, disassembly, repair or alteration by anyone other than BRK or an authorized service center. Further, the warranty
does not cover Acts of God, such as fire, flood, hurricanes and tornadoes or any batteries that are included with this unit.
BRK shall not be liable for any incidental or consequential damages caused by the breach of any express or implied warranty. Except to the extent prohibited by
applicable law, any implied warranty of merchantability or fitness for a particular purpose is limited in duration to the duration of the above warranty. Some states,
provinces or jurisdictions do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied warranty lasts, so the
above limitations or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights that vary from state to state or
province to province.
How to Obtain Warranty Service
Service: If service is required, do not return the product to your retailer. In order to obtain warranty service, contact the Consumer Affairs Division at 1-800-323-9005,
7:30 AM - 5:00 PM Central Standard Time, Monday through Friday. To assist us in serving you, please have the model number and date of purchase available when
calling. 25 Spur Drive, El Paso, TX 79906
Battery: BRK Brands, Inc. make no warranty, express or implied, written or oral, including that of merchantability or fitness for any particular purpose with respect
to battery.
Printed in Mexico M08-0150-014 Q 07/12
First Alert
®
is a registered trademark of the First Alert Trust.
1 2
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.
T
his unit was shipped with a user’s manual that contains important
i
nformation about its operation. If you are installing this unit for use by others,
y
ou must leave this manual—or a copy of it—with the end user.
TABLE OF CONTENTS
B
asic Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
I
nstallation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
W
here To Install This Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Where This Alarm Should Not Be Installed . . . . . . . . . . . . . . . . . . . . . . . . .2
Before You Begin Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
How To Install This CO Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
H
ow Your Alarm Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
I
f Your CO Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
What To Do if CO is Detected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Using the Silence Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Using the Peak CO Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Understanding the Light, Horn, and Display Patterns . . . . . . . . . . . . . . .3-4
W
eekly Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5
R
egular Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
W
hat You Need To Know About CO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-6
W
hat is CO? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Symptoms of CO Poisoning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
F
inding the Source of CO After an Alarm . . . . . . . . . . . . . . . . . . . . . . . . . .5
Potential Sources of CO in the Home . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
H
ow Can I Protect My Family From CO Poisoning? . . . . . . . . . . . . . . . . .6
R
egulatory Information For CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
G
eneral Limitations Of CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
©
2012 BRK Brands, Inc. All rights reserved.
Distributed by BRK Brands, Inc.
3
901 Liberty Street Road, Aurora, IL 60504-8122
C
onsumer Affairs: (800) 323-9005 www.firstalert.com
BASIC SAFETY INFORMATION
Dangers, Warnings, and Cautions alert you to important operating
i
nstructions or to potentially hazardous situations. Pay special
a
ttention to these items.
The CO Alarm is not designed to detect fire or any other gas. It will
o
nly indicate the presence of carbon monoxide gas at the sensor.
C
arbon monoxide gas may be present in other areas.
Do not stand too close to the unit when the alarm is sounding. It is
loud to wake you in an emergency. Exposure to the horn at close
range may harm your hearing.
Do not paint over the unit. Paint may clog the openings to the sensing
chambers and prevent the unit from operating properly.
This unit must be powered by a 24-hour circuit. Be sure the circuit
c
annot be turned off by a switch, dimmer, or ground fault circuit
i
nterrupter. Failure to connect this unit to a 24-hour circuit may
p
revent it from providing constant protection.
This Alarm must have AC or battery power to operate. If AC power
fails and the battery is dead or missing, the alarm cannot operate.
Test the Alarm once a week. If the Alarm ever fails to test correctly,
h
ave it replaced immediately! If the Alarm is not working properly, it
c
annot alert you to a problem.
This Carbon Monoxide Alarm is intended for residential use and is
n
ot suitable for use in hazardous locations as defined in the National
E
lectrical Code.
This product is intended for use in ordinary indoor locations of family
l
iving units. It is not designed to measure CO levels in compliance with
O
ccupational Safety and Health Administration (OSHA) commercial or
i
ndustrial standards. Individuals with medical conditions that may
m
ake them more sensitive to carbon monoxide may consider using
w
arning devices which provide audible and visual signals for carbon
m
onoxide concentrations under 30 ppm. For additional information on
c
arbon monoxide and your medical condition contact your physician.
F
CC Compliance
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC rules. These limits are
designed to provide reasonable protection against harmful interference in
a residential installation. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that the interference will not occur in a
particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the equip-
ment off and on, the user is encouraged to try to correct the interference by
one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that of
the receiver.
Consult the dealer or an experienced radio or TV technician for help.
Warning: Changes or modifications to the product, not expressly approved
by First Alert / BRK Brands, Inc., could void the user’s authority to operate
the equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
PLUG-IN CARBON MONOXIDE ALARM
WITH BATTERY BACK-UP AND SILENCE
FEATURES
USER’S MANUAL
Printed in Mexico
M08-0150-014 Q 07/12
Model CO615
WHERE THIS ALARM SHOULD NOT BE INSTALLED
T
o avoid causing damage to the unit, to provide optimum protection, and
to prevent unnecessary alarms, Do NOT locate this Alarm:
In garages, kitchens, crawl spaces and unfinished attics. Avoid extremely
dusty, dirty or greasy areas. Installation in these areas could lead to
nuisance alarms, may expose the sensor to substances that could damage
or contaminate it, or the Alarm may not be heard by persons in other areas
of the home, especially if they are sleeping.
In the garage, vehicle exhaust can contain some carbon monoxide. These
l
evels are higher when the engine is first started. Within hours of starting a
v
ehicle and backing it out of the garage, the levels present over time can
a
ctivate the Alarm and become a nuisance.
In the kitchen, some gas appliances can emit a short burst of CO upon
start-up. This is normal. If your CO Alarm is installed too close to these
appliances, it may alarm often and become a nuisance.
Keep units at least 20 feet (6 meters) from the sources of combustion
particles (stove, furnace, water heater, space heater) if possible. In areas
where a 20-foot (6m) distance is not possible in modular, mobile, or
smaller homes, for example it is recommended the Alarm be placed as
far from these fuel-burning sources as possible. The placement recom-
mendations are intended to keep these Alarms at a reasonable distance
from a fuel-burning source, and thus reduce “unwanted” alarms. Unwanted
alarms can occur if an Alarm is placed directly next to a fuel-burning
source. Ventilate these areas as much as possible. If you must install the
Alarm near a cooking or heating appliance, install at least 5 feet (1.5
meters) from appliance.
In extremely humid areas. This Alarm should be at least 10 feet (3 meters)
f
rom a shower, sauna, humidifier, vaporizer, dishwasher, laundry room,
u
tility room, or other source of high humidity.
In direct sunlight.
In turbulent air, like near ceiling fans or open windows. Blowing air may
prevent CO from reaching the sensors.
In areas where temperature is colder than 40˚ F (4.4˚ C) or hotter than
1
00˚ F (37.8˚ C). These areas include non-airconditioned crawl spaces,
u
nfinished attics, uninsulated or poorly insulated ceilings, porches, and
g
arages.
Less than 12 inches (305 mm) away from fluorescent lights. Electrical
noise” can interfere with the sensor.
A
VOIDING DEAD AIR SPACES
Dead air” spaces may prevent CO from reaching the Alarm. To avoid dead
a
ir spaces, stay at least 4 inches (102 mm) away from corners where walls or
c
eilings and walls meet.
Recommended Placement
INSTALLATION
WHERE TO INSTALL THIS ALARM
The National Fire Protection Association (NFPA) recommends that a CO Alarm
should be centrally located outside of each separate sleeping area in the
immediate vicinity of the bedrooms. For added protection, install additional
CO Alarms in each separate bedroom, and on every level of your home.
In general, install Carbon Monoxide Alarms:
WHERE YOU CAN HEAR THE ALARM FROM ALL SLEEPING AREAS
In or near bedrooms and living areas or wherever you suspect a CO
exposure is likely.
On each level of a multi-level home.
Improper location can affect the sensitive electronic components in this Alarm.
Please see “Where this Alarm Should Not Be Installed”.
GARAGE
SUGGESTED AREAS FOR INSTALLING ADDITIONAL CO ALARMS
BEDROOM
BEDROOM
HALL
LIVING ROOM
KITCHEN
BASEMENT
BEDROOM
REQUIRED TO MEET NFPA RECOMMENDATIONS
BEFORE YOU BEGIN INSTALLATION
Make sure the alarm is not receiving excessively noisy power.
E
xamples of noisy power could be major appliances on the same
c
ircuit, power from a generator or solar power, light dimmer on the
s
ame circuit or mounted near fluorescent lighting. Excessively noisy
p
ower may cause damage to your Alarm.
F
ind the pair of self-adhesive labels included with this CO Alarm.
• On each label write in the phone number of your emergency responder
(like 911) and a qualified appliance technician.
Place one label near the CO Alarm, and the other label in the “fresh air”
l
ocation you plan to go if the alarm sounds.
HOW TO INSTALL THIS CO ALARM
IMPORTANT! Read all instructions before using this product.
Tools you will need: Screwdriver, drill.
1
. Determine the best location for your CO Alarm.
2. Your Alarm is equipped to be mounted as a corded unit or a direct plug
unit. The unit can be plugged directly into a wall outlet. If your outlets are
mounted horizontally, refer to “If Outlet is Mounted Horizontally (Sideways)”.
If the adapter is taken out of the unit, the Alarm can be installed high on
the wall, while the adapter is plugged into a wall outlet.
ACTIVATING THE BATTERY BACK-UP
Activate the battery back-up by installing the two
(2) AA batteries. The battery is for back-up only
and is not intended to power the Alarm for an
extended period of time in the absence of AC.
The Alarm will light-up the display briefly to indicate the unit is receiving power.
DIRECT PLUG ALARM INTO AN OUTLET
This Alarm can be plugged directly into a wall outlet located close to the floor.
1. Choose a standard UNSWITCHED 120V AC outlet.
2. Plug Alarm in.
IF OUTLET IS MOUNTED HORIZONTALLY (SIDEWAYS)
If you are going to use your Alarm as a direct plug into an outlet that is
mounted horizontally (sideways), you may want to rotate the adapter 90º,
as follows:
1. With back of unit facing you (AC blades on your left), place your left thumb
on adapter release and grab AC blades with your right hand to release the
left side.
2. Repeat for the other side adapter thumb release. This will allow adapter to
slide out.
3. Remove adapter.
4. Rotate the adapter 90º and snap firmly back into place.
5. Plug Alarm into AC outlet.
WALL MOUNTED ALARM
Installation tips for power cord models: The power cord option provides
more flexibility in mounting locations and allows the Alarm to be easily
installed at or above eye level.
NOTE: If you mount the Alarm high on a wall, make sure it is at least 4 inches
(102 mm) down from the ceiling. Any higher than this, it will be in “dead air”
space and carbon monoxide may not reach the sensor.
NOTE: Do not cover the Alarm with a curtain.
To install for a wall-mount, you will need to pull out the removable adapter and
power cord, as follows:
1. Repeat steps 1 to 3 as described above in “to rotate the adapter”.
2. With adapter out, pull out power cord and unwrap it.
3. Insert the screws provided until head is approx. 1/8 inch (3 mm) from wall
(if mounting in plaster board or drywall, drill 3/16 inch (5 mm) hole and use
plastic anchor provided).
4. Hook the Alarm over the screw onto the keyhole in back of unit.
5. Plug power cord into AC outlet.
120VAC ~ 60Hz, 0.09 A
3 4
1
. Test/Silence Button:
P
ress and hold to
a
ctivate test, or to
s
ilence the alarm.
2
. Display Button: Press
t
o recall highest CO
l
evel recorded
3. POWER Light (GREEN)
4. Display
5
. (Behind the Cover)
A
larm Horn: 85 dB
a
udible alarm for
t
est, alarm, and unit
m
alfunction warning.
6. Battery Compartment
(Behind the Door)
7
. Open door here
UNDERSTANDING THE LIGHT, HORN, AND DISPLAY PATTERNS
Horn Display
C
ondition LED
NORMAL AC POWER LED is Green.
BATTERY BACK-UP POWER Green LED is flashing once every 45
seconds.
DURING TESTING LED flashes Red in sync with the
horn, simulating an Alarm condition.
LOW OR MISSING BATTERY Green LED On if AC power is present
CARBON MONOXIDE ALARM LED flashes Red in sync with horn
MALFUNCTION SIGNAL LED flashing Green 3 times in sync
with 3 chirps
END OF LIFE LED flashing Green 5 times in sync
with 5 chirps
LOW BATTERY SILENCE LED is Green.
PRE-ALARM CONDITION
CO IS PRESENT
Green power LED On if AC power is
present
Silent Flashing battery icon.
The CO alarm horn pattern
(4 beeps, pause, 4 beeps) is issued.
During the simulated
CO alarm, “CO” is
displayed along with
a full alarm level.
Several ppm CO
levels are also
displayed and
the alarm level is
shown increasing.
A chirp is issued about every
minute.
Battery icon will
show either 1 bar
or an empty icon.
3 chirps every minute “Err” is displayed.
5 chirps every minute “End” is displayed.
Silent “bat” and
“SILENCE”
are displayed.
Repeating
4 beeps, pause
“CO” alternating
with the ppm
number, a full level,
and “EVACUATE”.
Silent
“CO” alternating with the ppm number.
The level will indicate relative CO
exposure level.
Silent All segments
of display are
turned on for
a short time
upon initial
power. Then
the battery level icon is displayed.
USING THE SILENCE FEATURE
N
E
VER disconnect the power to your Alarm to silence the horn—use the
S
ilence Feature. Disconnecting the Alarm removes your protection!
The Silence Feature is intended to temporarily silence the horn while
y
ou identify and correct the problem.
To use the Silence Feature, press the Test/Silence button until the horn
i
s silent.
If the Test/Silence button is pressed while the Alarm is in the silence
mode, the alarm will start sounding again.
WHEN THE CO ALARM IS SILENCED...
T
he CO Alarm will remain silent for up to 4 minutes. While the Alarm is
s
ilenced, it will continue to monitor the air for CO. After 4 minutes, if CO levels
r
emain potentially dangerous the horn will start sounding again.
The Silence Feature is intended to temporarily silence the Alarm horn. It will
not correct a CO problem.
IF THE CO ALARM SOUNDS:
1. Operate the Test/Silence button.
2. Call your emergency services, fire department or 911. Write down the
number of your local emergency service here:
_______________________________________________________________
3
. Immediately move to fresh air—outdoors or by an open door or window.
D
o a head count to check that all persons are accounted for. Do not re-
e
nter the premises, or move away from the open door or window until the
emergency services responder has arrived, the premises have been aired
out, and your CO Alarm remains in its normal condition.
4
. After following steps 1-3, if your CO Alarm reactivates within a 24-hour
p
eriod, repeat steps 1-3 and call a qualified appliance technician to
i
nvestigate for sources of CO from fuel-burning equipment and appliances,
a
nd inspect for proper operation of this equipment. If problems are identi-
f
ied during this inspection have the equipment serviced immediately. Note
a
ny combustion equipment not inspected by the technician, and consult
t
he manufacturers’ instructions, or contact the manufacturers directly, for
m
ore information about CO safety and this equipment. Make sure that
m
otor vehicles are not, and have not, been operating in an attached
g
arage or adjacent to the residence. Write down the number of a qualified
a
ppliance technician here:
_______________________________________________________________
IF YOUR CO ALARM SOUNDS
WHAT TO DO IF CARBON MONOXIDE IS DETECTED
Actuation of your CO Alarm indicates the presence of carbon monoxide
(CO) which can kill you. In other words, when your CO Alarm sounds, you
must not ignore it!
USING THE PEAK CO MEMORY
T
he CO Memory Feature lets you check the highest level of CO recorded.
T
o check CO Memory:
1. Press the Display button until the peak CO level is displayed.
To clear CO Memory:
1. Automatically resets after 24 hours.
2a. While checking CO memory, press or hold the Display
button until “CLEAR” is displayed.
b. Press or hold the Display button until the CO Memory is
cleared.
3
. Remove all power; unplug the Alarm and remove the batteries.
N
OTE:
T
he highest CO level will be saved for 24 hours. DO NOT clear the
C
O Memory reading if you plan to call someone to investigate a CO problem!
C
lear the CO Memory reading only after the investigator has checked your
h
ome. If the investigator will not arrive within the 24 hour time period before
t
he unit automatically resets, be sure to write down the peak level.
TEST THE ALARM
1.
Make sure the Alarm is receiving AC power. Under normal operation, the
Green indicator light will shine continuously.
If the Green power indicator
light does not light, recheck connections. If connections are correct and
the Green power indicator still does not light, the unit should be replaced
immediately.
2
. Press and hold the test button until the alarm sounds. You will hear the
s
ignal that indicates the presence of carbon monoxide.
When testing the Alarm, have someone else check that the Alarm can be
heard easily from the sleeping areas. The unit should be located where it
can wake you if it alarms at night.
SILENCING THE LOW BATTERY WARNING
This Silence Feature can temporarily quiet the low battery warning “chirp” for
up to 8 hours if AC power is present. You can silence the low battery warning
“chirp” by pressing the Test/Silence button on the Alarm cover until you see
the Green LED flicker, acknowledging the button-press.
The display will flash “SILENCE” for 8 hours while the low battery warning
“chirp” silence feature is activated. After 8 hours, the low battery “chirp” will
resume. The Alarm will continue to operate as long as AC power is supplied.
However, replace the battery as soon as possible, to maintain protection in
event of a power outage.
N
OTE: For any location, make sure no door or other obstruction could keep
c
arbon monoxide from reaching the Alarm.
2
3
5
4
1
7
6
HOW YOUR ALARM WORKS
THE COVER OF YOUR ALARM
CONFORMS TO
UL STD 2034
SILENCING THE END OF LIFE SIGNAL
T
his silence feature can temporarily quiet the End of Life warning “chirp” for
u
p to 2 days. You can silence the End of Life warning “chirp” by pressing the
T
est/Silence button. The horn will chirp, acknowledging that the End of Life
f
eature has been activated.
After approximately 2 days, the End of Life “chirp” will resume.
For your records, please record:
Date Purchased: _______________________________
Where Purchased: ____________________________________________
Date Installed: ____________/____________Month/Year
Replace alarm 7 years after installation. Please write the date in the
space provided:
_____________/____________Month/Year
The alarm will also provide an audible End-of-Life Signal approximately
7 years after installation to remind you to replace the unit.
The End-of-Life Signal can be silenced for up to 2 days. Do not unplug
the alarm or remove the batteries until you get replacement.
I
NSTALLATION, Continued

Summary of content (2 pages)